ETC URGD

FRENCH CYLINDRICAL
URGD
SEMICONDUCTOR PROTECTION FUSES
PROTISTOR® FUSES
600V - 660V AC
URGD from 63 up to 250A
SIZES: 27 X 60mm
Features / Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
➤ 600V-660V AC Voltage Rating
➤ aR Class according to VDE 636-23 and IEC 269.4
➤ Model according to NF C 63210 and 63211 with
built-in blown fuse indication
APPLICATIONS DATA
Voltage
rating
UN( VAC )
Class
660 V
URGD
600 V
URGD
Current
rating
IN( A )
pre-arcing
I2t @ 1 ms
I2tp (A2s)
Total clearing I2t @ UN
I2tt (A2s)
63
80
100
125
160
200
405
860
1620
3425
6480
13700
1840
3750
6800
13600
24600
61500
250
29600
107000
Watt losses
Tested
interrupting rating
0.8 IN
IN
12
13.5
15
16
17
18.5
22
24.6
27
29.5
32.5
35.7
21
40
200 kA
@ 660 V
200 kA @ 600 V
Minimum operating voltage for trip-indicator: 20 V
PART NUMBERS
27x60 - With blown fuse trip-indicatior
Ø 27
60,3
TYPE
VOLTAGE
CURRENT
RATING
URGD
660 V
63
80
100
125
160
200
URGD
600 V
250 A
7
Ø5
D 96
A
A
A
A
A
A
REF #
CATALOG NO.
6.621
6.621
6.621
6.621
6.621
6.621
CP
CP
CP
CP
CP
CP
URGD
URGD
URGD
URGD
URGD
URGD
27x60/ 63
27x60/ 80
27x60/100
27x60/125
27x60/160
27x60/200
A
B
C
D
E
F
076820
076821
076822
076823
076824
076825
621 CP URGD 27x60/250 W 076264
FRENCH CYLINDRICAL
URGD
SEMICONDUCTOR PROTECTION FUSES
Melting Time-Current Data
D
Tolerance for the mean pre-arcing current ± 8%
These curves indicate, for each rated current, the pre-arcing time vs. the R.M.S. pre-arcing current.
Clearing I2t vs. AC Operating Voltage
Peak arc Voltage
63 to 200A URGD
63 to 200A URGD
K
1,2
Um(V)
2000
1
0,8
0,6
1000
0,4
0,2
0
200
400
600
U(V)
250A URGD
K
1,2
Correction factor to
determine the clearing I2t of
a fuse operating below its
rated voltage.
0
100 200 300 400 500 600 700
250A URGD
Um(V)
2000
1
0,8
0,6
1000
0,4
0,2
0
100 200 300 400 500 600
U(V)
0
D 97
100 200 300 400 500 600 700
These curves determine the
peak arc voltage across the
fuse terminals as a function of
the applied voltage.