ETC CLP2ET1C115

Conductive Sensors
2-point level controller
Type CL with teach-in
• Conductive level controller
• Teach-in of sensitivity – operating resistance from
220Ω to 220KΩ
• For filling or emptying applications
• Low-voltage AC electrodes
• Easy installation on DIN rails or with 11 pin circular
plug
• Rated operational voltage:
24 VAC/DC, 115 VAC or 230 VAC
• Output 2x5A/250 VAC DPDT relay
• LED indication for: Calibration, faulty operation and
relay status
Product Description
Ordering Key
µ-Processor
based
level
controller for liquids with a
wide sensitivity range (like
sewage water, chemicals, salt
water etc.).
Type
DIN rail mounting
Inputs
Function
Adjustment
Outputs
Relay versions
Power supply
Max./min. control of charging/
discharging. The sensitivity is
adjustable by means of the
teach-in function.
2 X 5A DPDT relay output.
CLD2ET1CM24
Type Selection
Mounting
Relay
Ordering no.
Supply: 24 VAC/DC
Ordering no.
Supply: 115 VAC
Ordering no.
Supply: 230 VAC
DIN-rail
DPDT
CLD2ET1CM24
CLD2ET1C115
CLD2ET1C230
CLP2ET1CM24
CLP2ET1C115
CLP2ET1C230
11-p circular plug
Specifications
Rated operational voltage (UB)
Pin 2 & 10
230
115
924
Rated insulation voltage
Rated impulse withstand
voltage
4 kV (1.2/50 µs) (line/neutral)
Rated operational power
AC supply
AC/DC supply
5 VA
5 VA / 5 W
Delay on operate (tV)
< 300 mS
Outputs
Rated insulation voltage
Relay Rating (AgCdO)
Resistive loads
Small induc. Loads
AC1
DC1
or
AC11
DC13
Mechanical life (typical)
Electrical life (typical)
Level probe supply
AC1
195 to 265 VAC, 45 to 65 Hz
98 to 132 VAC, 45 to 65 Hz
19.2 to 28.8 VAC/DC
<2.0 kVAC (rms)
250 VAC (rms) (cont./elec.)
µ (micro gap)
5 A / 250 VAC (2500 VA)
1 A / 250 VDC (250 W)
5 A 25 VDC (250 W)
0,4 A 250 VAC
0,4 A / 30 VDC
≥ 30 x 106 operations
@ 18’000 imp/h
> 250’000 operations
Max. 12 VAC
Level probe current
Max. 2.5 mA
Sensitivity
220Ω to 220KΩ
Factory preset: 47KΩ
Specifications are subject to change without notice (08.12.2005)
Dielectric voltage
>2.0 KVAC (rms)
(contacts / electronics)
Rated impulse withstand volt.
4 kV (1.2/50 µS) (contacts /
electronics) (IEC 664)
Operating frequency (f)
Relay output
1 HZ
Response time
1 s (3.5 s with filter)
Environment
Overvoltage category
Degree of protection
Pollution degree
III (IEC 60664)
IP 20 /IEC 60529, 60947-1)
2 (IEC 60664/60664A,
60947-1)
Temperature
Operating
Storage
-20º to +70ºC (-4º to + 158º)
-50º to +85ºC (-58º to +185ºF)
Housing material
NORYL SE1, light grey
Weight
AC supply
AC/DC supply
200 g
125 g
Approvals
UL508, CSA
CE marking
Yes
1
CLD2ET1CM24
Mode of Operation
(In the diagram this electrode
is shown by the dotted line).
Example 1
(Din-rail)
Y2
Hi
Filter
The
signal
delay
is
selectable from 1 second or
3 seconds, and works for
the on/off switching of the
output relays.
and min. control. The relays
react to the low alternating
current created when the
electrodes are in contact
with the liquid.
The reference (Ref) must be
connected to the container
or if the container consists
of a non-conductive material,
to an additional electrode.
(To be connected to pin Y3).
Lo
DIP-switch setting
Select the needed function
on the DIP-switches, so that
the desirable application
occurs. Press the pushbutton in front of the controller shortly, until the green
LED flashes once. The DIPswitch setting will now be
read by the controller.
other electrodes are in contact with the liquid –
approximately 1 cm. Press
the “teach” pushbutton at
the front of the controller for
approximately 2 seconds,
until the green LED turns
OFF. The controller will now
auto-adjust itself according
to the resistance of the
measuring liquid. If the
resistance of the liquid is
outside the maximum range
handled by the controller,
the green LED will flash
quickly for a period of 2
seconds, indicating a wrong
teach-in.
REF
Connection cable
2, 3, or 4 conductor PVC
cable, normally screened.
Cable length: max. 100 m.
The resistance between the
cores and the ground must
be at least 220k. Normally, it
is recommended to use a
screened cable between
probe and controller, e.g.
where the cable is placed in
parallel to the load cables
(mains). The screen has to be
connected to Y3 (reference).
12
14
Y3
Y1
A1
22
24
A2
11 21
Teach-in:
Make sure that the reference
electrode and one of the
Example 1
The diagram shows the level
control connected as max.
Function: Charge or Discharge
The Controller can be used as a
minimum-maximum control for
one system.
ON
DIP switches
1
1
2
2
Discharge
Charge
Filter off
Filter on
ON
Charging
Charging or discharging
Power Supply
X-REFERENCE
TERM
PLUG
Y1
6
Y2
5
Y3
22
A1
A2
11
7
8
2
10
1
12
14
21
24
4
3
11
9
Time
Power supply
LO electrode in liquid
HI electrode in liquid
Relay on pumping contact (make)
Discharging
Power supply
HI electrode in liquid
LO electrode in liquid
Relay on pumping contact (make)
2
Specifications are subject to change without notice (08.12.2005)
CLD2ET1CM24
Operating Schedule
The following schedule provides an overview of the setup and failure situations
Situation
Condition
Action
Read DIP-switch
setting
The DIP-switch setting has
to match one of the
descriptions written in
”mode of operation”
Press the Teach-button in
front of the controller shortly
until the green control lamp
turns off. Release the teach
button immediately
Fill the tank with the liquid to
be measured until the
second longest electrode is
immersed approx. 1cm
Press the Teach button in
front of the controller for
approx. 2 seconds until the
green control lamp turn off
continuously. Release the
teach button
Teach-in
Failure
indication
The Green lamp is
flashing fast for approx. 2
seconds after a teach-in
operation
Green Control lamp
Control the electrode for
short-cut connections.
Control that the resistance of
the measured liquid is within
the specified range
Teach button
Green lamp
Teach button
Green lamp
Teach button
Green lamp
Wiring Diagram
Din-rail version
Plug version
A1
Hi
Lo
12 14 22 24
2
Hi
Lo
Y2
Y1
Y3
A2
11
21
4
3
8
9
5
6
7
10
1
11
(PE)
(PE)
Ref
Ref
Dip Switch Settings
ON
DIP switches
1
1
2
2
Discharge
Charge
Filter off
Filter on
ON
Specifications are subject to change without notice (08.12.2005)
3
CLD2ET1CM24
Dimension Drawings
Din-rail version
45
21
41,5
60,2
63
Plug version
81
35,5
35,5
Delivery Contents
Accessories
• 11 pole corcular socket
• Mounting rack
4
ZVD11
SM13
• Amplifier
• Packaging: Carton box
• Manual
Specifications are subject to change without notice (08.12.2005)