ETC DUC01DB23500V

Monitoring Relays
1-Phase True RMS AC/DC Over and Under Voltage
Types DUC01, PUC01
DUC01
• TRMS AC/DC over+under, over+over or
under+under voltage monitoring relays
• Selection of measuring range by DIP-switches
• Measuring ranges from 2 to 500 V AC/DC
• Adjustable voltage on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 1 or 2 x 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DUC01) or plug-in module (PUC01)
• 45 mm Euronorm housing (DUC01)
or 36 mm plug-in module (PUC01)
• LED indication for relay, alarm and power supply ON
• Galvanically separated power supply
PUC01
Product Description
DUC01 and PUC01 are precise TRMS AC/DC over+under,
over+over or under+under
voltage (selectable by DIPswitch) monitoring relays. The
voltage levels are adjustable
separately and have their own
time delay.
Owing to the built-in latch
Ordering Key
function, the ON-position of
the relay output can be
maintained. Inhibit function
can be used to avoid relay
operation when not desired
(maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay.
Housing
Function
Type
Item number
Output
Power supply
Range
DUC 01 D B23 500V
Type Selection
Mounting
Output
Supply: 24 VDC
Supply: 24/48 VAC
Supply: 115/230 VAC
DIN-rail
Plug-in
DPDT
SPDT
DUC 01 D 724 500V
PUC 01 C 724 500V
DUC 01 D B48 500V
PUC 01 C B48 500V
DUC 01 D B23 500V
PUC 01 C B23 500V
Input Specifications
Output Specifications
Input
Voltage level
Output
Measuring ranges
2 to 20 V AC/DC
5 to 50 V AC/DC
20 to 200 V AC/DC
50 to 500 V AC/DC
DUC01: Terminals Y1, Y2
PUC01: Terminals 5, 7
Internal resis.
Max. volt.
> 500 kΩ
350 V
> 500 kΩ
350 V
> 500 kΩ
600 V
> 500 kΩ
600 V
Max. voltage for 1 s
Note:
The input voltage cannot
raise over 300 VAC/DC
with respect to ground
(PUC01 only)
Contact input
DUC01
PUC01
Disabled
Enabled
Latch disable
1000 V
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
2 x SPDT relays (DUC01)
1 x SPDT relays (PUC01)
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Terminals Z1, Y1
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
Specifications are subject to change without notice (21.10.00)
1
DUC01, PUC01
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2 (DUC01)
2, 10 or 11, 10
(PUC01)
724:
B48:
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Reaction time
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
DC supply
AC supply
2 kV
4 kV
4 kV
4 kV
4 kV
4 kV
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
Indication for
Power supply ON
Alarm ON
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
5 VA
3W
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-Marking
1 s ± 0.5 s or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 100 ms
< 100 ms
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
LED, green
LED, red (flashing 2 Hz
during delay time)
1 or 2 x LED, yellow
(EN 60529)
IP 20
3 (DUC01), 2 (PUC01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
45 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 250 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Mode of Operation
DUC01 and PUC01 monitor
both AC and DC over+under,
over+over or under+under
voltage.
Example 1
(no contact input - under+over
voltage - 2 x SPDT relays
(1 x SPDT for PUC01))
DUC01: One relay operates
when the voltage drops
below the under voltage set
point for more than the
respective delay time. It
releases when the voltage
exceeds the set level plus
the set hysteresis. The other
relay operates when the voltage exceeds the over voltage set point for more than
the respective delay time. It
releases when the voltage
drops below the set level
minus hysteresis (the hysteresis is the same for both
set levels).
2
PUC01: The relay operates
when the voltage drops
below the under voltage set
level for more than the
respective set delay time or
when it exceeds the over
voltage set level for more
than the respective set delay
time. The relay releases when
the voltage exceeds the
under voltage set level plus
hysteresis and it drops
below the over voltage set
level minus hysteresis (the
hysteresis is the same for
both set levels).
Example 2
(latch enabled active - under+
under voltage - 2 x SPDT
relays (1 x SPDT for PUC01))
DUC01: Each relay operates
and latches when the voltage drops below the respective set level for more than
the respective delay time.
Provided that the voltage
has exceeded the respective
set level (see hysteresis), each
relay releases when the contact input’s connection is interrupted.
for more than the respective
delay time. It releases when
the voltage drops below the
lower set level (see hysteresis) or when the contact
input’s pins are connected.
PUC01: The relay operates
when the voltage drops
below the higher set level for
more than the respective
delay time. Provided that the
voltage has exceeded the
respective set level plus hysteresis, the relay releases
when the contact input is
opened.
Note:
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay(s) activation.
Example 3
(inhibit enable active - over+
over voltage - DPDT relay
(1 x SPDT for PUC01))
Provided that the contact
input is opened, the relay
operates when the voltage
exceeds the lower set level
Specifications are subject to change without notice (21.10.00)
DUC01, PUC01
Function/Range/Level and Time Delay Setting
5
Selection of measuring range:
DIP-switch selector (1 to 2)
Contact input as latch function enable. When the contact
is closed the latch function is
activated. The reset of the latch
condition occurs when the contact is open or by power down.
12
2 to 20 V input range
5 to 50 V input range
20 to 200 V input range
50 to 500 V input range
ON
Contact input as inhibit of
alarm enable. When the contact is closed the relay remains
in normal position even if alarm
condition occurs
Selection of function:
DIP-switch selector (3 to 6
and 1A, 2A)
3
Relay de-energized in
normal condition.
6
Relay energized in normal
condition.
Set point 1 over voltage
monitoring relay. The alarm condition occurs when voltage input
is over the set point value.
Power ON delay 6 ± 0.5 s
Power ON delay 1 ± 0.5 s
Set point 1 under voltage
monitoring relay. The alarm
condition occurs when voltage
input is under the set point
value.
1A
Set point 2 over voltage
monitoring relay. The alarm
condition occurs when voltage
input is over the set point value.
ON
Set point 2 under voltage
monitoring relay. The alarm
condition occurs when voltage
input is under the set point
value.
Selection of level and time
delay:
Upper knob:
Setting of hysteresis on relative scale: 0 to 30% on set
value.
Centre knobs:
Current level setting on relative scale: 10 to 110% on full
scale.
Lower knobs:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
2A
ON
2 x SPDT relays
(DUC01)
4
1 x DPDT relay
(DUC01)
Wiring Diagrams
Example 1
Example 1
24 VDC (+)
48/230 VAC 24/115 VAC
L
Z1
PE
A1
µ
A3
16
24 VDC (+)
48/230 VAC 24/115 VAC
L
µ
18 26
28
2
U
PE
Y1
A2
Y2
15
25
10
1
N (-)
24 VDC (+)
48/230 VAC 24/115 VAC
Examples 2 and 3
24 VDC (+)
48/230 VAC 24/115 VAC
Latch/inhibit
enable
L
Z1
A1
16
L
µ
µ
A3
18 26
2
28
U
µ
11
4
3
U
PE
Y1
Y2
3
U
5
Latch/inhibit
enable
PE
4
7
N (-)
Examples 2 and 3
µ
11
7
A2
15
5
25
N (-)
DUC01
Specifications are subject to change without notice (21.10.00)
10
1
N (-)
PUC01
3
DUC01, PUC01
Operation Diagrams
Over+over voltage
Over+over voltage - Latch
Power Supply
Power Supply
Latch ON
Set Level 1
Hysteresis
Set Level 1
Hysteresis
Set Level 2
Hysteresis
RE1(DUC01)
RE2(DUC01)
DPDT(DUC01)/RE(PUC01)
Set Level 2
1 or 6 s
T1
1 or 6 s
T2
Hysteresis
T1
T2
1 or 6 s
Red LED ON
RE1(DUC01)
1 or 6 s
T1
RE2(DUC01)
1 or 6 s
T2
DPDT(DUC01)/RE(PUC01)
1 or 6 s
T1
T2
Red LED ON
Over+under voltage - N.E. relay(s)
Over+under voltage - Inhibit - N.E. relay(s)
Power Supply
Power Supply
Inhibit ON
Set Level 1
Hysteresis
Set Level 1
Hysteresis
Set Level 2
Hysteresis
1 or 6 s
RE1(DUC01)
T1
1 or 6 s
DPDT(DUC01)/RE(PUC01)
T
Hysteresis
1 or 6 s
T2
RE2(DUC01)
1 or 6 s
Set Level 2
T1
RE1(DUC01)
T1
1 or 6 s
T
T2
RE2(DUC01)
1 or 6 s
Red LED ON
DPDT(DUC01)/RE(PUC01)
T1
T1
T2
T1
Red LED ON
Under+under voltage
Power Supply
Set Level 1
Set Level 2
Hysteresis
Hysteresis
RE1(DUC01)
1 or 6 s
RE2(DUC01)
1 or 6 s
DPDT(DUC01)/RE(PUC01)
1 or 6 s
T1
T1
T2
T
Red LED ON
4
Specifications are subject to change without notice (21.10.00)