ETC DAC01CM24

Timers
Star Delta
Types DAC01, PAC01
• Time range (Star): 0.1 to 600 s
• Time range (Star to Delta): 50 to 130 ms
• Knob selection of star time range
• Knob adjustable time setting
• Automatic start
• Repeatability: ≤ 0.2%
• Output: 8 A SPDT relay with neutral centre position
• For mounting on DIN-rail in accordance with DIN/EN
50 022
• 22.5 mm Euronorm housing or 36 mm Plug-in module
housing
• LED indication for relay status and power supply ON
DAC01
PAC01
Product Description
Star-delta control relay with
two adjustable time ranges:
Star function (0.1 to 600 s)
and star to delta function
(50 to 130 ms). For mount-
Ordering key
ing on
DIN-rail (DAC 01) on Plug-in
(PAC01).
DAC 01 C M24
Housing
Function
Type
Item number
Output
Power Supply
Type Selection
Mounting
Output
Housing
Supply: 24 to 240 VAC/DC
Supply: 380 to 415 VAC
For DIN-rail
Plug-in
1 x SPDT
D - 22.5 mm
P - Housing
DAC 01 C M24
PAC 01 C M24
DAC 01 C M40
PAC 01 C M40
Time Specifications
Time ranges (star)
Knob selectable
Star to delta delay
Neutral centre position
Setting accuracy
Repeatability
Time variation
Within rated power supply
Within ambient temperature
Reset
Time and relay
Output Specifications
Output
0.1 to 1 s
1 to 10 s
6 to 60 s
60 to 600s
50 to 130 ms
between star and delta
position
≤ 5%
≤ 0.2%
≤ 0.05%
≤ 0.2%
Power supply interruption
≥ 200 ms
Specifications are subject to change without notice (15.09.05)
Rated insulation voltage
Contact Ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand
voltage
SPDT relay with neutral
centre position
250 VAC (RMS)
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
< 7200 operations/h
2 kVAC (RMS)
4 kV (1.2/50µs)
1
DAC01, PAC01
Supply Specifications
Power supply
Rated operational voltage
through terminals:
A1 and A2
(DAC01)
2, 10
(PAC01)
M24
General Specifications
Overvoltage cat. III
(IEC 60664, IEC 60038)
24 to 240 VAC/DC
+10% -15%, 45 to 65 Hz
380 to 415 VAC
+10% -15%, 45 to 65 Hz
≤ 10 ms
M40:
Voltage interruption
Rated operational power
M24
AC Supply:
DC Supply:
M40
AC Supply:
4 VA
1.5 W
13 VA @ 400 VAC, 50 Hz
Time Setting
Upper knob:
Setting of star time range
scale: 1 to 10 with respect
to the chosen range.
Lower knob:
Star to delta time setting (50
to 130 ms)
Centre knob:
Star time setting on relative
≤ 100 ms
≤ 100 ms
Power ON delay
Power OFF delay
Indication for
Power supply ON
Output relays ON
LED, green
LED, yellow (flashing when
timing)
(EN 60529)
IP 20
3 (DAC01) ,2 (PAC01)
(IEC 60664)
-20 to 60 °C, R.H. < 95%
-30 to 80 °C, R.H. < 95%
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
22.5 x 80 x 99.5 mm
36 x 80 x 94 mm
Approx 110 g
DAC01
Max 0.5 Nm according to
IEC EN 60947
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
According to EN 61812-1
Approvals
CE Marking
EMC
Immunity
Emission
Timer Specifications
Mode of Operation
The output relay is normally
in the neutral centre position.
When the power supply is
applied, the relay switches to
star position (pin 16 or 4)
and the star period starts.
At the end of the set time
period, the relay returns to
the neutral centre position
and the set delay between
star and delta position starts.
At the end of the star to
delta delay (adjustable from
50 to 130 ms), the relay
switches in delta position
(pin 18 or 3) and does not
release until the power supply is interrupted for at least
200 ms.
If the power supply is inter-
rupted for more than 200 ms
before the star time period
has expired, the relay does
not operate and the time circuit is set to zero. The relay is
ready for a new time period.
Wiring Diagrams
DAC01
PAC01
L(+)
A1
A2
N(-)
2
L(+)
m
16
18
15
m
4
2
10
3
1
N(-)
Specifications are subject to change without notice (15.09.05)
DAC01, PAC01
Operation Diagram
³ 200 ms
≤£ 10
40 ms
ms
³ 200 ms
Power Supply
Relay ON (15-16) Y
ON
OFF
Relay ON (15-18) D ON
OFF
TY
TY
TY-D
TY-D
Dimensions
DIN-rail
Plug-in
94
90
63
28.5
Specifications are subject to change without notice (15.09.05)
80
36
63
99.5
83.5
80
22.5
28.5
3