ETC EABCT40

Timers
Star-Delta Control Relay
Type EAB
•
•
•
•
•
•
•
•
•
•
Time range 1 s to 100 s
Automatic start
Knob-adjustable time setting
Adjustable delay between star and delta output
(50 - 130 ms)
Oscillator-controlled time circuit
Repeatability deviation: ≤ 0.2%
Output: 5A SPDT relay with neutral centre position
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for power supply and star or delta ON
Product Description
Ordering Key
Star-delta control relay with
two adjustable time ranges. 1.
Star function (1 s to 100 s) and
2. between star and delta function (50 - 130 ms). For moun-
Housing
Function
Type
Output
Power supply
ting on DIN-rail. Used in applications where motors are
started in a star-delta configuration such as large blowers etc.
EAB C T23
Type Selection
Mounting
Output
For DIN-rail
SPDT
(with neutral
centre pos.)
Time range
1 - 100 s
Supply: 24 VAC/DC & 115-230 VAC
Supply: 115-230 VAC, 300-415 VAC
EAB C T23
EAB C T40
Time Specifications
Time range
Delay adjustable
Neutral centre position
Time range accuracy
Repeatability deviation
Time variation
Within rated power supply
and ambient temperature
Reset
Time and relay
Output Specifications
1 - 100 s
50 - 130 ms
between star and delta pos.
±10% on max.
min. setting: actual time
≤ min. set time
≤ 0.2%
≤ 0.05%/V
≤ 0.2%/°C
Power supply interruption
≥ 100 ms
Specifications are subject to change without notice (26.10.99)
Output
Rated insulation voltage
Contact ratings (AgCdO)
AC 1
Resistive loads
DC 1
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
SPDT relay
250 VAC (contact/elect.)
µ (micro gap)
5 A, 250 VAC
5 A, 24 VDC
2 A, 250 VAC
3 A, 24 VDC
≥ 40 x 106 operations
≥ 105 operations
(at max. load)
≤ 7200 operations/h
2 kVAC (rms)
4 kV (1.2/50 µs)
1
EAB
Supply Specifications
General Specifications
Power supply
Rated operational voltage
Through term. A1 & A2 T23
Frequency
Through term. A2 & A3 T23
Frequency
Through term. A1 & A2 T40
Frequency
Through term. A2 & A3 T40
Frequency
Voltage interruption
Dielectric voltage
Rated impulse withstand
Voltage
Rated operational current
EMC
Overvoltage cat. III (IEC 60664)
(IEC 60038)
115-230 VAC, -10/+15%
50/60 Hz, -5/+5 Hz
24 VAC/DC, -10/+15%
50/60 Hz, -5/+5 Hz
300-400 VAC, -10/+15%
50/60 Hz, -5/+5 Hz
115-230 VAC, -10/+15%
50/60 Hz, -5/+5 Hz
≤ 40 ms
None
4 kV (1.2/50 µs)
15 mA @ 24 VDC
40 mA @ 24 VAC
20 mA @ 115 VAC
40 mA @ 230 VAC
40 mA @ 400 VAC
Electromagnetic
Compatibility
Acc. to IEC 60801-4
Acc. to IEC 60801-5
≤ 50 ms @ 230/400 V
≥ 100 ms
Immunity
Power ON delay
Power OFF delay
Indication for
Power supply ON
Star output ON
Delta output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Screw terminals
Tightening torque
Approvals
LED, green
LED, yellow
LED, yellow
IP 20
3
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
145 g
Max. 0.5 Nm acc. to IEC 60947
UL, CSA
Mode of Operation
Time Setting
neutral centre position and the
set delay between star and
delta position starts.
The output relay is normally in
the neutral centre position.
When power supply is applied,
the relay is switched to star
position (pin 16) and the star
time period starts.
At the end of the delay (adjustable 50 - 130 ms), the relay is switched to delta position (pin 18) and will not release until power supply is in-
At the end of the set time
period, the relay returns to
terrupted for at least 100 ms.
If power supply is interrupted
for at least 100 ms before the
star time period has expired,
the relay will not operate and
the time circuit is reset to zero.
The relay is ready for a new
time period.
Star time period
Upper knob:
Knob-adjustable on scale in
seconds.
Delay-time (Y-D)
Lower knob:
Knob-adjustable on scale in
milliseconds.
Wiring Diagrams
EAB C T23
EAB C T40
115-230 V
~
24 V
L
~
Y µ
400 V
~
115-230 V
L
D
N
Y
~
µ
D
N/L
Operation Diagram
≥ 100 ms
≥ 100 ms
≤ 40 ms
Power supply
Relay ON (15-16) Y
Relay ON (15-18) D
2
Specifications are subject to change without notice (26.10.99)