ETC GS-AQ911

Data Sheet Ref: 90500997
Issue: 5.1
GS-AQ911
Space air quality transmitter
www.sontay.com
Technical Overview
The GS-AQ911 is wall-mounting air quality transmitter designed for use for the control of fresh air for ventilation purposes. The GS-AQ911 measures the level of contaminant
gases in an air sample, and is sensitive to most heavy
odours, smoke, solvent gases etc., providing an output proportional to the mixed gas concentration. This signal can be
used to control fresh air fans and dampers according to the
ventilation load. Where the primary contaminant load is human respiration, it is recommended that a Carbon Dioxide
transmitter is used.
Features
•
•
Low cost air quality measurement
Detects particulates such as cigarette smoke
Specification
Product Codes
Sensor reference
Tin Dioxide film
Cal. accuracy
±5% of reading
Re-calibration
2 years
Housing material
Flame retardant ABS
Dimensions
85mm x 85mm x 27mm
GS-AQ911
Space air quality transmitter
Ambient:
Temperature
15°C to 30°C
RH
45 to 65% RH
Power supply
Output
24Vac/dc (±10%) @ 45mA
0-10Vdc
(0v = Lo contamination)
(10Vdc = Hi contamination)
Country of origin
UK
International Tel: +44 1732 861225
UK Sales Tel: 0845 345 7253
Page 1
International Fax: +44 1732 861226
UK Sales Fax: 0845 345 7353
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.
Data Sheet Ref: 90500997
Issue: 5.1
GS-AQ911
Space air quality transmitter
www.sontay.com
Installation
Connections
1.
Undo the tamperproof screw at the bottom of the
housing and gently pull the front panel from the
base.
2.
Using the base as a template mark the hole centres
and fix to the wall with suitable screws. Alternatively
the base plate can be mounted on to a conduit box
or a standard recessed back box.
3.
Feed cable through the 22mm knockout in the base
of the housing and terminate the cores at the terminal block. Leaving some slack inside the unit.
Replace the housing to the base plate.
4.
5.
Fit the tamperproof screw (if required) through the
lug at the bottom of the base plate.
6.
Power the unit with 24Vac/dc and after a stabilising
period of 2-3 minutes functionality checks can be
made.
7.
Pre-commissioning checks are made after approximately 30 minutes. Final commissioning should only
be carried out after the unit has been running for a
minimum of seven days.
LK1
Output
+24V
0V
Operation
LK2
The GS-AQ911 space air quality transmitter is most suited
to areas such as common rooms, canteens, office spaces
and other areas where pollutants given off by occupants are
of concern.
LK2 can be ON for response damping or OFF for no dampThe typical pollutants of which the GS-AQ911 would monitor
are body odours, methane, solvent gases, cigarette smoke,
carbon monoxide, alcohol, perfume and most other heavy
odours related to high occupancy.
ing.
NB Jumper LK1 should not be changed.
The normal operation of the GS-AQ911 is to set the dampers to minimum fresh air at below 2Vdc. As the signal increases, dampers should be modulated to fully open at 810Vdc.
Trend Scaling
Typically, the output could be scaled for 0 to 100% contamination.
Brange
-100
Trange
100
Upper
100
Lower
0
Exponent 3
International Tel: +44 1732 861225
UK Sales Tel: 0845 345 7253
Page 2
International Fax: +44 1732 861226
UK Sales Fax: 0845 345 7353
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.