Product Data Sheet Part Number: C3322 Revision Level: 0 4C 20 7/28 TC OAS FLEX PVDF Date: TYPE CL2P A. CONSTRUCTION Conductor: Insulation: Cable: Jacket: Print Legend: DIAMETERS #20 AWG 7/28 Tinned Copper 0.038” nom. 0.007" Wall FLEXGUARD* 0.052" nom. 4 conductors @ 2.50” LHL w/ AL/Polypro (foil out) 0.133" nom. 0.010"Wall PVDF – Natural 0.153" +/- 0.008" -Plenum ripcord under jacket. CAROL (R) 20 AWG -- C3322 -- 60C E60233-8 CL2P (UL) -- MADE IN USA DATE CODE (PRINT EVERY 2 FT) B. INDUSTRY APPROVALS National Electrical Code UL Standard 13 Article 725 Type CL2P C. ELECTRICAL PROPERTIES TEMPERATURE: SUGGESTED WORKING VOLTAGE (Vrms): CONDUCTOR D.C. RESISTANCE: D. COLOR CODE 1 2 3 4 60C 150 Vrms (CL2P) 10.3 Ohms/1000 ft. nom. @ 20C (Listed as Individual Conductors or Pairs of Conductors) Black White Red Green Note: Data are subject to change without notice. Contact your Customer Service representative for latest information. *FLEXGUARD is a trademark of General Cable Corporation for polymer alloy insulation and jackets. 7/7/2007