GENERAL C3116

Product Data Sheet
Part Number: C3116
Revision Level:
0
4C 22 7/30 TC FLEX FLEX
Date:
TYPE CMP / CL3P
A. CONSTRUCTION
Conductor:
Insulation:
Cable:
Jacket:
Print Legend:
DIAMETERS
#22 AWG 7/30 Tinned Copper
0.030" nom.
0.008" Wall FLEXGUARD*
0.046" nom.
4 Conductors @ 4.00" LHL.
0.111" nom.
0.015"Wall FLEXGUARD* - Natural
0.141" +/- 0.007"
-Plenum ripcord under jacket.
CAROL (R) 22 AWG -- C3116 -- 75C E60233-8 (UL) CL3P --- C(UL) CMP -- MADE IN USA
DATE CODE (PRINT EVERY 2 FT)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 13
Article 725
Type CL3P
National Electrical Code
UL Standard 444
Article 800
Type CMP
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
D. COLOR CODE
1
2
3
4
75C
150 Vrms (CL3P) / 300Vrms (CMP)
16.6 Ohms/1000 ft. nom. @ 20C
(Listed as Individual Conductors or Pairs of Conductors)
Black
White
Red
Green
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.
*FLEXGUARD is a trademark of General Cable Corporation for polymer alloy insulation and jackets.
7/7/2007