05040 587B051LP - 587B301LP Only One Name Means ProTek’Tion™ low profile 120v ac power line surge suppressor Description The 587BxxxLP Series of 120 Volt AC Surge Suppressors is designed for use by the OEM, equipment installer and or maintenance contractor. These modules employ a three stage technology proven to be the most cost effective and reliable method in protecting sensitive electronic equipment from over voltage transients. This series is designed to protect AC powered equipment from the 6,000 volt peak open circuit voltage and 3,000 Amp short circuit current as defined in ANSI/IEEE C62.41, Category C1. The 587BxxxLP Series offers a high degree of protection against 120 VAC EMI line noise. It is ideal for protecting 400 Volt components because the solid state TVS technology assures that the line-to-neutral voltage will not exceed 400 Volts. While the modules are designed for transient voltage protection, the advanced circuitry will also attenuate the amplitude and slow the rate of rise of high frequency noise acting as an EMI filter. The 587BxxxLP Series includes differential mode protection, which is effective in reducing interference from line to equipment and are effective in reducing equipment generated noise to meet FCC, VDE and CSA interference requirements. low profile Features applications • Compatible with IEC 61000-4-5 (Surge): 1kA, 8/20µs, Level 4 (LineGnd) & 333A, Level 4 (Line-Line) • Meets ANSI/IEEE C62.41 Requirements • Listed to CSA, File LR65240 • Differential and Common Mode Protection • Low Clamping Voltage • Nanosecond Response Time • Long Life and Maintenance Free • Finger Safe Connections • Hard Wired Equipment AC Power Protection • Load Side Distribution Systems • Secondary Protection for Light Industrail AC Power Mechanical characteristics • Low Profile Plastic Package • Approximate Weight: 360 grams • Flammability Rating UL 94V-0 figure 2 typical clamping action of a 15a module 8 6 6 4 Kilovolts Kilovolts figure 1 transient voltage threat condition 4 2 0 2 0 0 10 20 30 40 50 60 0 t - Time - µs 10 20 30 40 50 60 t - Time - µs Figures 1 and 2 are photographs of digitized waveforms showing the typical clamping action of a 15A module. A 12 Ohm resistor is used to represent a 10A equipment load. The load is then subjected to the ANSI/IEEE C62.41 Catagory CI test conditions (6000V/3000A). These photographes contrast the effect on equipment with and without the protector. 05040.R5 2/11 Page 1 www.protekdevices.com 05040 587B051LP - 587B301LP Only One Name Means ProTek’Tion™ typical device characteristics MAXIMUM RATINGS @ 25°C Unless Otherwise Specified PARAMETER Operating Line Voltage: +10% SYMBOL VALUE UNITS VO 130 Volts AC Line Current: 587B051LP/587B101LP/587B151LP/587B301LP - 5/10/20/30 Amps Peak Transient Voltage - 6000 Volts Peak Transient Current - 3000 Amps Current Leakage @ 130 Volts AC: Line-to-Neutral, Neutral-to-Ground, Line-to-Ground - 1 mA Operating Temperature - Note 1 TA -40 to 85 °C TSTG -40 to 85 °C Storage Temperature - Note 1 Notes 1. Measured at the center of the mounting surface. ELECTRICAL CHARACTERISTICS @ 25°C Unless Otherwise Specified Protection mode (Note 1) maximum clamping voltage (Note 2) open circuit voltage (Note 2) short circuit current (Note 2) volts @1.2/50µs volts @ 8/20µs amps Line to Neutral 295 1000 500 Line to Neutral 330 6000 3000 Neutral to Ground 500 1000 500 Line to Ground 500 6000 3000 Notes 1. Differential Mode Protection: Line to Neutral. Common Mode Protection: Line to Ground & Neutral to Ground. 2. Test condition responses to transient voltages. arrestor definitions Clamping Voltage: The clamping voltage of an arrester is the voltage that appears across its terminals during conduction of a transient current. Standard Wave Form: The waveform of a surge current or voltage is designated by a combination of two numbers. The first number is for the time of the wave front expressed in microseconds from zero to the peak of the wave. The second number is for the time of the wavetail also expressed in microseconds from zero to the instant that the wavetail reaches one half of the crest or peak value, i.e., 8/20 µs waveform. Transient Current: The transient current of an arrestor is the peak surge current which flows through the arrester when voltage clamping occurs. operation For maximum effectiveness, the protector should be installed directly after the AC line on/off switch and fuse. This will protect the electronics from the AC line switch arcing and the severe transients caused by a fuse clearing. Some heat is produced when operating at full current load, and heat sinking may be required to maintain case temperature below 85°C. The case temperature is measured at the center of the mounting surface. The unit should not be mounted to a low combusting temperature material such as wood. High energy transients will cause a large circulating current in the AC input line (2,500A is possible). To prevent electromagnetic coupling, the AC line on the input side of the protector must be dressed away from other wiring, magnetic shielding may be required. In addition, the electrical service must be connected to a low impedance earth ground. 05040.R5 2/11 Page 2 www.protekdevices.com 05040 587B051LP - 587B301LP Only One Name Means ProTek’Tion™ package information outline dimensions dim millimeters min max inches min max A 96.8 3.81 B 88.9 3.50 C 110.92 D E 4.37 14.43 4.40 0.586 43.89 F G 111.68 44.39 1.62 27.9 1.72 1.10 58.04 58.80 2.29 2.32 A E D B F C G Line 1 Out Line In Dia. 0.181” Line 2 Out DEVICE MARKING Neutral 1 Out Neutral In Neutral 2 Out Ground In Ground Out ORDERING INFORMATION base PART NUMBER (xx = Voltage) MARKING 587BxxxLP Part Number, Date Code, Voltage, Logo, Current Rating, CSA Logo 05040.R5 2/11 Page 3 www.protekdevices.com 05040 587B051LP - 587B301LP Only One Name Means ProTek’Tion™ company information COMPANY PROFILE ProTek Devices, based in Tempe, Arizona USA, is a manufacturer of Transient Voltage Suppression (TVS) products designed specifically for the protection of electronic systems from the effects of lightning, Electrostatic Discharge (ESD), Nuclear Electromagnetic Pulse (NEMP), inductive switching and EMI/RFI. With over 25 years of engineering and manufacturing experience, ProTek designs TVS devices that provide application specific protection solutions for all electronic equipment/systems. ProTek Devices Analog Products Division, also manufactures analog interface, control, RF and power management products. CONTACT US Corporate Headquarters 2929 South Fair Lane Tempe, Arizona 85282 USA By Telephone General: 602-431-8101 Sales: 602-414-5109 Customer Service: 602-414-5114 By Fax General: 602-431-2288 By E-mail: Sales: [email protected] Customer Service: [email protected] Technical Support: [email protected] Web www.protekdevices.com www.protekanalog.com COPYRIGHT © ProTek Devices 1998 - This literature is subject to all applicable copyright laws and is not for resale in any manner. SPECIFICATIONS: ProTek reserves the right to change the electrical and or mechanical characteristics described herein without notice. DESIGN CHANGES: ProTek reserves the right to discontinue product lines without notice and that the final judgement concerning selection and specifications is the buyer’s and that in furnishing engineering and technical assistance. ProTek assumes no responsibility with respect to the selection or specifications of such products. ProTek makes no warranty, representation or guarantee regarding the suitability of its products for any particular purpose, nor does ProTek assume any liability arising out of the application or use of any product or circuit and specifically disclaims any and all liability without limitation special, consequential or incidental damages. LIFE SUPPORT POLICY: ProTek Devices products are not authorized for use in life support systems without written consent from the factory. PATENT INFORMATION: This device is patented under U.S. Patent No. 4,563,720 05040.R5 2/11 Page 4 www.protekdevices.com