ETC CIF06B

Bussmann®
HRCI-CB Industrial Ceramic Body Fuse
CIF06B
EK-B
Clip-In Mounting
Dimensional Data
A
C
D
E
N
F
CATALOG SYMBOL: CIF06B (1 - 30 Amps)
EK-B (35 - 60 Amps)
600 Volts AC; 250 Volts DC
INTERRUPTING RATING: 200,000A RMS SYMMETRICAL
CSA C22.2 NO. 106-M92
• Industrial miniature fuse with offset blades for clip-in mounting.
• Ground ceramic body with plated endcaps.
• Provides both short circuit and overload protection.
• CIF06B fits the 30 Amp SafeLOC fuseholder.
EK-B fits the 60 Amp SafeLOC fuseholder.
Type
Catalog
Symbol
Amps
CIF06B
1-30A
EK-B
35-60A
HRCI-CB
12-21-98
SB98107
Rev. A
Dimensions in Inches and (mm)
A
E
2.38
.50
(60.40)
(12.70)
2.65
.58
(67.30)
(14.80)
F
.03
(0.81)
.05
(1.22)
N
.14
(3.50)
.14
(3.50)
C
1.44
(35.50)
1.44
(36.30)
D
.54
(13.80)
.84
(21.40)
Form No. HRCI-CB
Page 1 of 3
BIF Doc #4128
Bussmann®
HRCI-CB Industrial Ceramic Body Fuse
CIF06B
EK-B
Clip-In Mounting
100
10
30
25
20
15
10
6
1
3
AMPERE
RATING
10
1
.1
100
10
1
.1
0.1
AMPERE
RATING
10
15
20
25
30
100
TIME IN SECONDS
1,000
PEAK CURRENT (KA)
1,000
6
Time/Current-Curves (Cat. No. CIF06B)
3
Peak Let-Through Curves (Cat. No. CIF06B)
PROSPECTIVE CURRENT (SYM. RMS KA)
100,000
10,000
1,000
100
1
10
.01
Energy Let-Through Curves (Cat. No. CIF06B)
CURRENT IN AMPERES
Power Dissipation @ Rated Amps
10,000
Catalog No.
AMPERE2 SECONDS (I2t)
Total I2t at 600V
3CIF06B
6CIF06B
10CIF06B
15CIF06B
20CIF06B
25CIF06B
30CIF06B
Total I2t at 460V
Pre-Arcing I2t
1,000
Watts
1.8
1.5
3.4
2.4
3.2
3.6
3.6
100
30
25
20
15
10
6
1
3
10
FUSE RATING (AMPERES)
12-21-98
SB98107
Rev. A
Form No. HRCI-CB
Page 2 of 3
BIF Doc #4128
Bussmann®
HRCI-CB Industrial Ceramic Body Fuse
CIF06B
EK-B
Clip-In Mounting
Time/Current-Curves (Cat. No. EK-B)
35
40
45
50
60
Peak Let-Through Curves (Cat. No. EK-B)
1,000
1,000
AMPERE
RATING
60
50
45
40
35
10
1
TIME IN SECONDS
100
AMPERE
RATING
PEAK CURRENT (KA)
100
10
1
100
10
1
.1
0.1
.1
PROSPECTIVE CURRENT (SYM. RMS KA)
Energy Let-Through Curves (Cat. No. EK-B)
10,000
1,000
100
1
10
.01
100,000
CURRENT IN AMPERES
10,000
AMPERE2 SECONDS (I2t)
Power Dissipation @ Rated Amps
Catalog No.
1,000
Total I2t at 600V
EK35B
EK40B
EK45B
EK50B
EK60B
Watts
4.2
4.8
5.8
6.6
7.0
Total I2t at 460V
100
Pre-Arcing I2t
65
60
50
45
35
1
40
10
FUSE RATING (AMPERES)
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled.This bulletin is intended to
clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-21-98
SB98107
Rev. A
Form No. HRCI-CB
Page 3 of 3
BIF Doc #4128