ETC DLS-R-60

Bussmann®
Dura-Lag
DLS-R
Dual-Element, Time-Delay Construction Grade Fuses
Class RK5 – 600 Volt
1 –600 Amps
Dimensional Data
5.5" (± 0.31)
5" (± 0.31)
1.06" (± 0.008)
.81" (± 0.008)
⁄Ω¡ºA to 30A
35A to 60A
A
B
Dimensions (inches)
Ampere Ratings
70-100
110-200
225-400
450-600
Catalog Symbol: DLS-R (600V)
Current-Limiting
Dual-Element, Time-Delay – 10 seconds (minimum) at
500% rated current
Voltage Rating: 600 Volts AC (or less)
Self-Certified for 300 Vdc
Interrupting Rating: 200,000A RMS Symmetrical
20,000A DC
Agency Approvals:
U.L. Listed, Std. 248-12, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers
DLS-R-1
DLS-R-10
DLS-R-100
DLS-R-1flꭧ
DLS-R-12
DLS-R-110
DLS-R-2
DLS-R-15
DLS-R-125
DLS-R-2⁄Ω™
DLS-R-17⁄Ω™
DLS-R-150
DLS-R-2 8ꭧ
DLS-R-20
DLS-R-175
DLS-R-3
DLS-R-25
DLS-R-200
DLS-R-32ꭧ
DLS-R-30
DLS-R-225
DLS-R-3⁄Ω™
DLS-R-35
DLS-R-250
DLS-R-4
DLS-R-40
DLS-R-300
DLS-R-5
DLS-R-45
DLS-R-350
DLS-R-6
DLS-R-50
DLS-R-400
DLS-R-6⁄Ω¢
DLS-R-60
DLS-R-500
DLS-R-7
DLS-R-70
DLS-R-600
DLS-R-8
DLS-R-80
—
DLS-R-9
DLS-R-90
—
A
7.88 (± 0.062)
9.63 (± 0.062)
11.63 (± 0.094)
13.38 (± 0.094)
1.16
1.66
2.38
2.88
B
(± 0.008)
(± 0.008)
(± 0.008)
(± 0.008)
General Information:
• Designed for contractor needs.
• Protects industrial equipment and large motors.
• Recommended for AC power distribution system mains,
feeders and branch circuits.
• Industry standard time-delay of 10 seconds at 5 times
the fuse rating.
Carton Quantity and Weight
Ampere
Ratings
Weight*
Carton
Qty.
Lbs.
Kg.
⁄Ω¡º–30
10
1.62
0.729
35–60
10
3.00
1.35
70–100
5
2.20
1.0
110–200
1
1.10
0.5
225–400
1
2.36
1.1
450–600
1
3.44
1.5
*Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
2-18-00
SB99006 Rev. A
Form No. DLS-R
Page 1 of 3
BIF Doc #1022
Bussmann®
Dura-Lag
DLS-R
Dual-Element, Time-Delay Construction Grade Fuses
Class RK5 – 600 Volt
1 –600 Amps
1
1.25
1.6
2
2.5
3.2
4
5
6.25
8
.6
.8
.2
.3
.4
100
.1
.5
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
RMS SYMMETRICAL CURRENT IN AMPERES
TIME IN SECONDS
10
1
RMS SYMMETRICAL CURRENT IN AMPERES
2-18-00
SB99006 Rev. A
100
0.1
1
.01
10
.1
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPERES
Form No. DLS-R
Page 2 of 3
BIF Doc #1022
Bussmann®
Dura-Lag
DLS-R
Dual-Element, Time-Delay Construction Grade Fuses 1 Amp –600 Amps
Class RK5 – 600 Volt
Time-Current Characteristic Curves–Average Melt
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
2-18-00
SB99006
Rev. A
Form No. DLS-R
Page 3 of 3
BIF Doc #1022