Fusetron® FRN-R - Cooper Bussmann

Bussmann®
Fusetron®
FRN-R
Dual-Element, Time-Delay Fuses
Class RK5 – 250 Volt
70-600A
Dimensional Data
5.88"
(± 0.062)
1.06" (± 0.008)
70A to 100A
7.13"
(± 0.062)
1.56" (± 0.008)
110A to 200A
8.63"
(± 0.094)
2.06" (± 0.008)
225A to 400A
10.38"
(± 0.094)
Catalog Symbol: FRN-R †
Current-Limiting
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Ampere Rating: 70 to 600A
Voltage Rating:
250Vac (or less)
125Vdc (70-200A)
250Vdc (201-600A)
Interrupting Rating:
200,000A RMS Sym.
20,000A AIC
Agency Information:
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-01, File 53787
Catalog Numbers
2.59" (± 0.008)
450A to 600A
General Information:
• Provides motor overload, ground fault and short-circuit
protection.
• Helps protect motors against burnout from overloads and
single phasing when sized properly.
• Simplifies and improves blackout prevention (selective
coordination).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high performance short-circuit and overload
protection.
• The overload element provides protection against low level
overcurrent of overloads and will hold on inrush current
which is five times greater than the ampere rating of the
fuse for a minimum of ten seconds.
FRN-R-70
FRN-R-125
FRN-R-350
FRN-R-75
FRN-R-150
FRN-R-400
FRN-R-80
FRN-R-175
FRN-R-450
FRN-R-85
FRN-R-200
FRN-R-500
Fuse Reducers For Class R Fuses
FRN-R-90
FRN-R-225
FRN-R-600
FRN-R-100
FRN-R-250
—
Equipment
Fuse Clips
FRN-R-110
FRN-R-300
—
200A
400A
Carton Quantity and Weight
Weight*
Ampere
Ratings
Carton
Qty.
Lbs.
Kg.
70–100
5
1.5
0.680
101–200
1
0.77
0.349
201–400
1
1.52
0.689
401–600
1
3.0
1.4
*Weight per carton.
† To obtain information for 0-60A, access Data Sheet: 1019
4-2-03
SB03091
600A
Desired Fuse
(Case) Size
Catalog Number
(Pairs) 250V
100A
No. 2621-R
100A
No. 2641-R
200A
No. 242-R
100A
No. 2661-R
200A
No. 2662-R
400A
No. 2664-R*
*Single reducer only (pair not required).
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Form No. FRN-R 70-600
Page 1 of 3
Data Sheet: 1020
Bussmann®
Fusetron®
FRN-R
Dual-Element, Time-Delay Fuses
Class RK5 – 250 Volt
70-600A
AMPERE
RATING
600
400
300
200
100
Time-Current Characteristic Curves–Average Melt
Recommended fuseblocks for
Class R 250V fuses
See Data Sheet 1110
100
TIME IN SECONDS
10
1
.1
40,000
10,000
1,000
100
.01
CURRENT IN AMPERES
4-2-03
SB03091
Form No. FRN-R 70-600
Page 2 of 3
Data Sheet: 1020
Bussmann®
Fusetron®
FRN-R
Dual-Element, Time-Delay Fuses
Class RK5 – 250 Volt
70-600A
Current-Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
4-2-03
SB03091
Form No. FRN-R 70-600
Page 3 of 3
Data Sheet: 1020