ETC FRN-R-400

Bussmann®
Fusetron®
FRN-R
Dual-Element, Time-Delay Fuses
Class RK5 – 250 Volt
70-600A
Dimensional Data
5.88"
(± 0.062)
1.06" (± 0.008)
70A to 100A
7.13"
(± 0.062)
1.56" (± 0.008)
110A to 200A
8.63"
(± 0.094)
2.06" (± 0.008)
225A to 400A
10.38"
(± 0.094)
Catalog Symbol: FRN-R †
Current-Limiting
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Ampere Rating: 70 to 600 Amperes
Voltage Rating: 250 Volts AC (or less)
Interrupting Rating: 200,000A RMS Sym.
DC Ratings: 20,000 AIC @ 125 VDC 70-400 Amperes
20,000 AIC @250 VDC 401-600 Amperes
Agency Approvals:
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-01, File 53787
Catalog Numbers
FRN-R-70
FRN-R-125
FRN-R-350
FRN-R-75
FRN-R-150
FRN-R-400
FRN-R-80
FRN-R-175
FRN-R-450
FRN-R-85
FRN-R-200
FRN-R-500
FRN-R-90
FRN-R-225
FRN-R-600
FRN-R-100
FRN-R-250
—
FRN-R-110
FRN-R-300
—
Carton
Qty.
70–100
101–200
450A to 600A
General Information:
• Provides motor overload, ground fault and short-circuit
protection.
• Helps protect motors against burnout from overloads and
single phasing when sized properly.
• Simplifies and improves blackout prevention (selective
coordination).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high performance short-circuit and overload
protection.
• The overload element provides protection against low level
overcurrent of overloads and will hold on inrush current
which is five times greater than the ampere rating of the
fuse for a minimum of ten seconds.
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
Carton Quantity and Weight
Ampere
Ratings
200A
Desired Fuse
(Case) Size
Catalog Number
(Pairs) 250V
100A
No. 2621-R
100A
No. 2641-R
0.680
200A
No. 242-R
0.349
100A
No. 2661-R
Weight*
Lbs.
Kg.
5
1.5
1
0.77
201–400
1
1.52
0.689
401–600
1
3.0
1.4
*Weight per carton.
2.59" (± 0.008)
400A
600A
200A
No. 2662-R
400A
No. 2664-R*
*Single reducer only (pair not required).
† To obtain information for 0-60 Amps, access BIF # 1019
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
11-1-00
A00115
Form No. FRN-R 70-600
Page 1 of 3
BIF Doc #1020
Bussmann®
Fusetron®
FRN-R
Dual-Element, Time-Delay Fuses
Class RK5 – 250 Volt
70-600A
Fuseblocks for Class R Fuses
Time-Current Characteristic Curves–Average Melt
Amps
70
Poles
1
to
2
R25100-2
CR
COR
100
3
R25100-3
CR
COR
to 200
1
R25200-1
CR
—
to 400
1
R25400-1
CR
—
to 600
1
R25600-1
CR
—
AMPERE
RATING
600
300
400
Terminal Type (Suffix No.)
Box Lug w/
—
Clip
CU only
CR
COR
200
Basic
Catalog
Number
R25100-1
100
(Clip Retaining Spring Standard, Suffix “R”)
100
TIME IN SECONDS
10
1
.1
40,000
10,000
1,000
100
.01
CURRENT IN AMPERES
11-1-00
A00115
Form No. FRN-R 70-600
Page 2 of 3
BIF Doc #1020
Bussmann®
Fusetron®
FRN-R
Dual-Element, Time-Delay Fuses
Class RK5 – 250 Volt
70-600A
Current-Limitation Curves
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
11-1-00
A00115
Form No. FRN-R 70-600
Page 3 of 3
BIF Doc #1020