Fusetron® FRS-R

Bussmann®
Fusetron
FRS-R
®
Dual-Element, Time-Delay Fuses
Class RK5 – 600 Volt
Dimensional Data
5" (± 0.31)
.81" (± 0.008)
⁄Ω¡ºA to 30A
5.5" (± 0.31)
1.06" (± 0.008)
35A to 60A
Catalog Symbol: FRS-R
Dual-Element, Time-Delay – 10 second (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: ⁄Ω¡º to 60A
Voltage Rating: 600Vac (or less)
Interrupting Rating: 200,000A RMS Sym.
dc Ratings (20,000AIC @ 250Vdc)
Agency Information:
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers
FRS-R-⁄Ω¡º
FRS-R-1°Ω¡º
FRS-R-8
FRS-R-⁄Ω•
FRS-R-2
FRS-R-9
FRS-R-⁄fiΩ¡ºº
FRS-R-2⁄Ω¢
FRS-R-10
FRS-R-¤Ω¡º
FRS-R-2⁄Ω™
FRS-R-12
FRS-R-⁄Ω¢
FRS-R-2°Ω¡º
FRS-R-15
FRS-R-‹Ω¡º
FRS-R-3
FRS-R-17⁄Ω™
FRS-R-›Ω¡º
FRS-R-3¤Ω¡º
FRS-R-20
FRS-R-⁄Ω™
FRS-R-3⁄Ω™
FRS-R-25
FRS-R-flꭧ
FRS-R-4
FRS-R-30
FRS-R-°Ω¡º
FRS-R-4⁄Ω™
FRS-R-35
FRS-R-1
FRS-R-5
FRS-R-40
FRS-R-1⁄Ω•
FRS-R-5flꭧ
FRS-R-45
FRS-R-1⁄Ω¢
FRS-R-6
FRS-R-50
FRS-R-1›Ω¡º
FRS-R-6⁄Ω¢
FRS-R-60
FRS-R-1⁄Ω™
FRS-R-7
—
FRS-R-1flꭧ
FRS-R-7⁄Ω™
—
General Information:
• Provides motor overload, ground fault and short-circuit protection. When used in circuits subject to surge currents such
as those caused by motors, transformers and other inductive
components, these fuses can be sized close to full-load
amperes to give maximum overcurrent protection.
• Permits the use of smaller and less costly switches. The timedelay feature makes it possible to use fuse ampere ratings
which are much smaller than those of non-time-delay fuses.
Considerable cost saving occurs by permitting the use of
smaller size switches, panels and fuses themselves.
• Provides a higher degree of short-circuit protection (greater
current-limitation) in circuits in which surge currents or temporary overloads occur.
• Helps protect motors against burnout from overloads.
• Gives motor running back-up protection to motors without
extra costs.
• Helps protect motors against burnout from single phasing on
three phase systems.
• Simplifies and improves blackout prevention (selective
coordination).
• Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both
high-performance, short-circuit and overload protection.
• The overload element provides protection against low level
overcurrent of overloads and will hold an overload which is
five times greater than the ampere rating of the fuse for a
minimum of ten seconds.
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
60A
100A
200A
Desired
Fuse (Case)
Size
Catalog Number
(Pairs)
600V
30A
No. 663-R
30A
No. 216-R
60A
No. 616-R
60A
No. 626-R
Recommended fuseblocks for
Class R 600V fuses
See Data Sheet: 1111
Carton Quantity and Weight
Ampere
Ratings
⁄Ω¡º-60A
Weight*
Carton
Qty.
Lbs.
Kg.
⁄Ω¡º–15
10
0.40
0.181
17.5–30
10
0.50
0.277
35-60
10
3.10
1.406
*Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
7-25-03
A03014
Form No. FRS-R 1/10-60
Page 1 of 2
Data Sheet: 1017
Bussmann®
Fusetron
FRS-R
®
Dual-Element, Time-Delay Fuses
Class RK5 – 600 Volt
⁄Ω¡º-60A
.1
.15
300
AMPERE
RATING
60A
30A
300
AMPERE RATING
15A
.2
.3
.4
.5
.6 .8
1 1.25
1.6
2 2.5
3.2 4
5 6.25
8
10
12
Time-Current Characteristic Curves–Average Melt
100
100
10
1
TIME IN SECONDS
TIME IN SECONDS
10
.1
1
1,000
100
10
1
.1
.01
CURRENT IN AMPERES
.1
60
30,000
10,000
20
.01
1,000
100,000
100
B
400,000
CURRENT IN AMPERES
30
10,000
15
200,000
1,000
1,000
100,000
A
10,000
INSTANTANEOUS PEAK LET-THROUGH
CURRENT IN AMPERES
AMPERE
RATING
Current-Limitation Curves
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPERES
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
7-25-03
A03014
Form No. FRS-R 1/10-60
Page 2 of 2
Data Sheet: 1017