ETC FRS-R-15

Bussmann®
Fusetron
FRS-R
®
Dual-Element, Time-Delay Fuses
Class RK5 – 600 Volt
Dimensional Data
5" (± 0.31)
.81" (± 0.008)
⁄Ω¡ºA to 30A
5.5" (± 0.31)
1.06" (± 0.008)
35A to 60A
Catalog Symbol: FRS-R
Dual-Element, Time-Delay – 10 second (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: ⁄Ω¡º to 60 Amperes
Voltage Rating: 600 Volts AC (or less)
Interrupting Rating: 200,000A RMS Sym.
DC Ratings (20,000AIC @ 250 VDC)
Agency Approvals:
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers
FRS-R-⁄Ω¡º
FRS-R-1°Ω¡º
FRS-R-⁄Ω•
FRS-R-2
FRS-R-8
FRS-R-9
FRS-R-⁄fiΩ¡ºº
FRS-R-2⁄Ω¢
FRS-R-10
FRS-R-¤Ω¡º
FRS-R-2⁄Ω™
FRS-R-12
FRS-R-⁄Ω¢
FRS-R-2°Ω¡º
FRS-R-15
FRS-R-‹Ω¡º
FRS-R-3
FRS-R-17⁄Ω™
FRS-R-›Ω¡º
FRS-R-3¤Ω¡º
FRS-R-20
FRS-R-⁄Ω™
FRS-R-3⁄Ω™
FRS-R-25
FRS-R-flꭧ
FRS-R-4
FRS-R-30
FRS-R-°Ω¡º
FRS-R-4⁄Ω™
FRS-R-35
⁄Ω¡º-60A
General Information:
• Provides motor overload, ground fault and short-circuit protection. When used in circuits subject to surge currents such
as those caused by motors, transformers and other inductive
components, these fuses can be sized close to full-load
amperes to give maximum overcurrent protection.
• Permits the use of smaller and less costly switches. The timedelay feature makes it possible to use fuse ampere ratings
which are much smaller than those of non-time-delay fuses.
Considerable cost saving occurs by permitting the use of
smaller size switches, panels and fuses themselves.
• Provides a higher degree of short-circuit protection (greater
current-limitation) in circuits in which surge currents or temporary overloads occur.
• Helps protect motors against burnout from overloads.
• Gives motor running back-up protection to motors without
extra costs.
• Helps protect motors against burnout from single phasing on
three phase systems.
• Simplifies and improves blackout prevention (selective
coordination).
• Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both
high-performance, short-circuit and overload protection.
• The overload element provides protection against low level
overcurrent of overloads and will hold an overload which is
five times greater than the ampere rating of the fuse for a
minimum of ten seconds.
Fuse Reducers For Class R Fuses
Desired
Fuse (Case)
Size
Equipment
Fuse Clips
60A
100A
200A
Catalog Number
(Pairs)
600V
30A
No. 663-R
30A
No. 216-R
60A
No. 616-R
60A
No. 626-R
FRS-R-1
FRS-R-5
FRS-R-40
FRS-R-1⁄Ω•
FRS-R-5flꭧ
FRS-R-45
FRS-R-1⁄Ω¢
FRS-R-6
FRS-R-50
Class R Catalog Numbers
FRS-R-1›Ω¡º
FRS-R-6⁄Ω¢
FRS-R-60
(Clip Retaining Spring Standard, Suffix “R”)
FRS-R-1⁄Ω™
FRS-R-7
—
FRS-R-1flꭧ
FRS-R-7⁄Ω™
—
Terminal Type (Suffix No.)
Screw w/
Box Lug w/
—
Pres.
—
Clip
Plate
CU only
SR
PR
CR
COR
to
2
R60030-2
SR
PR
CR
COR
30
3
R60030-3
SR
PR
CR
COR
31
1
R60060-1
SR
—
CR
COR
to
2
R60060-2
SR
—
CR
COR
60
3
R60060-3
SR
—
CR
COR
Amps
⁄Ω¡º
Carton Quantity and Weight
Ampere
Ratings
Poles
1
Basic
Catalog
Number
R60030-1
Weight*
Carton
Qty.
Lbs.
Kg.
⁄Ω¡º–15
10
0.40
0.181
17.5–30
10
0.50
0.277
35-60
10
3.10
1.406
*Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
12-17-98
SB98107
Rev. A
Form No. FRS-R 1/10-60
Page 1 of 2
BIF Doc #1017
Bussmann®
Fusetron
FRS-R
®
Dual-Element, Time-Delay Fuses
Class RK5 – 600 Volt
⁄Ω¡º-60A
.1
.15
300
AMPERE RATING
AMPERE
RATING
60A
30A
300
15A
.2
.3
.4
.5
.6 .8
1 1.25
1.6
2 2.5
3.2 4
5 6.25
8
10
12
Time-Current Characteristic Curves–Average Melt
100
100
10
1
TIME IN SECONDS
TIME IN SECONDS
10
.1
1
1,000
100
10
1
.1
.01
CURRENT IN AMPERES
.1
30,000
10,000
1,000
20
.01
CURRENT IN AMPERES
60
10,000
30
200,000
1,000
1,000
100,000
A
10,000
INSTANTANEOUS PEAK LET-THROUGH
CURRENT IN AMPERES
100,000
100
B
400,000
AMPERE
RATING
Current-Limitation Curves
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPERES
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-17-98
SB98107
Rev. A
Form No. FRS-R 1/10-60
Page 2 of 2
BIF Doc #1017