ETC FRS-R-85

Bussmann®
Fusetron®
FRS-R
Dual-Element, Time-Delay Fuses
Class RK5 –– 600 Volt
65-600A
Dimensional Data
A
B
Dimensions (inches)
Ampere Ratings
65-100
110-200
225-400
450-600
Catalog Symbol: FRS-R
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 65 to 600 Amperes †
Voltage Rating: 600 Volts AC (or less)
Interrupting Rating: 200,000A RMS Sym.
DC Ratings (20,000AIC @ 300 Vdc)
Agency Approvals:
U.L. Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-01, File 53787
Catalog Numbers
FRS-R-65
FRS-R-125
FRS-R-300
FRS-R-70
FRS-R-135
FRS-R-325
FRS-R-75
FRS-R-150
FRS-R-350
FRS-R-80
FRS-R-175
FRS-R-400
FRS-R-85
FRS-R-200
FRS-R-450
FRS-R-90
FRS-R-225
FRS-R-500
FRS-R-100
FRS-R-250
FRS-R-600
FRS-R-110
FRS-R-275
—
Carton Quantity and Weight
Weight*
Ampere
Ratings
Carton
Qty.
Lbs.
Kg.
65–100
1
0.54
0.245
101–200
1
1.22
0.544
201–400
1
3.00
1.359
401–600
1
5.00
2.268
A
7.88 (± 0.062)
9.63 (± 0.062)
11.63 (± 0.094)
13.38 (± 0.094)
1.11
1.61
2.34
2.88
B
(± 0.020)
(± 0.020)
(± 0.020)
(± 0.020)
General Information:
• Provides motor overload, ground fault and short-circuit
protection. When used in circuits subject to surge currents
such as those caused by motors, transformers and other
inductive components, these fuses can be sized close to
full-load amperes to give maximum overcurrent protection.
• The time-delay feature makes it possible to use fuse ampere
ratings which are much smaller than those of non-time-delay
fuses. Considerable cost saving occurs by permitting the use
of smaller size switches, panels and fuses themselves.
• Provides a good degree of short-circuit protection (greater
current-limitation) to help protect downstream components
from high fault currents.
• Gives motor running back-up protection to motors without
extra costs.
• Helps protect motors against burnout from overloads and
single phasing when sized properly.
• Simplifies and improves blackout prevention (selective
coordination ratios).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high-performance, short-circuit and overload protection.
*Weight per carton.
Fuse Reducers For Class R Fuses
Fuseblocks – Class R Catalog Numbers
(Clip Retaining Spring Standard, Suffix “R”)
Poles
1
Basic
Catalog
Number
R60100-1
Terminal Type (Suffix No.)
Box Lug w/
—
Reinforced Clip
CU only
CR
COR
to
2
R60100-2
CR
COR
100
3
R60100-3
CR
COR
to 200
1
R60200-1
CR
—
to 400
1
R60400-1
CR
—
to 600
1
R60600-1
CR
—
Amps
65
For additional information on the R600 Series fuseblocks, refer to
BIF Document 1111.
† To obtain information for 0-60 Amps, access BIF # 1017
11-1-00
A00115
Equipment
Fuse Clips
200A
400A
600A
Desired
Fuse (Case)
Size
Catalog Number
(Pairs)
600V
100A
No. 2621-R
100A
No. 2641-R
200A
No. 642-R
100A
No. 2661-R
200A
No. 2662-R
400A
No. 2664-R*
*Single reducer only (pair not required).
For additional information, see BIF Document 1118.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Form No. FRS-R 70-600
Page 1 of 3
BIF Doc #1018
Bussmann®
Fusetron®
FRS-R
Dual-Element, Time-Delay Fuses
Class RK5 –– 600 Volt
AMPERE
RATING
600
400
200
300
100
10
TIME IN SECONDS
For information on previous design FRS-R, 70-600, see
BIF Document 1153.
600A
5,000
10,000
13,700
15,000
16,100
17,050
17,900
18,700
20,050
21,250
23,300
25,000
28,450
31,200
100
Time-Current Characteristic Curves–Average Melt
Current-Limiting Effects
FRS-R Apparent RMS Symmetrical Let-Through Current
Prospective
SCC
30A
60A
100A
200A
400A
5,000
1,400
2,000
2,900
3,950
5,000
10,000
1,850
2,650
3,600
5,100
8,550
15,000
2,200
3,200
4,100
5,950
9,750
20,000
2,450
3,550
4,500
6,600
10,700
25,000
2,700
3,900
4,850
7,150
11,500
30,000
2,900
4,280
5,150
7,650
12,200
35,000
3,100
4,400
5,400
8,100
12,800
40,000
3,300
4,760
5,600
8,500
13,400
50,000
3,550
5,150
6,050
9,250
14,400
60,000
3,800
5,500
6,400
9,850
15,250
80,000
4,300
6,100
7,000
10,950
16,750
100,000
4,500
6,600
7,550
11,900
18,000
150,000
5,200
8,000
8,600
13,800
20,550
200,000
5,800
8,500
9,400
15,350
22,550
65-600A
1
.1
40,000
10,000
1,000
100
.01
RMS SYMMETRICAL
CURRENT INCURRENT
AMPERES IN AMPERES
11-1-00
A00115
Form No. FRS-R 70-600
Page 2 of 3
BIF Doc #1018
Bussmann®
Fusetron®
FRS-R
Dual-Element, Time-Delay Fuses
Class RK5 –– 600 Volt
65-600A
Current-Limitation Curves
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
B
400,000
AMPERE
RATING
100,000
600A
400A
200A
100A
10,000
A
200,000
100,000
10,000
1,000
1,000
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPERES
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
11-1-00
A00115
Form No. FRS-R 70-600
Page 3 of 3
BIF Doc #1018