Dual-Element, Time-Delay Construction Grade Fuses
Class RK5 – 250 Volt, ⁄Ω¡º-600 Amps
Dimensional Data
3"
(± 0.31)
2"
(± 0.31)
.81" (± 0.008)
.56" (± 0.008)
1/10A
to 30A
35A to 60A
5.88"
(± 0.062)
1.06" (± 0.008)
70A to 100A
7.13"
(± 0.062)
Catalog Symbol: DLN-R
Current-Limiting
Dual-Element, Time-Delay – 10 seconds (minimum)
at 500% rated current
Electrical Rating: 250 Volts AC (or less)
Self-Certified for DC under UL 198L
125 VDC (⁄Ω¡º-60A)
250 VDC (70-600A)
Interrupting Rating: 200,000A RMS Symmetrical
20,000A DC
Agency Approvals:
UL Listed, Std. 248-12, Class RK5, Guide 198E, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers
1.56" (± 0.008)
110A to 200A
8.63"
(± 0.094)
2.06" (± 0.008)
225A to 400A
10.38"
(± 0.094)
2.59" (± 0.008)
450A to 600A
DLN-R-1
DLN-R-15
DLN-R-100
DLN-R-2
DLN-R-20
DLN-R-125
DLN-R-2⁄Ω™
DLN-R-25
DLN-R-150
DLN-R-3
DLN-R-30
DLN-R-175
DLN-R-3¤Ω¡º
DLN-R-35
DLN-R-200
DLN-R-4
DLN-R-40
DLN-R-225
DLN-R-5
DLN-R-45
DLN-R-250
DLN-R-6
DLN-R-50
DLN-R-300
DLN-R-6⁄Ω¢
DLN-R-60
DLN-R-400
DLN-R-8
DLN-R-70
DLN-R-600
DLN-R-10
DLN-R-80
—
Carton Quantity and Weight
DLN-R-12
DLN-R-90
—
Ampere
Ratings
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
• Designed for contractor needs.
• Protects industrial equipment and large motors.
• Recommended for AC power distribution system mains,
feeders and branch circuits.
• Industry standard time-delay of 10 seconds at 5 times
the fuse rating.
Weight*
Carton
Qty.
Lbs.
Kg.
⁄Ω¡º–30
10
0.56
0.252
35–60
10
1.38
0.621
70–100
5
1.56
0.702
110–200
1
0.90
0.405
225–400
1
1.80
0.810
450–600
1
3.30
1.485
*Weight per carton.
12-17-98
SB98107
Rev. A
Form No. DLN-R
Page 1 of 2
BIF Doc #1021
Bussmann®
Dura-Lag
DLN-R
Dual-Element, Time-Delay Construction Grade Fuses
Class RK5 – 250 Volt, ⁄Ω¡º-600 Amps
600
400
200
100
60
AMPERE
RATING
10
0.1
RMS SYMMETRICAL CURRENT IN AMPERES
10
.01
100
.01
10
.1
1
.1
RMS SYMMETRICAL CURRENT IN AMPERES
10,000
1
1,000
1
100
TIME IN SECONDS
TIME IN SECONDS
10
30
100
15
AMPERE
RATING
10
1
1.25
1.6
2
2.5
3.2
4
5
6.25
.6
.8
.2
.3
.4
100
.1
.5
Time-Current Characteristic Curves–Average Melt
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-17-98
SB98107
Rev. A
Form No. DLN-R
Page 2 of 2
BIF Doc #1021