ETC SV160230

Level Sensors
Amplifier, Capacitive
Types SV 150/250, SV 160/260
• Level control for solid, fluid, or granulated
substances
• SV 150/250: Max./min. control of DISCHARGING
• SV 160/260: Max./min. control of CHARGING
• Factory-set sensitivity
• For capacitive sensors VR.. and VRY..
• 10 A SPDT or 8 A DPDT output relay
• LED-indication: SV 150/250: Power supply and relay ON
•
SV 160/260: Relay ON
• AC or DC power supply
SV 150/250
SV 160/260
Product Description
Ordering Key
Level control relays for
capacitive sensors, types VR
and VRY. The relays can con-
Housing
Output
Power supply
trol one or two levels of
charging (SV 160/260) or discharging (SV 150/250).
SV 150 024
Type Selection
Plug
Output
Function
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
Supply: 24 VDC
Circular
SPDT
DPDT
SPDT
DPDT
Discharging
Discharging
Charging
Charging
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
SV
150
250
160
260
024
024
024
024
150
250
160
260
115
115
115
115
150
250
160
260
230
230
230
230
Input Specifications
Supply Specifications
Sensitivity
Power supply AC-types
Rated operational voltage
through pin 2 & 10
230
115
024
Rated insulation voltage
Rated impulse withstand
voltage
Sensor voltage
Sensor current
Activated
Not activated
Sensor short-circuit current
depends on sensor type
and material
max. 24 VDC
terminal 6 is negative
min. 15 mA, max. 20 mA
max. < 5 mA
max. 45 mA
General Specifications
Indication for
Output ON
Power supply
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Approvals
CE-marking
150
250
160
260
724
724
724
724
Overvoltage cat. II (IEC 60664)
230 VAC ± 15%
115 VAC ± 15%
24 VAC ± 15%
≥ 2.0 kVAC (rms)
4 kV (1.2/50 µs)
(line/neutral)
Power supply DC-types
Installation cat. II (IEC 60664)
Rated operational voltage 724 24 VDC ±15% (pin 2 pos.)
Rated insulation voltage
None
Rated transient protection volt. 800 V (1.2/50 µs)
LED, red
LED, green
(only SV 150/250)
IP 20 B
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
UL, CSA
Yes
Specifications are subject to change without notice (25.06.99)
1
SV 150/250, SV 160/260
Output Specifications
Output
Rated insulation voltage
Contact ratings (Ag-CdO)
Resistive loads
AC 1
DC 1
or
AC 15
DC 13
Small inductive loads
Mechanical life
Electrical life
Operation frequency
Insulation voltages
Rated insulation voltage
AC
DC
AC
Rated impulse withstand voltage
DC
SV150/SV160
SV250/SV260
SPDT relay
250 VAC (rms)
(cont./elec.)
µ (micro gap)
10 A/250 VAC (2500 VAC)
1 A/250 VAC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 5 x 107 operations
≥105 operations
≤ 7200 operations/h
DPDT relay
250 VAC (rms)
(Cont./elec., cont./cont.)
µ (micro gap)
8 A/250 VAC (200 VA)
0,4 A/250 VDC (100 W)
4 A/25 VDC (100 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 5 x 107 operations
≥105 operations
≤ 7200 operations/h
≥ 2.0 kVAC (rms)
(cont./elect.)
None
4 kV (1.2/50 µs)
(cont./elect.) (IEC 60664)
800 V
≥ 2.0 kVAC (rms)
(cont./elect.)
None
4 kV (1.2/50 µs)
(cont./elect.) (IEC 60664)
800 V
Mode of Operation
Max. and/or min. control of
solid, fluid or granulated
substances, e.g. sand,
gravel, sugar or chemicals.
SV 150/250: Relay control of
DISCHARGING
SV 160/260: Relay control of
CHARGING
Example 1
The diagram shows the level
control connected as max.
and min. control, i.e. registration of 2 levels during charging (discharging).
The relay releases (operates)
when the max. sensor is in
contact with the substance,
provided that the min. sensor
is immersed. The relay operates (releases) when the min.
sensor is no longer in contact
with the substance.
of 1 level during charging (discharging).
The relay releases (operates)
when the sensor is in contact
with the substance.
Example 1
The diagram shows the level
control connected as max. or
min. control, i.e. registration
Wiring Diagrams
Example 1: Two levels max./min.
Example 2: One level
Max.
Min.
Power Supply
2
Max. or Min.
Power Supply
Specifications are subject to change without notice (25.06.99)
SV 150/250, SV 160/260
Operation Diagrams
SV 150/250 DISCHARGING
SV 160/260 CHARGING
Example 1
Example 1
Power supply
Power supply
Max.
Max.
Min.
Min.
Relay on
Relay on
Example 2
Example 2
Power supply
Power supply
Max./Min.
Max./Min.
Relay on
Relay on
Accessories
Sensors: Types VR and VRY
Bases
Hold down spring
Base covers
Front mounting bezel
Optical: VP
Capacitive: DR, EC
Specifications are subject to change without notice (25.06.99)
3