J54 SERIES WATERFLOW AND SUPERVISORY SWITCHES DESCRIPTION The J54 sprinkler switches are designed to activate upon alarms in either wet or dry pipe sprinkler systems. Model 8295 is UL Listed for supervisory service as well as being UL Listed and FM approved as a waterflow alarm switch to sound local or central station alarms. Models 8300 and 8305, primarily used as supervisory and/or control switches for sprinkler systems, are UL Listed and designed to receive approval upon submission of total system to Factory Mutual. FEATURES • Model 8295 FM Approved for 20,000 Cycle Life Requirement at 125 PSI Testing, Qualified in FM Leak Test to 500 PSI • Model 8295 UL Tested for 100,000 Cycles at all E/R Loads and Normal Pressure. • Model s 8300 and 8305 Qualified in UL Leak Test Minimum Requirement of 350 PSI Without Leakage or Rupture • Calibration Accuracy Maintained up to 300 PSI • Buna-N Dacron-backed Diaphragm Sensor for Fast Response and Repeatability ±1% of range ORDERING INFORMATION/SPECIFICATIONS Part No. 117-2110A 117-1120A 117-1130A Model J54/8295 J54/8300 J54/8305 Pressure Connection: Contact Type: Contact Ratings: Adjustable Range 2 to 15 PSI 10 to 100 PSI 20 to 200 PSI On-Off Differential 0.7 to 1.7 PSI 1.0 to 2.5 PSI 1.5 to 4.0 PSI 1/2" NPT male polysulphone* SPDT 15 amps @ 125/150 VAC 10 amps @ 12 VDC 1/4 HP @ 125 VAC 125 VA Pilot Duty at 125/150 VAC *1/8" and 1/4" NPT male aluminum pressure connections available Specifications are provided for information only and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 1997 All Rights Reserved 301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132 9020-0037/Ver. 1.3