1174 SERIES Operating Voltage = 115/250 Vac Operating Current Max= 10 amps Operating Frequency = 50 - 60Hz Operating Temperature = -20 to +70oC ** See note below. Diel Withstand ( L to Case)= 1500V~for 1 Min. Diel Withstand ( L to L )= TVS Diode protected to 390-430VDC Leakage current @ 250V~60Hz= 1.0 mA at 250Vac, 50Hz Max Residual Voltage after 5 secs = 34 Volts Max Agency Approvals =Pending The 1174 Series was designed to be used with very high frequency switching power supplies such as the Vicor "HAM" units. The specific design of this filter is to control the conducted emissions to meet the requirements of EN55022. ** Heat Sink Required 8.7A Operating Current --- 80 C Max. Heatsink Temperature 9.0A Operating Current --- 75 C Max. Heatsink Temperature 10.0A Operating Current --- 70 C Max. Heatsink Temperature USA JMK Inc 15 Caldwell Dr. Amherst, NH 03031 EUR JMK Inc Glasgow G13 1DN Scotland UK PH: 603 886-4100 FX: 603 886-4115 email: [email protected] PH: 44-(0) 7785310729 Fax: 44-(0) 141 589 1884