ALLEN-BRADLEY 1336R-VB180-AN-HAB

1336 REGEN
Line Regeneration Package
The 1336 REGEN Line Regeneration Package is a line regeneration
option for 1336 PLUS, 1336 PLUS II, 1336 IMPACT™ and
1336 FORCE™ AC drives. In a regenerative brake configuration (bus
supply configuration is also available, see page 4), the 1336 REGEN is
used to remove braking energy from the DC bus of a stand-alone AC
drive and return it back to the three-phase AC utility, where it is absorbed
by other loads. In many regenerative applications, the 1336 REGEN
offers an energy-efficient alternative to dynamic brakes and chopper
module/resistor combinations.
The 1336 REGEN Line Regeneration Package consists of:
• A converter that transforms a three-phase AC input source into a DC
output source.
• A precharge unit that limits the inrush current and provides AC line
voltage phase and magnitude information to the converter.
A 3% 1321 Line Reactor is also required to limit current harmonics on
the AC line and to provide impedance between the regenerative brake
and the attached drive.
Conformity to Standards
The 1336 REGEN conforms to the following:
Standard
UL Listed
CSA Certified (C-UL)
Standard Products Program
Allen-Bradley
Conformity
✔
✔
This program includes standard 1336 REGEN Line Regeneration
Packages for use in regenerative brake applications rated from 48 to 180
Amps. Mounting options include IP00 (open) and IP20 (NEMA Type 1).
There is a limited offering of factory mounted options, along with a
larger offering of option kits for user installation. All products in this
program are predefined and not generally subject to modification.
1
1336 REGEN
Line Regeneration Package
Product Selection
1336R –
Bulletin
Number
Code
VB
1336 REGEN Catalog Number Explanation
VB
180
Drive Rating
(must be specified)
Nominal Current Rating
(must be specified)
Voltage
380-480VAC,
Three-Phase, 50/60 Hz.
Code
048
078
180
–
AA
–
HAB
Enclosure Type
(must be specified)
kW (Hp)
38.4 (48.2)
62.3 (78.2)
143.7 (180.4)
Code
AA
AN
Human Interface Module,
(must be specified)
Enclosure
IP 20 (NEMA Type 1)
IP 00 (Open)
Code
Description
IP 20 (NEMA Type 1)
HAB
HAP
Blank - No Functionality
Programmer Only
1336 REGEN Package (Includes Converter and Precharge Module)
Nominal Brake Rating
IP00 (Open)
No Enclosure
IP20 (NEMA Type 1)
General Purpose
Frame
Input Amps
Output kW
Code
Code
B
C
D
48.2
78.2
180.4
38.4
62.3
143.7
VB048-AN
VB078-AN
VB180-AN
VB048-AA
VB078-AA
VB180-AA
Required 3% Line Reactor (Supplied Loose for Customer Mounting)
IP00 (Open), No
Enclosure
IP20 (NEMA Type 1), General
Purpose
Frame
Brake Rating Catalog Number
Catalog Number
B
C
D
VB048
VB078
VB180
1321-3RA55-B
1321-3RA100-B
1321-3RA200-B
1321-3R55-B
1321-3R100-B
1321-3R200-B
1336 REGEN Brake Example
The diagram below shows the components needed for a 1336 REGEN
brake configuration at 78 Amps. Note that the 1336 REGEN precharge
unit is included in the base catalog number of the 1336 REGEN Line
Regeneration Package. The 3% reactor is also required to provide proper
line impedance.
1336
AC Drive
AC Input
DC
1336
REGEN
Precharge
3% Line
Reactor
included in REGEN
1321-3R100-B
part number 1336R-VB078
Factory Installed Options
1336
REGEN
Converter
1336R-VB078-AN
Interface Options
Description
Used with
Option Code
Human Interface Module, IP 20 (NEMA Type 1) IP 00 (Open) and IP 20
(NEMA Type 1) Drives -HAB
Blank - No Functionality
-HAP
Programmer Only
2
Allen-Bradley
1336 REGEN
Line Regeneration Package
User Installed Options
Gasket and Enclosure Kits
Description
Used with
Catalog Number
Gasket Kits for mounting 1336 REGEN
Converter Units in User Supplied IP 54 or 65
(NEMAType12or4) Encl.
Frame B
Frame C
Frame D
Frame B
Frame C
Frame D
1336-RF4
1336-RF5
1336-RF6
1336R-AA4
1336R-AA5
1336R-AA6
Enclosure Kits for 1336 REGEN Converter
IP 20 (NEMA Type 1)
Human Interface Module (HIM) Kits - User Installed
ESC
Description
HIM
SEL
JOG
HIM
Cradle
Option Cable
1202-H03/H10/H30/H90
Used with . . .
Catalog Number
(Loose Kit)
All Open Chassis and IP 20
IP 20 (NEMA Type 1) HIM
(NEMA Type 1) converter ratings 1201-HAB
Blank - No Functionality
1201-HAP
Programmer Only
Option Cable Kit - Connect to HIM Cradle Port All HIMs not mounted on the
converter chassis
1202-H03
0.33 Meters (1.1 Feet)
1202-H10
1 Meter (3.3 Feet)
1202-H30
3 Meter (9.8 Feet)
1202-H90
9 Meter (29.5 Feet)
Refer to the 1336 PLUS II Price List (publication number 1336F-PL001) for other options.
Communication Option Kits
Option Cable to Drive
(1202-C03/C10/C30/C90)
to PLC
RIO
SCANport
Comm
Status
Input Voltage
DIN Rail
120/240V AC
Input
Communication Module
GD1/GD2 – Typical Configuration
Mounts to
Drive Main
Control Board
to PLC
GM1/GM2, GM5/GM6 – Typical Configuration
Flex Modules
FB1 and FM1 – Typical Configuration
Description
Used with . . .
Remote Mounted (DIN Rail) – 115VAC
Requires 115VAC power supply
Single Point RIO
RS232/422/485, DF1 and DH485 Protocol
Remote Mounted (DIN Rail) – 24V DC
Requires 24VDC power supply
Single Point RIO
RS232/422/485, DF1 and DH485 Protocol
DeviceNet™
Enhanced DeviceNet™
ControlNet™ to SCANport Adapter
Remote Mounted (DIN Rail) – 24V DC
Requires 24VDC power supply
Flex™ I/O SCANport Module
Flex I/O Terminal Base
Flex I/O Module
Each FM1/FB1 combination provides a connection
for up to 2 drive products.
Serial Flash Cable
Connects CN1, GU6 and SSS to a computer RS232 port for adapter programming and for
DriveTools32™ & DriveExplorer™ serial interface.
SLC™ Communication Module
(SLC 500 to SCANport Module)
Provides a connection for up to 3 drive products.
Smart Serial to SCANport Adapter
Includes 1203-SFC and 1202-C10 Cables
Serial Null Modem Adapter
Universal Serial Bus™ (USB) Converter
Includes 2m USB, 20-HIM-H10 & 22-HIM-H10
Cables
All Converter Ratings
Catalog Number
(Loose Kit)
1203-GD1➊
1203-GD2➊
All Converter Ratings
All Converter Ratings
1203-GK1➊
1203-GK2➊
1203-GK5➊
1203-GU6➊➌
1203-CN1➊➌
All Converter Ratings
1203-FB1➋
1203-FM1➊➋
All Converter Ratings
1203-SFC
All Converter Ratings
1203-SM1➊
All Converter Ratings
1203-SSS
All Drives
1203-SNM
1203-USB
➊ Requires a Communication Option Cable (1202-C03/C10/C30/C90) to be functional. These units are not acceptable for NEMA Type 4 door mounting or UL Type
4X outdoor duty.
➋ Each Flex I/O SCANport Module requires (1) 1203-FB1 and (1) 1203-FM1.
➌ Adapter is programmed/configured with Windows® HyperTerminal via RS-232 using the 1203-SFC cable, (purchased separately) or using a compatible network
specific software tool.
Allen-Bradley
3
1336 REGEN
Line Regeneration Package
Communication Option Kits (continued)
Description
Used with . . .
Communication Option Cable Kit
0.33 Meters (1.1 Feet)
1 Meter (3.3 Feet)
3 Meter (9.8 Feet)
9 Meter (29.5 Feet)
SCANport™ Expander Option
One to Two Port Expander Module
One to Four Port Expander Module
One to Two Port Splitter Cable
All External
Communication
Options Listed
Above
Catalog Number
(Loose Kit)
1202-C03
1202-C10
1202-C30
1202-C90
All Drive Ratings
1203-SG2
1203-SG4
1203-S03
Drive Software
Description
DriveTools32™ Software
DriveExecutive™ Software
DrvieExplorer™ Software
Packaged Program
See publication 9303-PL002… for Ordering/Pricing Information
Factory configured and assembled Regenerative Brake or DC Bus
Supply Packages are available. Consult A-B for details.
Disc.
3% Line
Reactor
EMI
Filter
w/3%
Reactor
1336
AC Drive
1336 REGEN
Line
Regeneration
Package
Disc.
10%
Line
Reactor
Disc.
Disc.
Disc.
Disc.
1336
AC Drive
1336
AC Drive
1336
AC Drive
1336
AC Drive
1336R
Line
Regeneration
Package
1336 REGEN Regeneration Brake Configuration
1336 REGEN Regeneration DC Bus Supply Configuration
1336 REGEN Bus Supply
The 1336 REGEN Bus Supply is available as a packaged product. The
bus supply is used to provide a DC bus for several common-bus input AC
drives. This configuration requires a 10% reactor and an EMI filter/3%
reactor combination for high frequency noise attenuation. Contact your
local Sales Office for details.
AC Input
3% Line
Reactor
EMI
Filter
1336
REGEN
Precharge
10% Line
Reactor
1336
REGEN
Converter
DC
DC
Common
Bus
Drive
DC
Common
Bus
Drive
1336 FORCE, 1336 IMPACT, SCANport, Flex, DriveTools32, DriveExplorer & SLC are trademarks of
Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their
respective companies.