DELTA DRR-20A

CliQ II Redundancy Module 20A 40A
Features
RoHS Compliant
Relay alarm indirection
Built-in 2 channel DC OK signal
caused by rugged handing
Ease of wire connection to terminals
Wide Input & Output Range 22-60 Vdc
Full corrosion resistance aluminium
chassis even with deep scratches
Model No. DRR-20A , DRR-40A
Weight:
0.37Kg, 0.51Kg
Size:
121 mm X 50 mm X 122.1 mm (H x W x D)
Description
The new Redundancy Module DRR 20A is the latest offering from one of the World’s No.1 Power Supply
Company. The product offers a variable input & output voltage from 22-60V, a wide temperature range from
-40°C to 80°C. The state-of-the-art design is made to withstand harsh industrial environments. The rugged,
compact aluminium case is shock and vibration resistant according to IEC60068-2-6. Due to the wide input
& output voltage range from 22 to 60Vdc, the Delta’s CliQ II Redundancy Module is able to support power
supply in parallel operation. The DRR module has an alarm relay contact as an indicator.
DRR-20A
1)
Input terminal block connector
2)
Output terminal block connector
3)
LED indicator of V in 1 & V in 2
4)
Universal mounting rail system
5)
Earth connection
www.deltaPSU.com
DRR-40A
1
CliQ II Redundancy Module 20A 40A
Mechanical Drawing:
DRR-20A
Dimension (W x H x D) + Mounting Rail
Weight
121mm x 50mm x122.1mm
0.37 Kg
DRR-40A
Dimension (W x H x D) + Mounting Rail
Weight
www.deltaPSU.com
121mm x 50mm x122.1mm
0.51 Kg
2
CliQ II Redundancy Module 20A 40A
Block Diagram:
DRR-20A
DRR-40A
www.deltaPSU.com
3
CliQ II Redundancy Module 20A 40A
Derating Curve: Model DRR 20A, 40A
NOTE
1. Do not use the Redundancy Module in areas outside the shaded portion as shown in the above
graph, internal parts may occasionally deteriorate or be damaged.
2. For the power derating refer above graph ambient temperature > 50°C, the output capacity has to
be reduced by 2.5% per degree Celsius increase in temperature. If the output capacity is not
reduced when Amb > 50°C, some device will run into thermal stress problem, the ORing diodes
will get too hot.
3. If the Redundancy Module has to be mounted in any other direction please contact your service
provider.
4. In order for the device to function in the manner intended, it is also necessary to observe lateral
spacing of 20mm. to other modules.
5. Depending on the ambient temperature and load of the device, the temperature of the housing can
become very high!
www.deltaPSU.com
4
CliQ II Redundancy Module 20A 40A
Redundancy operation with DRP 20A- (40A)
Parallel Operation
When 2 Power Supplies are connected in parallel, they can share the load if the following steps are taken.
Step1. Measure the output voltages at no load from Anode1 to Ground i.e. Voltage Anode1 to Ground of PSU1 and
Voltage Anode2 to Ground of PSU2. If the voltages are not the same, follow Step 2. If they are the same, skip to Step 3.
Step2. . Adjust the output voltages, with the help of VR on the Power Supply front panel market as ADJUST, to the
same level. For e.g. if PSU1 is measuring 24.15Vdc and PSU2 is measuring 24.25Vdc, adjust the output voltage of one
to be the same as the other
Step3. Connect the Power Supply to the end system load and measure the output voltages from A1 to Ground i.e.
Voltage Anode 1 to Ground of PSU1 and Voltage Anode 2 to Ground of PSU2. Ensure that the output voltages are the
same even after the 2 Power Supplies are connected to load. If not, adjust them with the VR available on the front panel.
A tolerance of +/-25mV would be acceptable.
Note
1)
If the output voltage of any Power Supply is higher, it will take the initial load and share the maximum load.
2)
If the output voltages are the same, then an equal load current sharing between the 2 Power Supplies can be
achieved.
3)
The ORing diode must be of an appropriate rating. The rating must be at least 4 times of the output load current
and at least reverse voltage rating of 20Vrr.
4)
The use of a heat sink is advised to ensure the ORing Diode does not overheat.
5)
Recommended Redundancy Module: DRR-20A
www.deltaPSU.com
5
CliQ II Redundancy Module 20A 40A
Redundancy Module
DRR- 20A
1.) INPUT DATA
Nominal input voltage
Voltage range
Nominal current
DRR- 40A
24-48VDC
22-60VDC
40A max
20A max
24V system:
48V system:
both Vin1 & Vin2 >36V +/- 5% or
Input voltage alarm / relay contacts
both Vin1 & Vin2 >18V +/- 5% or
<60V max. relay contacts
<30V max. relay contacts
Note: The LED will turn on when The Vin1 & Vin2 > 18V +/- 5% (For 24V system) or > 36V +/- 5% (For 48V system) and not
more than 30V (For 24V system) or not more than 60V (For 48V system), The relay contacts will be closed. If Vin1 & Vin2 is under
or over this range, The LED will be turn off.
2.) OUTPUT DATA
Nominal output voltage UN / tolerance
Vin-0.65V (Typ)
Nominal current
20A max / 40A max
Derating above +50 °C
> 50°C (2.5% / K.)
(<50A for DRR- 40A)
Short circuit / Over Load Limit
(<25A for DRR- 20A)
Note: The overload condition must be controlled by The PSUs in parallel; The limit of input current would not more than 25A (For
20A module) or not more than 50A (For 60A module).
Efficiency
> 97% typical.
3.) CERTIFICATION / STANDARDS
Electrical equipment of machines
IEC60204-1 (over voltage category III)
UR/cUR recognized to UL60950-1, SIQ BG to EN60950-1, CB test certificate and report
Electrical safety (information technology equipment)
to IEC60950-1 and CE.
Industrial Control Equipment
UL/cUL recognize to UL508
Electronic equipment for use in electrical power
EN50178 / IEC62103
installations
Safety entry low voltage
PELV (EN60204), SELV (EN60950)
RoHS Compliant
Yes, RoHS directive, WEEE directive
Protection against electric shock
DIN 57100-410
4.) GENERAL DATA
Isolation voltage:
Input / PE
type
test/routine test:
1.5 KVAC / 1.5 KVAC
output / PE
type
1.5 KVAC / 1.5 KVAC
test/routine test:
Degree of protection
IP20
Class of protection
Class II with PE connection
MTBF
> 800,000hrs. as per BELL CORE STD or IEC61709
Type of housing
Aluminium (AL1100F)
Dimensions (W / H / D) + mounting rail
121 mm X 50 mm X 122.1 mm (L X W X H)
0.515Kg
Weight
0.375Kg
LED (DC INPUT OK)
Vin1 OK and Vin2 OK (GREEN LED)
5.) CLIMATIC DATA
Ambient temperature (Operating)
- 40°C to 80°C (> 50°C derating)
Ambient temperature (Storage)
- 40°C to 85°C
Humidity
at+25 °C, no condensation
< 95% RH
10Hz to 500Hz @ 30 m/S2 (3G peak); displacement of 0.35mm; 60min per axis for all
Vibration (Non-Operating)
X, Y, Z direction. Refer to IEC 60068-2-6. Note: all figures quoted are amplitudes (peak
values)
IEC60068-2-27, 30G (300m/s2) for duration 18ms 1 Shock in 2 Directions tested with
Shock (in all directions)
Fixture with EUT mounted on DINRAIL in Vertical and Horizontal position.
Pollution degree
2 according to EN50178
Climatic class
3K3 according to EN 60721
Conformance with EMC guideline
DRR-40A(EOE21010285)
2004/108/EC and for low voltage guideline
DRR-20A (EOE21010284)
2006/95/EC :
EMC (electromagnetic compatibility)
Immunity to interference :
CE (EMC and Low Voltage directive)
According to EN 61000-6-2
 EN 61000-4-2 1)
Discharge of static electricity (ESD)
Housing:
LEVEL 4
Contact discharge:
8 KV
Air Discharge:
15 KV
 EN 61000-4-3 1)
Radiate Field Immunity Housing:
LEVEL 3
Frequency/Field intensity:
80MHz - 1GHz / 10V/M with 1kHz tone / 80% modulation
 EN 61000-4-8 2)
Power frequency magnetic fields Input:
Level 3
Current:
10A/meter
EN55011 corresponds to CISPR11 / EN55022 corresponds to CISPR22 / EM 61000 corresponds to IEC 1000
1) Criterion A:
Normal operating behavior within the defined limits.
2) Criterion B:
Temporary impairment to operational behavior that is corrected by the device itself.
3) Symmetrical: Conductor to conductor.
4) Asymmetrical: Conductor to ground.
5) Class B:
Area of application industry and residential.