OMRON E5ER

Programmable Digital Controller
E5ER-T
CSM_E5ER-T_DS_E_3_1
A new 48 × 96-mm High-speed, Highprecision Digital Controller that is
Programmable!
• Create up to 32 programs with up to 256 segments total.
• 0.01°C High resolution for Pt input.
• High-speed sampling at 50 ms.
• Settings easily made from a computer using the CX-Thermo.
• RoHS compliance for world-wide application.
Refer to Safety Precautions for All E5@R
Models.
Model Number Structure
■ Model Number Legend
E5ER-T@@@@@@@@-@@@
1 2 3 4 5 6 7 8
9
1. Control method
Blank:Standard or heating/cooling control
P:
Position proportional control
2. Output 1
R:
NO relay output + NO relay output
Q:
Pulse output/current output + pulse output
C:
Current output + current output
3. Output 2
R:
NO relay output + NO relay output
Q:
Pulse output/current output + pulse output
C:
Current output + current output
4. Auxiliary Outputs
Blank:None
4:
NO relay output + NO relay output
T:
2 transistor outputs
5. Communications
Blank: None
3:
RS-485 communications
6. Optional Function
Blank: None
D:
4 event inputs
7. Input 1
B:
Universal-input and 2 event inputs
F:
Universal-input and FB
W:
Universal-input and universal-input
8. Input 2
Blank: None
W:
Universal-input and universal-input
9. Other
FLK:
CompoWay/F communications
(3 digits): (Modification type)
Note: The above model number legend is intended as a functional description of models. Not all possible combinations of functions are available.
Confirm model availability in Ordering Information when ordering.
Note: Be sure to read the precautions for correct use and other precautions in the following user's manual before using the Digital
Controller.
E5AR/ER Digital Controller User's Manual (Cat. No. Z182)
1
E5ER-T
Ordering Information
■ Digital Controllers
Programmable Digital Controllers
Size
48 × 96
mm
Control type
Control mode
Outputs (control/
transfer)
Optional functions
Model
Event
inputs
Serial
communications
2
None
E5ER-TQ4B
RS-485
E5ER-TQC43B-FLK
2 (pulse + pulse/cur- 2
4
2-loop control 2-loop standard control
(See Note
Single-loop heating and cooling control rent)
Single-loop cascade control
2 (current + current) 2.)
Single-loop control with remote SP
Single-loop proportional control
RS-485
E5ER-TQT3DW-FLK
Control valve
control
(1 loop)
2
4
(See Note
2.)
None
E5ER-TPRTDF
4
RS-485
E5ER-TPRQ43FFLK
Basic control
(1 loop)
Standard control
Heating and cooling control
Auxiliary
outputs
(SUB)
2 (pulse + pulse/cur- 4
rent)
2 (current + current)
E5ER-TC4B
2 (pulse + pulse/current)
Single-loop position-proportional control Relay outputs
(1 open, 1 closed)
Relay outputs
(1 open, 1 closed)
and 1 current
None
E5ER-TCT3DW-FLK
Note 1: Specify the power supply specifications when ordering. Model numbers for 100 to 240 VAC are different from those for 24 VAC/VDC.
2: The outputs are transistor output.
Inspection Results
If an inspection report is required, it can be ordered at the same time
as the Digital Controller using the following model number.
Inspection Report (Order Separately)
Model
E5ER-K
■ Accessories (Order Separately)
Terminal Cover
Descriptions
Terminal Cover for E5ER
Model
E53-COV15
Rubber Packing
Model
Y92S-P5
Note: The Rubber Packing is provided with the Digital Controller.
2
E5ER-T
Specifications
■ Ratings
Supply voltage
(See note 2.)
CE Marking
100 to 240 VAC, 50/60 Hz
UL certification
100 to 120 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
17 VA max. (with maximum load)
Sensor input (See note 3.)
Thermocouple: K, J, T, E, L, U, N, R, S, B, W
Platinum resistance thermometer: Pt100
Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input)
Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input)
(Input impedance: 150 Ω for current input, approx. 1 MΩ for voltage input)
Control output
11 VA/7 W max. (with maximum load)
Voltage (pulse) output 12 VDC, 40 mA max. with short-circuit protection circuit
Current output
0 to 20 mA DC, 4 to 20 mA DC; load: 500 Ω max. (including transfer output)
(Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC)
Relay output
Position-proportional control type (open, closed)
N.O., 250 VAC, 1 A (including inrush current)
Auxiliary output
Relay Output
N.O., 250 VAC, 1 A (resistive load)
Transistor Output
Maximum load voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max.
Potentiometer input
100 Ω to 2.5 kΩ
Event input
Contact
Input ON: 1 kΩ max.; OFF: 100 kΩ min.
No-contact
Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max.
Short-circuit: Approx. 4 mA
Remote SP input
Refer to the information on sensor input.
Transfer output
Refer to the information on control output.
Control method
2-PID or ON/OFF control
Setting method
Digital setting using front panel keys or setting using serial communications
Indication method
7-segment digital display and single-lighting indicator
Character Height
PV display: 9.5 mm; SV display: 7.2 mm; MV display: 7.2 mm
Other functions
Depends on model.
Ambient operating temperature
−10 to 55°C (with no icing or condensation)
For 3 years of assured use: −10 to 50°C (with no icing or condensation)
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no icing or condensation)
Note 1: Do not use an inverter output as the power supply. (Refer to Safety Precautions for All E5@R Models.)
2: The supply voltage (i.e., 100 to 240 VAC or 24 VAC/VDC) depends on the model. Be sure to specify the required type when ordering.
3: The Controller is equipped with multiple sensor input. Temperature input or analog input can be selected with the input type setting switch.
There is basic insulation between power supply and input terminals, power supply and output terminals, and input and output terminals.
■ Input Ranges
Platinum Resistance Thermometer, Thermocouple, Current, or Voltage Input
Input type
Pt100
Name
Temperature
range (°C)
Thermocouple
Platinum
resistance
thermometer
2300
1800
1300
900
800
700
600
400
200
100
0
−100
−200
Setting
Minimum
setting unit
(SP and alarm)
Input type
setting switch
K
J
T
E
L
U
N
R
S
B
1700.0
1700.0
1800.0
Current
Voltage
mA
V
W
( W/Re
5-26 )
2300.0
1300.0
1300.0
850.0
850.0
850.0
500.0
20 to
4
600.0
400.0
400.0
400.0
10 to
20 to
5 to 1 5 to 0
0
0
150.00
100.0
0.0
−200.0 −150.00 −200.0
0
1
0.1°C
0.01
°C
2
−20.0
−100.0
−20.0
3
4
5
−100.0
−200.0
6
7
−200.0
−200.0
9
10
8
0.1°C
0.0
0.0
11
12
0.0
13
14
15
16
17
TC.PT
Set to TC.PT.
IN1
TYPE
ANALOG
18
19
(Depends on scaling and number
of decimal places.)
TC.PT
Set to ANALOG
IN1
TYPE
ANALOG
Note: The shaded area indicates the setting status at the time of purchase.
3
E5ER-T
■ Characteristics
Indication accuracy
Thermocouple input with cold junction compensation: (±0.1% of PV or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Thermocouple input without cold junction compensation: (±0.1% FS or ±1°C, whichever is smaller) ±1 digit (See note 2.)
Analog input: ±0.1% FS ±1 digit max.
Platinum resistance thermometer input: (±0.1% of PV or ±0.5°C, whichever is greater) ±1 digit max.
Position-proportional potentiometer input: ±5% FS ±1 digit max.
Control mode
Standard control (heating or cooling control), heating/cooling control, standard control with remote SP (2-input models only), heating/cooling
control with remote SP (2-input models only), cascade standard control (2-input models only), cascade heating/cooling control (2-input models only), proportional control (2-input models only), position-proportional control (control-valve control models only)
Influence of
temperature
Thermocouple input (R, S, B, W): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*K-type thermocouple at -100°C max.: ±10°C max.
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Influence of voltage
Control period
0.2 to 99.0 s (in units of 0.1 s) for time-proportioning control output
Proportional band (P)
0.00% to 999.99% FS (in units of 0.01% FS)
Integral time (I)
0.0 to 3,999.9 s (in units of 0.1 s)
Derivative time (D)
0.0 to 3,999.9 s (in units of 0.1 s)
Hysteresis
0.01% to 99.99% FS (in units of 0.01% FS)
Manual reset value
0.0% to 100.0% (in units of 0.1% FS)
Alarm setting range
−19,999 to 99,999 EU (See note 3.)
(The decimal point position depends on the input type and the decimal point position setting.)
Input sampling period 50 ms
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between charged terminals of different polarities)
Vibration resistance
(malfunction)
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Shock resistance
(malfunction)
100 m/s2, 3 times each in X, Y, and Z directions
Inrush current
100 to 240-VAC models: 50 A max.
24 VAC/VDC models: 30 A max.
Weight
Controller only: Approx. 330 g; Mounting bracket: Approx. 60 g; Terminal cover: Approx. 16 g
Degree of protection
Front panel: NEMA4X for indoor use; Rear case: IP20; Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 100,000)
Applicable standards
UL 61010C-1, CSA C22.2 No. 1010-1
(Power supply voltage: 100 to 120 VAC): Pollution degree 2/Overvoltage category 2
EN 61010-1 (IEC 61010-1) (Power supply voltage: 100 to 240 VAC): Pollution degree 2/Overvoltage category 2
EMC
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1 Class A
Noise Terminal Voltage: EN55011 Group 1 Class A
EMS: EN61326
ESD Immunity: EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
10 V/m (amplitude-modulated, 80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3)
EN61000-4-4:2 kV power line (level 3)
2 kV output line (relay output) (level 4)
1 kV measurement line, I/O signal line (level 4)
1 kV communications line (level 3)
Conducted Disturbance Immunity: EN61000-4-6:
3 V (0.15 to 80 MHz) (level 3)
Surge Immunity:
EN61000-4-5:1 kV line to line (power line, output line (relay output)) (level 2)
2 kV line to ground (power line, output line (relay output)) (level 3)
Power Frequency Magnetic Field Immunity: EN61000-4-8: 30 A/m (50 Hz) continuous field
Voltage Dip/Interrupting Immunity: EN61000-4-11:
0.5 cycle, 100% (rated voltage)
Electromagnetic Immunity: EN61000-4-3:
Burst Noise Immunity:
Note 1: K-, T-, or N-type thermocouple at −100°C max.: ±2°C ±1 digit max.
U- or L-type thermocouple: ±2°C ±1 digit max.
B-type thermocouple at 400°C max.: No accuracy specification.
R- or S-type thermocouple at 200°C max.: ±3°C ±1 digit max.
W-type thermocouple: (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
2: U- or L-type thermocouple: ±1°C ±1 digit
R- or S-type thermocouple at 200°C max.: ±1.5°C ±1 digit
3: “EU” (Engineering Unit) represents the unit after scaling. If a temperature sensor is used, it is either °C or °F.
4
E5ER-T
■ Communications Specifications
Transmission path connection
Multiple points
Communications method
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Baud rate
9,600, 19,200, or 38,400 bps
Transmission code
ASCII
Data bit length
7 or 8 bits
Stop bit length
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC): CompoWay/F
CRC-16: Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer
217 bytes
Communications response send wait time 0 to 99 ms, Default: 20 ms
■ Program Control Functions
Number of programs (patterns)
32 (with 8 segments/program)
Number of segments (steps)
32 (with 8 programs)
Maximum number of segments
256
Segment setting method
Time setting (Segment set with set point and time.)
Gradient setting (Segment set with set point, gradient, and time.)
Segment times
0 h 0 min to 99 h 59 min
0 min 0 s to 99 min 59 s
0 min 00.0 s to 99 min 59.9 s
Alarm group num- Number of sets
ber specifications Setting method
4
Reset operation
Select either stopping control or fixed SP operation.
Startup operation
PID sets
Set separately for each program.
Select continuing, resetting, manual operation, run mode, or ramp back operation.
Number of sets
Setting method
Alarm SP function
8
Set separately for each program (automatic PID group selection also supported).
Select from ramp SP and target SP.
Program status
control
Segment operation
Advance, hold, and back
Program operation
Program repetitions and program links
Wait operation
Wait method
Select from waiting at segment ends and always waiting.
Wait width setting
Wait width upper limit and lower limit set separately for each program.
Setting method
ON/OFF setting for each segment
Number of outputs
6
Number of ON/OFF
operations
3 each per output
Setting method
Set separately for each program.
Time signals
Segment outputs Number of outputs
Setting method
10
ON/OFF set for each segment.
Program status output
Program end output (pulse width can be set)
Segment number output
Program startup
operation
PV start
Select from segment 1 set point, gradient-priority PV start, and time-priority PV start.
Standby
Standby
Operation end operation
Select from resetting, continuing control at final set point, and fixed SP control.
Number of event inputs
10 max.
5
E5ER-T
Wiring Terminals
■ E5ER-T (Programmable Type)
SUB2
5
6
1
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
SUB3
Event input
EV1
EV2
COM
+
−
TC
PT
+
−
+
C D E
−
+
+ 3
OUT2
Voltage output 12 V
−
4
40 mA
OUT1
+ 5
Voltage output 12 V
40 mA or
− 6
Current output
4 to 20 mA DC, 500 Ω max.
0 to 20 mA DC, 500 Ω max.
(Switched by output type setting.)
OUT2
Current output
I
V
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
SUB1
3
4
COM
SUB2
5
6
1
SUB4
2
COM
2
SUB3
SUB4
Event input
EV1
2
+
4 to 20 mA DC, 500 Ω max.
0 to 20 mA DC, 500 Ω max. −
(Switched by output
+
type setting.)
OUT1
−
Current output
4 to 20 mA DC, 500 Ω max.
0 to 20 mA DC, 500 Ω max.
(Switched by output type setting.)
EV2
3
4
COM
5
6
C D E
TC
PT
+
COM
!
Auxiliary output
(Relay output)
+
3
4
−
B
1
−
SUB1
A
100 to 240 VAC
−
COM
2
+
V
−
−
−
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
1
24 VAC/DC
+
!
B
A
100 to 240 VAC
+
−
24 VAC/DC
E5ER-TC4B
Auxiliary output
(Relay output)
+
E5ER-TQ4B
I
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
E5ER-TQC43B-FLK
100 to 240 VAC
Auxiliary output
(Relay output)
1
COM
2
SUB1
3
4
SUB2
5
6
1
SUB3
COM
SUB4
Event input
EV1
2
EV2
3
4
COM
−
5
6
+
C D E
TC
+
+
B(+)
RS-485
OUT2
A(−) −
Voltage output 12 V
+
40 mA
OUT1
−
Voltage output 12 V
40 mA or
+
Current output
4 to 20 mA DC, 500 Ω max. −
0 to 20 mA DC, 500 Ω max.
(Switched by output type setting.)
B
−
+
−
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
A
−
−
!
+
24 VAC/DC
+
PT
V
I
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
1
OUT4
Current output
+
2
3
4 to 20 mA DC, 500 Ω max.
−
0 to 20 mA DC, 500 Ω max.
4
(Switched by output
+
type setting.)
5
−
OUT3
6
Current output
4 to 20 mA DC, 500 Ω max.
D
0 to 20 mA DC, 500 Ω max.
(Switched by output type setting.)
Note
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5ER-T to comply with CE
marking requirements.
The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5ER-T to comply with UL
requirements.
6
E5ER-T
−
−
−
+
+
PT
V
I
−
2
4 to 20 mA DC, 500 Ω max. +
0 to 20 mA DC, 500 Ω max.
−
(Switched by output
type setting.)
+
OUT1
Current output
−
4 to 20 mA DC, 500 Ω max.
0 to 20 mA DC, 500 Ω max.
(Switched by output type setting.)
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
1
+
3
4
5
6
C D E
Auxiliary output
(Transistor output)
SUB1
−
+
SUB2
−
SUB1
SUB2
V
I
4
5
6
D
−
EV3
3
4
EV4
5
6
1
EV6
COM
3
4
C
PT
+
−
+
TC
V
I
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
1
2
+
−
+
Note
OUT2
−
5
6
C D E
SUB2
B(+)
RS-485
A(−)
O Potentiometer
W
Auxiliary output
(Transistor output)
SUB1
−
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
EV5
2
−
3
4
5
6
D
!
OUT1
+
−
1
2
3
4
5
6
C
Relay output
250 VAC 1 A
B
Auxiliary output
(Relay output)
1
COM
2
SUB1
3
4
SUB2
5
6
1
SUB3
COM
SUB4
Potentiometer
O
2
W
Closed
3
4
C
Open
5
6
C D E
1
TC
+
2
−
Open
1
A
100 to 240 VAC
24 VAC/DC
+
Event input
+
Closed
B
−
Relay output
250 VAC 1 A
A
+
OUT1
4
5
6
C
PT
−
+
1
3
TC
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
−
!
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
OUT2
Input 1
+
100 to 240 VAC
2
Input 2
E5ER-TPRQ43F-FLK
+
−
−
I
3
−
+
−
+
V
2
+
3
4
5
6
D
E5ER-TPRTDF
24 VAC/DC
PT
1
2
+
TC
+
TC
Input 1
EV6
COM
+
C D E
I
EV5
−
+
V
+
PT
Input 2
EV4
−
−
+
TC
5
6
Auxiliary output
(Transistor output)
−
3
4
−
2
B(+)
RS-485
A(−)
EV3
3
4
5
6
1
COM
OUT2
Current output
2
−
EV5
−
+
5
6
1
EV6
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
+
EV4
Event input
+
EV3
3
4
B
−
B(+) +
RS-485
OUT2
A(−) −
Voltage output 12 V
+
40 mA
OUT1
−
Voltage output 12 V
40 mA or
+
Current output
4 to 20 mA DC, 500 Ω max. −
0 to 20 mA DC, 500 Ω max.
(Switched by output type setting.)
2
+
+
Input power supply
depends on model.
100 to 240 VAC or 24
VAC/DC (no polarity)
A
1
!
−
!
100 to 240 VAC
24 VAC/DC
+
Event input
−
−
−
B
1
+
+
−
A
100 to 240 VAC
24 VAC/DC
E5ER-TCT3DW-FLK (2-loop Control)
+
E5ER-TQT3DW-FLK (2-loop Control)
PT
V
I
(Thermocouple)
(Voltage) (Current)
(Resistance temperature input sensor)
2
OUT4
+
Voltage output 12 V
3
40 mA
−
OUT3
4
Voltage output 12 V
+
5
40 mA or
−
Current output
6
4 to 20 mA DC, 500 Ω max.
0 to 20 mA DC, 500 Ω max. D
(Switched by output type setting.)
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5ER-T to comply with CE
marking requirements.
The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5ER-T to comply with UL
requirements.
7
E5ER-T
Nomenclature
E5ER-T
Operation
Indicators
Rear
SUB1 SUB2 SUB3 SUB4 WAIT FSP
Display No. 1
PV
Display No. 2
SV
CH2
CMW
MANU
Display No. 3
PRG.
SEG
OUT1 OUT2 RST RSP HOLD
Mode Key
Down Key
Up Key
Level Key
PF1
PF2
RUN/RST
Function Key 1/
Run/Reset Key
E5ER
Function Key 2
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5ER-T
110
95
11.5
48
2
3
44
SUB1 SUB2 SUB3 SUB4 WAIT FSP
PV
SV
96
CH2
CMW
MANU
CH2
CMW
MANU
PRG.
SEG
111
91
OUT1 OUT2 RST RSP HOLD
PF1
RUN/RST
PF2
E5ER
Crimp terminal size: M3
Terminal cover (E53-COV15; order separately)
Panel Cutouts
+0.6
450
60 min.
120 min.
+0.8
920
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible. (Maintain the specified
mounting space between Controllers.)
• When two or more Controllers are mounted, make sure
that the surrounding temperature does not exceed the
allowable operating temperature specified in the specifications.
8
E5ER-T
■ Accessories (Order Separately)
Terminal Cover
E53-COV15 (for E5ER)
48
95
28.5
10.1
Unit Label Sheet
Y92S-L1
11.8
4.8
Rubber Packing
Y92S-P5 (for DIN48 × 96)
Order the Rubber Packing separately if it becomes lost or damaged. (Refer to page 2.)
The Rubber Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the rubber packing may occur depending on the operating
environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing
specified in NEMA4. The time for periodic replacement depends on the operating environment.
Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be
liable for the level of water resistance if the customer does not perform periodic replacement.)
The Rubber Packing does not need to be attached if a waterproof structure is not required.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
9
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.3
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.