AC-DC 40-100 Watts xppower.com ECM Series • Compact Size - High Power Density • Industrial & Medical Approvals • Low Leakage Current • Level B Conducted Emissions • EN61000-3-2, -3 Compliant • Convection-cooled • Class II Approved 40-60 W Models Specification Input Input Voltage Input Frequency Input Current • 90-264 VAC (120-370 VDC) • 47-63 Hz; 440 Hz • 40 W: 0.4 A max at 230 VAC 60 W: 0.6 A max at 230 VAC 100 W: 0.9 A max at 230 VAC Inrush Current • 40 A max at 230 VAC Earth Leakage Current • <125 µA at 115 VAC/60 Hz <210 µA at 230 VAC/50 Hz Input Protection • Internal 3.15 A fuse in line and neutral Output Output Voltage Output Voltage Trim • See tables • ±5% on 3.3 V & 5 V versions, ±10% on other single output models and V1 of multi-output models. See note 1 for ECM40/60 models Initial Set Accuracy • ±1.0% V1, ±5% V2, V3 & V4 Minimum Load • See tables Start Up Delay • 2 s max Start Up Rise Time • 50 ms Hold Up Time • 16/75 ms min at 115/230 VAC Line Regulation • ±0.5% Load Regulation • ±1% single output models; ±3% V1, ±5% V2 & V3 ECM40/60 multi-output models. ±1% V1 & V2, ±5% V3 & V4 ECM100 Cross Regulation • 2% on ECM40/60 only Over/Undershoot • None at turn on/off Transient Response • 4% max. deviation, recovery to within 1% in 500 µs for a 25% load change Ripple & Noise • 1% pk-pk, 20 MHz bandwidth Overvoltage Protection • 115-135% Vnom, recycle input to reset Overload Protection • 110-150% on primary power limit, auto recovery Short Circuit Protection • Trip and restart (Hiccup mode) Temperature • 0.05%/°C Coefficient General Efficiency Isolation Switching Frequency Power Density MTBF • 80-85% depending on model • 4000 VAC Input to Output 1500 VAC Input to Ground 500 VAC Output to Ground • 70 kHz typical • 60 W: 6.25 W/In3 100 W: 7.40 W/In3 • 250 kHrs per MIL-HDBK-217F Environmental Operating Temperature • 0 °C to +70 °C. Refer to derating curves for specific operating limitations. Cooling • Convection & fan-cooled ratings (see derating curves) Operating Humidity • 95% RH, non-condensing Storage Temperature • -20 °C to +85 °C Operating Altitude • 3000 m Shock • 30 g pk, half sine, 6 axes Vibration • 2 g rms, 5 Hz to 500 kHz, 3 axes EMC & Safety Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge Conducted Immunity Dips & Interruptions Safety Approvals • EN60601-1-2, EN61204-3, FCC 20780, EN55022 & EN55011, level B conducted • EN61000-3-2 • EN61000-3-3 • EN61000-4-2, level 2 Perf Criteria A • EN61000-4-3, 10 V/m Perf Criteria A • EN61000-4-4, level 3 Perf Criteria A • EN61000-4-5, level 3 Perf Criteria A • EN61000-4-6, 10 V Perf Criteria A • EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms Perf Criteria A, B, B • EN60950, UL60950, CSA 22.2 601.1, EN60601-1, UL60601-1, CCC pending, contact sales Output 1 Max Power Voltage +5.0 +7.0 +9.0 +12.0 +15.0 +18.0 +24.0 +33.0 +48.0 +5.0 +5.0 +5.0 +5.0 +5.0 +3.3 +5.0 40 W V V V V V V V V V V V V V V V V Output 2 Current Min/Max(3) 0.0 A/8.0 A 0.0 A/5.7 A 0.0 A/4.4 A 0.0 A/3.5 A 0.0 A/2.7 A 0.0 A/2.2 A 0.0 A/1.7 A 0.0 A/1.2 A 0.0 A/0.9 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A 0.5 A/6.0 A Voltage +12.0 +15.0 +12.0 +24.0 +15.0 +5.0 +3.3 Output 3 Current Min/Max V V V V V V V 0.1 0.1 0.1 0.1 0.1 0.1 0.1 A/2.0 A/1.5 A/2.0 A/1.0 A/1.5 A/1.5 A/1.5 A A A A A A A -12.0 -12.0 -15.0 +12.0 +12.0 Model Number(2) Current Min/Max Voltage V V V V V 0.0 0.0 0.0 0.0 0.0 A/0.5 A/0.5 A/0.5 A/0.5 A/0.5 A A A A A ECM40US05†^ ECM40US07 ECM40US09^ ECM40US12†^ ECM40US15†^ ECM40US18 ECM40US24†^ ECM40US33 ECM40US48†^ ECM40UD21 ECM40UD22 ECM40UT31†^ ECM40UT32† ECM40UT33†^ ECM40UT34†^ ECM40UT35† Notes 1. V2 will track a change in V1 by the same percentage change in voltage as V1 is trimmed. 2. To receive unit with cover fitted, add suffix ‘-C’ to model number. For Class I operation only. 3. A 120% peak load can be taken for up to 100 ms with a 25% duty cycle. Average load not to exceed 40 W. † Available from Farnell. See pages 204-206. ^ Available from Newark. See pages 207-208. Mechanical Details 1.20 (30.5) 4.00 (101.6) Input Connector J1 Pin 1 Line Pin 2 Neutral 3.75 (95.25) J1 2.00 (50.8) J1 mates with Molex housing 43061-0003 & Molex series 5194 crimp terminals 1 2 1 J2 1.75 (44.45) 6 Pin 1 2 3 4 5 6 V Adj. 4X ø0.156 (3.96) mounting holes ø0.312 (7.92) clearance top and bottom 0.14 (3.5) SMD component height Output Connector J2 Single Multi +V1 +V1 +V1 +V1 RTN RTN RTN RTN NC -V3 NC +V2 J2 mates with Molex housing 43061-0006 & Molex series 5194 crimp terminals Weight: approx. 0.33 lb (150 g) Notes 1. All dimensions in inches (mm). Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25) 2. Cable harnessess with 300 mm wire available. For single output models, order part number ECM40/60S LOOM†. For multi-output models, order part number ECM40/60DT LOOM†. 3. Mating connector kit available. Order part number ECM40/60 CONKIT†. 4. Covers available. Order part number ECM40/60 COVER^†. Cover dimensions are 4.49 x 2.52 x 1.52 (114 x 64 x 38.5) Derating Curves All ECM40 models with 5 CFM 100% Output Power Output Power All ECM40 models convection-cooled 75% 50% 25% 0% 100% 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (°C) 70 80 0 10 20 50 60 30 40 Ambient Temp (°C) Note: Derate by 10% if cover is fitted Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications. 70 80 AC-DC ECM40 Models and Ratings Output 1 Max Power Voltage +5.0 +7.0 +9.0 +12.0 +15.0 +18.0 +20.0 +24.0 +33.0 +48.0 +5.0 +5.0 +5.0 +5.0 +5.0 +3.3 +5.0 60 W V V V V V V V V V V V V V V V V V Output 2 Current Min/Max(3) 0.0 A/12.00 A 0.0 A/8.60 A 0.0 A/6.70 A 0.0 A/5.00 A 0.0 A/4.00 A 0.0 A/3.30 A 0.0 A/3.00 A 0.0 A/2.50 A 0.0 A/1.80 A 0.0 A/1.25 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A 0.5 A/8.00 A Voltage +12.0 +15.0 +12.0 +24.0 +15.0 +5.0 +3.3 Output 3 Current Min/Max V V V V V V V 0.1 0.1 0.1 0.1 0.1 0.1 0.1 A/3.0 A/2.5 A/3.0 A/1.5 A/2.5 A/1.5 A/1.5 A A A A A A A -12.0 V -12.0 V -15.0 V +12.0 V +12.0 V Model Number(2) Current Min/Max Voltage 0.0 0.0 0.0 0.0 0.0 A/0.5 A/0.5 A/0.5 A/0.5 A/0.5 A A A A A ECM60US05†^ ECM60US07 ECM60US09^ ECM60US12†^ ECM60US15†^ ECM60US18 ECM60US20 ECM60US24†^ ECM60US33 ECM60US48†^ ECM60UD21 ECM60UD22 ECM60UT31†^ ECM60UT32† ECM60UT33†^ ECM60UT34†^ ECM60UT35† Notes 1. 2. 3. 4. V2 will track a change in V1 by the same percentage change in voltage as V1 is trimmed. To receive unit with cover fitted, add suffix ‘-C’ to model number. For Class I operation only. A 120% peak load can be taken for up to 100 ms with a 25% duty cycle. Average load not to exceed 60 W. 48 V DC input version of 12 V single output model available in OEM quantities (DCM6048S12). Contact sales for details. † Available from Farnell. See pages 204-206. ^ Available from Newark. See pages 207-208. Mechanical Details Input Connector J1 Pin 1 Line Pin 2 Neutral 1.20 (30.5) 4.00 (101.6) 3.75 (95.25) J1 2.00 (50.8) J1 mates with Molex housing 43061-0003 & Molex series 5194 crimp terminals. Optional ground (0.25 faston) tab available, contact sales. 1 2 1 J2 1.75 (44.45) Pin 1 2 3 4 5 6 6 Output Connector J2 Single Multi +V1 +V1 +V1 +V1 RTN RTN RTN RTN NC -V3 NC +V2 J2 mates with Molex housing 43061-0006 & Molex series 5194 crimp terminals. V Adj. 4X ø0.156 (3.96) mounting holes ø0.312 (7.92) clearance top and bottom 0.14 (3.5) SMD component height Weight: approx. 0.33 lb (150 g) Notes 1. All dimensions in inches (mm). Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25) 2. Cable harnesses with 300 mm wire available. For single output models, order part number ECM40/60S LOOM†. For multi-output models, order part number ECM40/60DT LOOM†. 3. Mating connector kit available. Order part number ECM40/60 CONKIT†. 4. Covers available. Order part number ECM40/60 COVER^†. Cover dimensions are 4.49 x 2.52 x 1.52 (114 x 64 x 38.5). 5. Selected single output models available in a 3” x 5” footprint for OEM quantities. Contact sales for details. Derating Curves All ECM60 models convection-cooled All ECM60 models with 5 CFM Output Power 100% Output Power AC-DC ECM60 Models and Ratings 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (°C) 70 80 100% 75% 50% 25% 0% 0 10 Note: Derate by 10% if cover is fitted 20 50 60 30 40 Ambient Temp (°C) Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications. 70 80 AC-DC ECM100 Models and Ratings Single Output Models Output Voltage +3.3 V +5.0 V +7.0 V +9.0 V +12.0 V +15.0 V +18.0 V +24.0 V +33.0 V +48.0 V Output Current Maximum 15.0 A 15.0 A 11.4 A 8.8 A 7.5 A 6.0 A 5.0 A 4.1 A 3.0 A 2.1 A Minimum 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A Model Number(1,3) ECM100US03*†^ ECM100US05*†^ ECM100US07* ECM100US09*† ECM100US12*†^ ECM100US15*†^ ECM100US18* ECM100US24*†^ ECM100US33* ECM100US48*†^ with 5 CFM Cooling 20.0 A 20.0 A 14.3 A 11.1 A 8.3 A 6.6 A 5.5 A 4.1 A 3.0 A 2.1 A Multi Output Models Output Power Convection Forced Air Cooled 5 CFM 80 W 100 W 80 W 100 W 75 W 100 W 80 W 100 W 80 W 100 W 65 W 100 W 70 W 100 W 80 W 100 W 70 W 100 W 65 W 100 W 60 W 100 W 80 W 100 W 80 W 100 W 80 W 100 W 80 W 100 W Output 1 Current Voltage Min/Max +5.0 V 0.0 A/12.0 A +5.0 V 0.0 A/12.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +3.3 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +3.3 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A +5.0 V 0.5 A/10.0 A Output 2 Current Voltage Min/Max +12.0 V 0.0 A/3.0 A +15.0 V 0.0 A/3.0 A +12.0 V 0.0 A/3.0 A +24.0 V 0.0 A/2.0 A +15.0 V 0.0 A/3.0 A +5.0 V 0.0 A/5.0 A +3.3 V 0.0 A/5.0 A +12.0 V 0.0 A/3.0 A +15.0 V 0.0 A/3.0 A +3.3 V 0.1 A/5.0 A +5.0 V 0.1 A/5.0 A +24.0 V 0.1 A/2.0 A +24.0 V 0.1 A/2.0 A +12.0 V 0.1 A/3.0 A +15.0 V 0.1 A/3.0 A Output 3 Current Voltage Min/Max -12.0 -12.0 -15.0 +12.0 +12.0 -5.0 -5.0 +12.0 +12.0 +12.0 +15.0 -12.0 -15.0 V V V V V V V V V V V V V 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 A/0.8 Output 4 Current Voltage Min/Max A A A A A A A A A A A A A -12.0 -12.0 -12.0 -15.0 -5.0 -5.0 V V V V V V 0.0 0.0 0.0 0.0 0.0 0.0 A/0.5 A/0.5 A/0.5 A/0.5 A/0.5 A/0.5 A A A A A A Model Number(1,3) ECM100UD21* ECM100UD22* ECM100UT31*†^ ECM100UT32* ECM100UT33*†^ ECM100UT34*^ ECM100UT35* ECM100UT36* ECM100UT37* ECM100UQ41*† ECM100UQ42*†^ ECM100UQ43*†^ ECM100UQ44*† ECM100UQ45*^ ECM100UQ46* Notes 1. To receive unit with cover fitted, add suffix ‘-C’ to model number. 2. Output 3 available with opposite polarity for OEM quantities. 3. ‘*’ denotes ECM100 models are class I only, contact sales for class II. 4. 48 VDC input version of 12 V single output model available in OEM quantities (DCM10048S12). † Available from Farnell. ^ Available from Newark. See pages 204-208. Mechanical Details Weight: approx. 0.4 lb (180g) 4.50 (114.3) Input Connector J1 Pin 1 Line Pin 2 Neutral 1.20 (30.5) 4.25 (107.95) J1 mates with Molex housing 43061-0003 and Molex series 5194 crimp terminals. Optional ground (0.25 faston) tab available. 1 2.50 (63.5) Pin 1 2 3 4 5 6 7 8 9 10 11 12 2 J1 2.25 (57.15) 1 J2 12 V Adj. 4X ø0.156 [3.96] mounting holes ø0.312 [7.92] clearance top and bottom 0.14 [3.5] SMD component height Cover dimensions are 4.98 x 3.01 x 1.54 (126.5 x 76.4 x 39.0) J2 mates with Molex housing 43061-0012 and Molex series 5194 crimp terminals. Notes 1. All dimensions in inches (mm). Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25) 2. Cable harnessess with 300 mm wire available. For single output models, order part number ECM100S LOOM†. For multi-outputs, p/n ECM100DT LOOM†. Derating Curves 3. Mating connector kit available for single output models. Order part number ECM100S CONKIT†. 4. Covers available. Order part number ECM100 COVER†^. 5. Available in a 3” x 5” footprint for OEM quantities. Contact sales for details. All ECM100 models with 5 CFM B 80 A B C D A C 60 D 40 20 0 0 10 20 50 60 30 40 Ambient Temp (°C) 70 80 US24-48 US12-18 US05 US03 Note: 1. Derate by 10% if cover is fitted. 2. For multi output convectioncooled operation above +50 ºC derate linearly to 50% at +70 ºC. 100% Output Power Output Power (W) All ECM100 single output models convection-cooled 100 Output Connector J2 Single Multi +V1 +V1 +V1 +V1 +V1 +V1 +V1 +V1 V1 RTN RTN V1 RTN RTN V1 RTN RTN V1 RTN RTN NOT USED +V2 NOT USED +V2 NOT USED ±V3 NOT USED -V4 75% 50% 25% 0% 0 10 20 50 60 30 40 Ambient Temp (°C) 70 80 Consult longform datasheet for installation information regarding optimum thermal ratings in convection-cooled applications. 22-Oct-07