SCHURTER GRM4.5402.013

GRM4
Power entry modules with line filter
www.schurter.com/pg06
"Lock and shield" mounting, line switch, fuseh. 5x20 mm with/without voltage sel. (series-parallel)
OU
T
Standard- or Medical-Filter
Snap-In Version
GRM4: with shield and line filter
C14
70° C
Description
Approvals
-VDE License Number: 118913
-UL License Number: E72928
-CSA License Number: 701867
Characteristics
-Ultra-compact design
Time saving "Lock and Shield" snap-in design for rear-panel mounting
-All single elements are already wired
-Fuseholder on the inside of the equipment prevents accidental use of
incorrect fuse-links by the user
-Voltage selector for two voltage ranges
Innovative EMC-shielding with flexible steel segments for an excellent
contact to the panel
-Insulation cover on the rear-side
-Qualified for use in equipment according IEC/EN 60950
E-
-Panel Mount:
Snap-In Version from rear-side
-5 Functions:
Inlet Protection class I, Line switch 2-pole, with or without Fuseholder
for fuse-links 5 x 20 mm, with or without voltage selector, Line filter in
standard and medical version
-On phase-out, not recommended for new design
Other versions on request
-Panel thickness 1.0 / 2 / 2.5 mm (max.)
-Fuseholder 1‑pole
-Line switch 1-pole
-Voltage selector with other marking
References
General Product Information
AS
Weblinks
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
PH
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
0.5 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
0.5 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Solder terminal on request
Solder terminals for voltage selector
Snap-in: 1.5 mm
(other on request)
Thermoplastic, black, UL 94V-0
Terminal
Panel Thickness s
Material: Housing
Approvals, RoHS, CHINA-RoHS, e-Store, SCHURTER-Stock-Check,
Distributor-Stock-Check
Appliance-Inlet /-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Voltage selector
Line Filter
MTBF
EMC products
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
condition) pin-temperature 70 °C, 10 A,
Protection class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Admissible power acceptance at higher ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical details
optional, jumper, 2 digits
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 1'400'000 h acc. to MIL-HB-217 F
GRM4
Power entry modules with line filter
www.schurter.com/pg06
Dimensions
GRM4
Length
48.3 mm
49.5
24
min.8
45.2
E = 31.7 mm with fuseholder
E = 26.25 mm without fuseholder
*) Min. space to remove the fuseholder cover
Technical Data of Filter-Components
Filter-Type
0.5
Standard Version
1
Standard Version
3
Standard Version
6
Standard Version
10
Standard Version
0.5
Medical Version (M5)
1
Medical Version (M5)
3
Medical Version (M5)
6
10
8.6
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
2 x 24
100
2.2
-
2 x 12
100
2.2
-
2 x 2.5
100
2.2
-
2 x 0.78
100
2.2
-
2 x 0.225
100
2.2
-
2 x 24
100
-
1
2 x 12
100
-
1
2 x 2.5
100
-
1
Medical Version (M5)
2 x 0.78
100
-
1
Medical Version (M5)
2 x 0.225
100
-
1
AS
Dimensions
Step 1
6.9 ±0.1
E-
Rated Current
[A]
E
Place the socket in top edge of the panel
cut-out.
Step 3
Push the socket upwards.
Push the socket forward into the panel
cut-out.
PH
Step 2
Release the socket. The component is
self adjusting.
7 ±0.1
OU
1.7
S 0.05
*)
R1
2.2
31.7
5
Step 4
PE
N
4.5
R5
40.9
3.9
38.4
45.4
30.4
8.4
4.5
PE
2
12.5
6.5
42.3
L
+0.1
0
13.4
33.9
T
26.0
EMC products
34.2 ±0.05
GRM4
Power entry modules with line filter
Derating Curves
1-pole
I = 1.0 In
I = 0.7 In
I = < < In
0.5
0.0
20
40
1) Line
2) Load
1) Line
2) Load
60
80
100
Admissible power acceptance in Watt per Pole
Admissible power acceptance in Watt
1.5
0
GRM4 Medical version
2-pole
2.0
1.0
GRM4 Standard version
Ambient air temperature Ta °C
1.6
1.4
1.2
0.8
I = 0.7 In
0.6
I = << In
0.4
0.2
0.0
0
60
80
100
- - - - differential mode _____ common mode
1A
3A
AS
10 A
Medical version (M5)
6A
1A
3A
6A
PH
0.5 A
40
E-
0.5 A
20
Ambient air temperature Ta °C
Attenuation Loss
Standard version
I = 1.0 In
1.0
OU
Diagrams
Voltage selector
T
www.schurter.com/pg06
10 A
EMC products
GRM4
Power entry modules with line filter
www.schurter.com/pg06
Variants
Distributor-Stock-Check | SCHURTER-Stock-Check | e-Store
Basic version:
- Marking of the voltage selector 115/230
- with housing and cover on the rear-side
Filter-Type
Fuseholder
Voltage selector
l
Order Number
6
Standard Version
-
1 pole
0.5
Standard Version
-
2-pole
0.5
Standard Version
-
2-pole
l
1
Standard Version
-
2-pole
l
1
Standard Version
-
2-pole
l
3
Standard Version
-
2-pole
l
3
Standard Version
-
2-pole
l
GRM4.4302.123
6
Standard Version
-
2-pole
l
GRM4.4402.013
6
Standard Version
-
2-pole
l
GRM4.4402.123
10
Standard Version
-
2-pole
l
GRM4.4502.013
10
Standard Version
-
2-pole
l
GRM4.4502.123
0.5
Standard Version
2-pole
2-pole
l
GRM4.4122.013
0.5
Standard Version
2-pole
2-pole
l
GRM4.4122.123
1
Standard Version
2-pole
2-pole
l
GRM4.4222.013
1
Standard Version
2-pole
2-pole
l
GRM4.4222.123
3
Standard Version
2-pole
2-pole
l
GRM4.4322.013
3
Standard Version
2-pole
2-pole
l
GRM4.4322.123
6
Standard Version
2-pole
2-pole
l
GRM4.4422.013
6
Standard Version
2-pole
2-pole
l
GRM4.4422.123
10
Standard Version
2-pole
2-pole
l
GRM4.4522.013
10
Standard Version
2-pole
2-pole
l
GRM4.4522.123
0.5
Medical Version (M5)
-
2-pole
l
GRM4.5102.013
0.5
Medical Version (M5)
-
2-pole
l
GRM4.5102.123
1
Medical Version (M5)
-
2-pole
l
GRM4.5202.013
1
Medical Version (M5)
-
2-pole
l
GRM4.5202.123
3
Medical Version (M5)
-
2-pole
l
GRM4.5302.013
3
Medical Version (M5)
-
2-pole
l
GRM4.5302.123
6
Medical Version (M5)
-
2-pole
l
GRM4.5402.013
6
Medical Version (M5)
-
2-pole
l
GRM4.5402.123
10
Medical Version (M5)
-
2-pole
l
GRM4.5502.013
10
Medical Version (M5)
-
2-pole
l
GRM4.5502.123
0.5
Medical Version (M5)
2-pole
2-pole
l
GRM4.5122.013
0.5
Medical Version (M5)
2-pole
2-pole
l
GRM4.5122.123
1
Medical Version (M5)
2-pole
2-pole
l
GRM4.5222.013
1
Medical Version (M5)
2-pole
2-pole
l
GRM4.5222.123
3
Medical Version (M5)
2-pole
2-pole
l
GRM4.5322.013
3
Medical Version (M5)
2-pole
2-pole
l
GRM4.5322.123
6
Medical Version (M5)
2-pole
2-pole
l
GRM4.5422.013
6
Medical Version (M5)
2-pole
2-pole
l
GRM4.5422.123
10
Medical Version (M5)
2-pole
2-pole
l
GRM4.5522.013
10
Medical Version (M5)
2-pole
2-pole
l
GRM4.5522.123
GRM4.4401.013
GRM4.4102.013
GRM4.4102.123
GRM4.4202.013
GRM4.4202.123
OU
GRM4.4302.013
E-
AS
PH
Packaging unit Line Switch
T
Rated Current
[A]
120 Pcs The
specifications,
descriptions and illustrations indicated in this document are based on
EMC
products
current information. All content is subject to modifications anamendments.