Next Previous Axial Lead and Cartridge Fuses Designed to IEC Standard 5 x 20 mm Fast-Acting Fuse 216/226 Series ® D ® V E • Designed to International (IEC) Standards for use globally. • Meets the IEC 60127-2, Sheet 1 specification for Fast Acting Fuses. • Available in Cartridge and Axial Lead Form. • Available in ratings of 0.050 to 10 amperes. • High breaking capacity. ELECTRICAL CHARACTERISTICS: 150% 210% 275% 400% 1000% Ampere Rating .05 – 3.15 4– 6.3 .05 – 3.15 4– 6.3 .05 – 3.15 4– 6.3 .05 – 3.15 4– 6.3 .05 – 3.15 4– 6.3 Opening Time 60 minutes, Minimum 60 minutes, Minimum 30 minutes, Maximum 30 minutes, Maximum 0.01 sec., Min.; 2 sec. Max. 0.01 sec., Min.; 3 sec. Max. .003 sec., Min.; 0.3 sec. Max. .003 sec., Min.; 0.3 sec. Max. .02 seconds, Maximum .02 seconds, Maximum 216 000 Series 5 (.197") thru 6.3 amps. Recognized under the Components Program of Underwriters Laboratories and recognized by CSA. BSI approved 1A to 6.3A. VDE approved .05-6.3. Ampere Rating .050 .063 .080 .100 .125 .160 .200 .250 .315 .400 .500 .630 .800 1 1.25 1.6 2 2.5 3.15 4 5 6.3 8* 10* Voltage Rating 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 Nominal Resistance Cold Ohms 15.90 10.45 7.89 5.42 3.68 5.20 3.35 2.35 1.85 1.67 1.20 0.790 0.588 0.228 0.153 0.108 0.0770 0.0575 0.0333 0.0243 0.0168 0.0125 0.0120 0.00775 Nominal Melting I2t A2 Sec. 0.00019 0.00055 0.00086 0.0033 0.0056 0.0018 0.0045 0.0092 0.015 0.028 0.045 0.097 0.18 0.19 0.49 1.04 1.92 2.77 7.85 15.4 28.2 57.9 66.1 158.5 100 22.5 MAX (.886) 40 (1.58") 1 0.1 0.01 *IEC Standards for 5 x 20mm fuses do not include ratings above 6.3 amperes, but are under consideration. 0.001 0.05 0.1 1 296 5.25 (.207") 10 TIME IN SECONDS Axial Lead Catalog Number 226.050 226.063 226.080 226.100 226.125 226.160 226.200 226.250 226.315 226.400 226.500 226.630 226.800 226 001 226 1.25 226 01.6 226 002 226 02.5 226 3.15 226 004 226 005 226 06.3 226 008 226 010 20 (.787") Average Time Current Curves ORDERING INFORMATION: Cartridge Catalog Number 216.050 216.063 216.080 216.100 216.125 216.160 216.200 216.250 216.315 216.400 216.500 216.630 216.800 216 001 216 1.25 216 01.6 216 002 216 02.5 216 3.15 216 004 216 005 216 06.3 216 008 216 010 1 .635 (.025") AGENCY APPROVALS: Sheet I IEC 60127-2:* SEMKO approved INTERRUPTING RATING: 1500 amperes. 216 000 XE 226 000 Series .100A .125A .160A .200A .250A .315A .500A .630A .800A 1A 1.25A 1.6A 2A 2.5A 3.15A 4A 5A 6.3A 10A % of Ampere Rating 1 10 CURRENT IN AMPERES 226 Series is used for North American ordering. w w w. l i t t e l f u s e . c o m 100 500