ETC 226002

AXIAL LEAD AND CARTRIDGE FUSES
DESIGNED TO IEC STANDARD
5 x 20 mm Fast-Acting Type
D
®
®
V
E
• Designed to International (IEC) Standards for use globally.
• Meets the IEC 127-2, Sheet 1 specification for Fast Acting
Fuses.
• Available in Cartridge and Axial Lead Form.
• Available in ratings of 0.050 to 10 amperes.
ELECTRICAL CHARACTERISTICS:
150%
210%
275%
400%
1000%
Ampere
Rating
.05 – 3.15
4– 6.3
.05 – 3.15
4– 6.3
.05 – 3.15
4– 6.3
.05 – 3.15
4– 6.3
.05 – 3.15
4– 6.3
Opening
Time
60 minutes, Minimum
60 minutes, Minimum
30 minutes, Maximum
30 minutes, Maximum
0.01 sec., Min.; 2 sec. Max.
0.01 sec., Min.; 3 sec. Max.
.003 sec., Min.; 0.3 sec. Max.
.003 sec., Min.; 0.3 sec. Max.
.02 seconds, Maximum
.02 seconds, Maximum
AGENCY APPROVALS: Sheet I IEC 127-2:* SEMKO
approved thru 6.3 amps. Recognized under the
Components Program of Underwriters Laboratories and
recognized by CSA.KEMA approved to 6.3A. BSI approved
1A to 6.3A. VDE approved .05–.2, .315–6.3.
216 000 Series
.635
(.025")
5
(.197")
100
Axial Lead
Catalog
Ampere Voltage
Number
Rating Rating
226.050
.050
250
226.063
.063
250
226.080
.080
250
226.100
.100
250
226.125
.125
250
226.160
.160
250
226.200
.200
250
226.250
.250
250
226.315
.315
250
226.400
.400
250
226.500
.500
250
226.630
.630
250
226.800
.800
250
226 001
1
250
226 1.25
1.25
250
226 01.6
1.6
250
226 002
2
250
226 02.5
2.5
250
226 3.15
3.15
250
226 004
4
250
226 005
5
250
226 06.3
6.3
250
226 008
8*
250
226 010
10*
250
Nominal
Resistance
Cold Ohms
15.90
10.45
7.89
5.42
3.68
5.20
3.35
2.35
1.85
1.67
1.20
0.790
0.588
0.228
0.153
0.108
0.0770
0.0575
0.0333
0.0243
0.0168
0.0125
0.0120
0.00775
*IEC Standards for 5 x 20mm fuses do not include ratings above
6.3 amperes.
Nominal
Melting I2t
A2 Sec.
0.00019
0.00055
0.00086
0.0033
0.0056
0.0018
0.0045
0.0092
0.015
0.028
0.045
0.097
0.18
0.19
0.49
1.04
1.92
2.77
7.85
15.4
28.2
57.9
66.1
158.5
5.25
(.207")
20.24
(.797")
40
(1.58")
10
TIME IN SECONDS
Cartridge
Catalog
Number
216.050
216.063
216.080
216.100
216.125
216.160
216.200
216.250
216.315
216.400
216.500
216.630
216.800
216 001
216 1.25
216 01.6
216 002
216 02.5
216 3.15
216 004
216 005
216 06.3
216 008
216 010
20
(.787")
Average Time Current Curves
INTERRUPTING RATING: 1500 amperes.
ORDERING INFORMATION:
226 000 Series
.100A
.125A
.160A
.200A
.250A
.315A
.500A
.630A
.800A
1A
1.25A
1.6A
2A
2.5A
3.15A
4A
5A
6.3A
10A
% of Ampere
Rating
1
0.1
0.01
0.001
0.05 0.1
1
10
CURRENT IN AMPERES
100
500
57