SYSTEMSENSOR PIBVEXP

OSYEXP and PIBVEXP
Explosion Proof
Supervisory Switch
System Sensor’s OSYEXP and PIBVEXP explosion proof
supervisory switches are designed for hazardous
locations and to handle extreme conditions.
Features
• Designed and approved to operate in hazardous locations
• NEMA 1, 7 and 9 enclosure rating
These units are ideal for installation in hazardous locations classified
as follows:
Class I, Groups C, D, Division 1 and 2
Class II, Groups E, F, G, Division 1 and 2
• Compact, rugged housing
• Ample wiring space
• Captured cover screws
Intended Use. The OSYEXP is intended for use with outside screw
and yoke type valves, while the PIBVEXP monitors the open position
of post indicator and butterfly type valves.
• Single conduit entrance
Robust Construction. The OSYEXP and PIBVEXP switches
are contained in a compact and rugged NEMA 1, 7 and 9 rated
enclosure. The enclosure operates across a wide temperature range,
from –40°F to 160°F.
Simplified Operation. The OSYEXP and PIBVEXP covers are
secured with four captured screws to prevent screw misplacement
while the cover is removed. A single tapped conduit entrance and
ample wiring space provide quick and easy electrical connection.
OSYEXP, PIBVEXP Specifications
Architectural/Engineering Specifications
Model shall be an OSYEXP or PIBVEXP as manufactured by System Sensor. The OSYEXP and PIBVEXP shall be installed on each valve as designated on the
drawings and/or specified herein. Switches shall be mounted so as not to interfere with the normal operation of the valve and shall be adjusted to operate
within two revolutions of the valve control or when the valve flag has moved no more than one-fifth of the distance from its normal position. The mechanism
shall be contained in a NEMA 1, 7 and 9 rated metal enclosure, which shall provide a side entrance for ½˝ conduit and incorporate a ½˝ NPT nipple for
attachment to the valve body. A grounding provision shall be provided. The switch assembly shall include one SPDT (Form C) switch with a rated capacity of 15
A, 125/250/480 VAC; 1/8 hp, 125 VAC; ¼ hp, 250 VAC; ½ A, 125 VDC; ¼ A, 250 VDC. The cover shall contain captivated screws. The OSYEXP’s and PIBVEXP’s switch
shall be Underwriters Laboratories listed for indoor use and CSA certified.
Physical/Operating Specifications
Overall Dimensions, Installed
OSYEXP: 7˝L × 3.125˝D × 4.875˝H
PIBVEXP: 3.75˝L × 3.25˝D × 4.5˝H
Shipping Weight
OSYEXP: 1.25 lbs.
PIBVEXP: 1.75 lbs.
Operating Temperature Range
–40°F to 160°F (–40°C to 71°C)
Enclosure Rating
NEMA 1, 7 and 9 – suitable for indoor applications
Conduit Entrances
One tapped opening for ½˝ conduit
Pressure Connection
½˝ NPT male brass fitting
Actuating Lever Extension Length for OSYEXP (max.)
2˝ from nipple
Hazardous Locations Classifications
Class I, Groups C, D
Class II, Groups E, F, G
Contact Ratings
One SPDT (Form C) switch:
15 A, 125/250/480 VAC
1⁄8 hp, 125 VAC
¼ hp, 250 VAC
½ A. 125 VDC
¼ A. 250 VDC
Service Use
Automatic Sprinkler: NFPA-13
One or two family dwelling: NFPA-13D
Residential occupancy up to four stories: NFPA-13R
National Fire Alarm Code: NFPA-72
Warranty
3 years
Ordering Information
Part No.
OSYEXP
PIBVEXP
Description
Explosion proof OS&Y supervisory switch
Explosion proof PIBV supervisory switch
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2007 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-1032-003 • 4/07 • #1676