OMRON S8TS02505F

Switch Mode Power Supply
Power
supplies
S8TS
Block-type Switch mode Power Supply That
Mounts to DIN-rail
• Power supply range of 60 to 240 W available with just one model
(24-V models).
• Easy creation of multi-power supply configurations with different
output power supplies connected together (24-V, 12-V, and 5-V
models).
• Improve power supply system reliability by creating N+1 redundant systems (24-V and 12-V models).
• Approved by UL/CSA standards, EN60950 (IEC 950), and VDE
0160.
Model Number Structure
■ Model Number Legend
S8TS-@@@@@@-@@
1
2
1. Capacity
060: 60 W
030: 30 W
025: 25 W
3
4
2. Output Voltage
24: 24 V
12: 12 V
05: 5 V
3. Structure
None: Screw terminals
F:
Connector
terminals
4. Bus Line Connectors
None: Basic Block only
E1:
S8T-BUS01 and
S8T-BUS02
included
Ordering Information
■ Basic Block
Output voltage
Output current
Screw terminal type
With Bus Line
Connectors
(See note 1.)
Connector terminal type
(See note 3.)
Without Bus Line
Connectors
(See note 2.)
With Bus Line
Connectors
(See note 1.)
Without Bus Line
Connectors
(See note 2.)
24 V
2.5 A
S8TS-06024-E1
S8TS-06024
S8TS-06024F-E1
S8TS-06024F
12 V
2.5 A
S8TS-03012-E1
S8TS-03012
S8TS-03012F-E1
S8TS-03012F
5V
5A
---
S8TS-02505
---
S8TS-02505F
■ Bus Line Connector
Type
Number of Connectors
Model number
AC line + DC line bus
(For parallel operation)
1 Connector
S8T-BUS01
10 Connectors (See note 4.)
S8T-BUS11
AC line bus
(For series operation or isolated operation)
1 Connector
S8T-BUS02
10 Connectors (See note 5.)
S8T-BUS12
Note 1. One S8T-BUS01 Connector and one S8T-BUS02 Connector are included as accessories.
2. Bus Line Connectors are ordered separately if necessary.
3. Attached connectors: 2ESDPLM-05P (for output terminal) and 3ESDPLM-03P (for input terminal) made by DINKLE ENTERPRISE.
4. One package contains 10 S8T-BUS01 Connectors.
5. One package contains 10 S8T-BUS02 Connectors.
Switch Mode Power Supply
S8TS
B-53
Specifications
■ Ratings/Characteristics
24/12-V Models (Basic Block: S8TS-06024@/S8TS-03012@)
Item
Single operation
Efficiency
Input
Voltage
100 to 240 VAC (85 to 264 VAC)
Frequency
50/60 Hz (47 to 63 Hz)
Current
100 V input
24-V models: 1.0 A max.
12-V models: 0.7 A max.
24-V models: 1.0 A × (No. of Blocks) max.
12-V models: 0.7 A × (No. of Blocks) max.
200 V input
24-V models: 0.5 A max.
12-V models: 0.4 A max.
24-V models: 0.5 A × (No. of Blocks) max.
12-V models: 0.4 A × (No. of Blocks) max.
Power factor
Leakage current
Inrush current
(25°C, cold start)
(See note 4.)
Output (See
note 3.)
Additional
functions
Other
Parallel operation
24-V models: 75% min.; 12-V models: 70% min. (with rated input, 100% load)
24-V models: 0.9 min.; 12-V models: 0.8 min. (with rated input, 100% load) (See note 3.)
100 V input
0.35 mA max.
0.35 mA × (No. of Blocks) max.
240 V input
0.7 mA max.
0.7 mA × (No. of Blocks) max.
100 V input
25 A max.
25 A × (No. of Blocks) max.
200 V input
50 A max.
50 A × (No. of Blocks) max.
Voltage adjustment range
24-V models: 22 to 28 V
12-V models: 12 V ±10% (with V.ADJ) (See note 1.)
Ripple
2% (p-p) max.
Input variation influence
0.5% max. (with 85 to 264 VAC input, 100% load)
Load variation influence
2% max. (with rated input, 10% to 100% load)
Temperature variation influence
0.05%/°C max. (with rated input and output)
Startup time (See note 4.)
1,000 ms max.
Hold time (See note 4.)
20 ms min. (with 100/200 VAC, rated input)
Overcurrent protection (See note 4.)
105% to 125% of rated load current, inverted L drop
type, automatic reset
Overvoltage protection (See note 4.)
Yes
Parallel operation
Yes, 4 Blocks max.
3% max. (with rated input, 10% to 100% load)
100% to 125% of rated load current inverted L drop
type, automatic reset
N+1 redundant system
Yes, 5 Blocks max.
Series operation
Yes
Undervoltage indicator (See note 4.)
Yes (color: red)
Undervoltage detection output (See
note 4.)
Yes (open collector output), 30 VDC max., 50 mA max.
Ambient operating temperature (See
note 4.)
Operating:
Storage:
Refer to the derating curve in Engineering Data.
−25 to 65°C (with no icing or condensation)
Ambient humidity
Operating:
25% to 85%; Storage: 25% to 90%
Dielectric strength
3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs and all inputs, and between all outputs and GR terminal) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (color: green)
Electromagnetic interference
Conforms to FCC Class A, EN50081-1
EMI
Conforms to EN50081-1/1992
Power factor correction
Conforms to EN61000-3-2, EN61000-3-2 A14
EMS
Conforms to EN61000-6-2/1999
Approved standards
UL:
508 (Listing; Class 2: Per UL1310), 1950, 1604 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations))
CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations), No. 950 (Class 2) (See note 2.)
EN/VDE: EN50178 (=VDE0160), 60950 (=VDE0806)
cUL:
Weight
450 g max.
450 g × (No. of Blocks) max.
Note 1. Refer to page B-59 for details on adjusting the output voltage for parallel operation. If set to less than −10%, the undervoltage detection
function may operate. Ensure that the output capacity and output current after adjustment do not exceed the rated output capacity and
rated output current respectively.
2. Class 2 approval does not apply to parallel operation.
3. The output current is specified at power output terminals.
4. Refer to the explanations of functions on page B-56 for details.
5. Be sure to mount End Plates (PFP-M) on both ends of the Power Supply.
B-54
Switch Mode Power Supply S8TS
5-V Models (Basic Block: S8TS-02505@)
Item
Single operation
Input
62% min. (with rated input, 100% load)
Voltage
100 to 240 VAC (85 to 264 VAC)
Frequency
50/60 Hz (47 to 63 Hz)
Current
100 V input
0.7 A max.
200 V input
0.4 A max.
Power factor
0.8 min. (with rated input, 100% load)
Leakage current
Inrush current
(25°C, cold start)
(See note 2.)
Output (See
note 2.)
Additional
functions
Other
Power
supplies
Efficiency (typical)
100 V input
0.35 mA max.
240 V input
0.7 mA max.
100 V input
25 A max.
200 V input
50 A max.
Voltage adjustment range
5 V ± 10% (with V. ADJ) (See note 1.)
Ripple
2% (p-p) max.
Input variation influence
0.5% max. (with 85 to 264 VAC input, 100% load)
Temperature variation influence
0.05%/°C max. (with rated input and output)
Load variation influence
1.5% max. (with rated input, 10% to 100% load)
Startup time (See note 3.)
1,000 ms max.
Hold time (See note 3.)
20 ms min. (with 100/200 VAC, rated input)
Overcurrent protection (See note 3.)
105% to 125% of rated load current, inverted L drop type, automatic reset
Overvoltage protection (See note 3.)
Yes
Parallel operation
No
N+1 redundant system
No
Series operation
Yes (with the external diode)
Undervoltage indicator (See note 3.)
Yes (color: red)
Undervoltage detection output (See note
3.)
Yes (open collector output), 30 VDC max., 50 mA max.
Ambient operating temperature (See note
3.)
Operating:
Storage:
Refer to the derating curve in Engineering Data.
−25 to 65°C (with no icing or condensation)
Ambient humidity
Operating:
25% to 85%, Storage: 25% to 90%
Dielectric strength
3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs and all inputs, and between all outputs and GR terminal) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (color: green)
Electromagnetic interference
Conforms to FCC Class A, EN50081-1
EMI
Conforms to EN50081-1/1992
Power factor correction
Conforms to EN61000-3-2, EN61000-3-2A14
EMS
Conforms to EN61000-6-2/1999
Approved standards
UL:
cUL:
EN/VDE:
Weight
508 (Listing), 1950, 1604 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations)
CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations), No. 950
EN50178 (=VDE0160), 60950 (=VDE0806)
450 g max.
Note 1. If set to less than −10%, the undervoltage detection function may operate. Ensure that the output capacity and output current after adjustment do not exceed the rated output capacity and rated output current respectively.
2. The output current is specified at power output terminals.
3. Refer to the explanations of functions on page B-56 for details.
4. Be sure to mount End Plates (PFP-M) on both ends of the Power Supply.
■ Reference Value
Item
Value
Definition
Reliability (MTBF)
250,000 hrs min.
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent the
life of the product.
Life expectancy
10 yrs min.
The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load
rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
Switch Mode Power Supply
S8TS