EXTECH 382099

1000A 3-Phase Power Analyzer/Datalogger
Four clamps with simultaneous display
On single phase, 3-phase/3-wire or 3-phase/4-wire systems
Features:
• Large backlighting LCD displays 10
parameters simultaneously (kW, kVAR,
kVA, PF plus the voltage and current of
the 3 phases)
• Up to four current probes can be
connected to the analyzer
• Clamp-on True RMS power
measurements with software for
Harmonics analysis
• Displays Active Power (kW), Apparent
Power (kVA), Reactive Power (kVAR)
and Power Factor
• Current measurements to 1000A and
Voltage measurements to 600V
• kWH, kVARh and kVAh
energy measurements
• Automatically logs up to 20,000 sets of
measurements and manually logs up to
99 sets
Software included to download,
store data, and display on a PC
• Programmable Start/Stop
datalogging times
• PC interface with Windows®
95/98/NT/2000/ME/XP compatible
software for single and three phase
voltage/current Waveform display
and Harmonic analysis
• Phase sequence measurements
Complete with 4 current clamps, 4 voltage leads
with alligator clips, 8 AA batteries, AC adaptor,
software, PC interface cable, and case
Software included for
Harmonics Analysis
• Auto power off with disable feature
• CAT III-1000V, UL Listed; CE approved;
1yr warranty
Applications:
• AC Power Quality Evaluation
• Harmonic Analysis
• Motor/Generator Installation
• Energy Audits
Specifications
ACV (True rms)
ACA
Active Power (kW)
Apparent Power (kVA)
Reactive Power (kVAR)
Power Factor
Frequency
Phase
Active Power Energy (kWh)
Apparent Power Energy (kVAh)
Reactive Power Energy (kVARh)
Harmonics
Datalogging
Dimensions
Weight
Range
999.9V
1000A
999.9kW
999.9kVA
999.9kVAR
-1.000 to +1.000
60Hz to 100Hz
+90.0°~ 11°~ -90.0°
0.0kWh to 119.3MWh
0.0kVAh to 119.3MVAh
0.0kVARh to 119.3MVARh
1 to 31 (with the software)
20,000 reading
9.25 x 4.5 x 2.1" (235 x 116 x 54mm)
Meter: 25.8oz (730g); Clamp: 11.8oz (333g)
Basic Accuracy
±(0.5%rdg+10d)
±(2%rdg+20d)
±(1.5%rdg+20d)
±(1.5%rdg+20d)
±(1.5%rdg+20d)
±(3%rdg+30d)
±(0.5%rdg+1d)
±(3°+30d)
±(1.5%rdg+20d)
±(1.5%rdg+20d)
±(1.5%rdg+20d)
±(1.5%rdg+20d)
Ordering Information:
382090................1000A 3-Phase Power Analyzer/Datalogger (60Hz)
382091................1000A 3-Phase Power Analyzer/Datalogger (50Hz)
382099................Voltage Test Leads with Alligator Clips (4 leads)
USB100 ..............RS-232 to USB Adaptor
www.extech.com
Specifications subject to change without notice.
6/5/08 - R1
Copyright © 2007-2008 Extech Instruments Corporation. All rights reserved including the right of reproduction in whole or in part in any form.