SCHURTER T9-311C-16A

circuit breakers
Resettable Thermal Circuit Breaker, Single Pole, 4–16 A
T9-311: Threaded neck
T9-311 with cover TZZ31
T9-611: Snap-in from front side
Description
Applications
–
–
–
–
–
–
–
–
–
–
–
–
–
Thermal circuit breaker
Supplementary protector for general industrial use
Cycling trip-free release
Reset type
Single pole
Mounting style: T9-311: Threaded neck
T9-611: Snap-in front side
T9-711: Snap-in rear side
T9-711: Snap-in from back side
Power supplies
UPS
Power tools
Household appliances
Industrial appliances
Medical diagnostic appliances
HVAC
Weblinks
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
Standards
– IEC 60934
– UL 1077
– CSA C22.2 235
– GB 17701
Technical Data
Rated voltage
(see approvals)
Rated current
Conditional short circuit capacitiy
Overload rating
Degree of protection
IEC: Inc, PC1, AC 240 V
CSA: SC, AC 240 V / DC 48/32 V
According to CSA C22.2 235
Accessible range
Termination range
IEC: 200% In, cos phi 0.6
4–8 A: 150% In, cos phi 0.9
10–16 A: 150% In, cos phi 0.9
Endurance minimum
Endurance typical
Dielectric strength
Insulation resistance
Ambient temperature
DC 500 V
5–16 A
4A
Reset Type (manual)
Type of actuation
Type of tripping
Weight
Typical internal resistance
Rated current
4A
5A
6A
7A
8A
2
Internal resistance
(mΩ)
21.6
23.6
16.3
15.3
12.9
Rated current
10 A
12 A
14 A
15 A
16 A
Internal resistance
(mΩ)
7.3
7.0
4.8
4.3
3.9
circuit breakers
AC 240 V, 50/60 Hz
DC 48/32 V
4–16 A
2 kA
2 kA, C1
OL0 240 VAC
OL0 48 VDC and 32 VDC
IP 40
IP 00
min. 50 cycles
2500 cycles
6000 cycles
AC 1500 V
> 100 MΩ
-5 °C to 60 °C
-5 °C to 50 °C
R
Cycling trip-free
9g
T9
www.schurter.com/pg17_18_19
TRiPPing ChARACTeRiSTiCS
[min]
[sec]
10'000
T9
Type
Rated Current
5 A -16 A (TC-1)
4A
(TC-2)
60
30
20
effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C.
To determine the rated current for a lower or higher ambient
temperature, use a correction factor from the table below:
Reference Temperature + 23˚C
Ambient temperature (°C)
-5
+10
+23
+40
+60
1'000
10
5
3
Correction factor
0,85
0,95
1,00
1,08
1,21
100
1
example
Rated current at +23°C
Ambient temperature
Correction factor
Chosen rated current at +60°C
ambient temperature
10
10,0 A
+60°C
1,21
10,0 A x 1,21 = 12,1 A
1.35
1.45
0.1
1
1.05
Trip Time
1
2
3
4
5
6
7
8
10
[ x In ]
Multiple of Rated Current
APPRovAlS
UL
UL
VDE
CQC
UL 1077
CSA C22.2 235
IEC 60934
GB 17701
Rated currents
Rated voltage AC
Rated voltage DC
4–12 A
240 V
48 V
> 12–16 A
240 V
32 V
4–12 A
240 V
48 V
> 12–16 A
240 V
32 V
4–12 A
240 V
48 V
> 12–16 A
240 V
32 V
4–16 A
240 V
circuit breakers
3
circuit breakers
oRDeR CoDe
Basic type
T9
single pole, thermal overload switch, cycling trip-free
Mounting style
3
6
7
Threaded neck type (including one hexagonal nut)
Snap-in type from front side (0.8…2.0 mm)
Snap-in type from rear side (0.5…3.0 mm)
Actuation type
1
Reset Type (R-type)
Terminal type
1
6.3 x 0.8 mm quick connect terminals IEC 61210
Front printing
C
P
rated current not marked on front (T9-311 and T9-711)
rated current printed on front (T9-611 only)
Rated current
4A
10 A
5A
12 A
6A
14 A
7A
15 A
8A
16 A
T9 - 6
1
1
P
-
10A
Accessories
17
Protection cover TZZ31 for IP 65 for type T9-311:
13.6
SW 14
Hexagonal nut TZZ12:
3/8" -27UNS
Order number
4404.0039
4400.0420
4400.0559
4400.0425
4
2.5
Type description
TZZ31
TZZ11
TZZ11-414
TZZ12
Protection cover for IP 65
Knurled nut nickel-plated
Knurled nut black
Additional hexagonal nut nickel-plated
circuit breakers
T9
www.schurter.com/pg17_18_19
dimensions
36.1
10
19
8.6
8
5
6.3x0.8
3/8" -27UNS
max. torque 0.6 Nm
+0.10
0
8.90
9.6
9.6
19
10.4
SW14
ø 15.4 ±0.2
13.6 ±0.2
T9-311
Panel thickness S = 0.8–5.5 mm
T9-611
ø 15.4 ±0.2
34
10
19
19
13.6 ±0.2
3.4
8
5
+0.15
0
+0.15
0
Panel thickness S = 0.8–2.0 mm
Recommended panel thickness: 0.8/1.2/1.6/2.0 mm
T9-711
3.4
43.1
10
25
11
13.6 ±0.2
ø 15.4 ±0.2
8
5
ø 15.5
15
+0.15
0
16
+0.15
0
16
14
+0.15
0
16
6.3x0.8
6.3x0.8
0
0
15.9 -0.1
13.9 -0.1
Panel thickness S = 0.5–3.0 mm
circuit breakers
5