FC-73 www.firecontrolinstruments.com DESCRIPTION The FC-73 Series Fire Alarm Control panel is a proven, versatile conventional zoned unit which meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, Auxiliary, Remote and Proprietary Supervising Station Fire Alarm Systems. It is listed to UL Standard 864; inherently power limited, and has all necessary circuitry to meet the UL transient immunity requirements. The system is housed in a heavy-duty steel enclosure finished in red, with panels displaying the status of vital functions. The surface mounted enclosure, with its slim appearance (4-inch depth), is designed to blend with any environment. The cabinet can house up to 7AH batteries while the system’s power supply can maintain batteries of up to 33 AH batteries (enclosed in the separately available BC-1R, 11000654). The many features of the FC-73 provide a cost effective approach to system design, and allow a great degree of flexibility in one enclosure. The panel provides ten (10) Class "B" (Style B) or five (5) Class "A" (Style D) zones, expandable to twenty (20) Class "B" or ten (10) Class "A" zones with the addition of the ZDM-FC73 Module. The FC-73 also provides four (4) Class "B" (Style Y) or two (2) Class "A" (Style Z) notification appliance circuits. Standard on all FC-73 control panels are a City Master Box output, Polarity Reversal signaling connections, and Integrated DACT. The combination of a conventional fire alarm control panel with a microprocessor design allows for programming of many unique features such as time limit cutoff, programmed verification, pre-alarm delay, and cross-zoning. Individual zones can be assigned specific outputs and zone types such as alarm, supervisory or waterflow. In addition, up to eight (8) selectable/programmable notification appliance circuit output patterns are available for alternate styles of warnings. Programming is achieved through the LCD-FC73 annunciator module or through the Field Configuration Program (FCP-73). Supervision of vital components, modules, functional switches, and standby batteries is provided. CONVENTIONAL FIRE ALARM CONTROL PANEL The integral Digital Alarm Communicator Transmitter supports all standard reporting formats including: • 3/1, 1400 Hz • 3/1, 2300 Hz • SK 4/2, 1400 Hz • SIA 8 • SIA 20 • Contact ID Optional modules include an LCD remote annunciator, a zone expander module used to expand the system and a status display module which provides outputs and control functions for each zone as well as program access. FEATURES . •Individual Zone Disconnect Switches •Supports up to six (6) Remote LCD Displays • Supports up to six (6) Remote LED Annunciators • Integral Digital Communicator Transmitter • Expandable to Twenty (20) Class B or Ten (10) Class A Zones • Field Programmable Configuration • Eight (8) Selectable/Programmable Output Patterns Including Temporal Pattern Output per ANSI S3.41 •"Walk Test" Capability provided by the LCD-FC73 optional Remote Annunciator • Programmable Alarm Verification and Cross-Zoning • Four (4) Class B or Two (2) Class A Notification Appliance Circuits • Six (6) Amp power Supply • Three integral progammable relays • Provides Municipal Circuit or Reverse Polarity output • Reverse Polarity or Municipal Circuit output S1869 An ISO 9001 Company Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2001 All Rights Reserved 9020-0523 Rev. B Page 1 of 4 FC-73 www.firecontrolinstruments.com the BASIC FC-73 ASSEMBLY RING TIP 59 P1 58 RING TIP 57 T2 56 RING TIP 55 P2 54 TROUBLE SILENCED POWER ACK SILENCE RESET DRILL TEST 43 NC 6 7 B Z2 C 44 NO SUPERVISORY 1 ON 2 3 10 11 B Z3 C 38 39 40 + PR – MB + 4 9 A 41 NO 8 D 42 COM 5 A ALARM 45 COM 4 D 46 NC 47 NO 2 3 B Z1 C 48 COM 1 A 49 NC RING TIP 61 T1 60 ZONE EXPANDER (ZDM-FC73) The ZDM-FC73 Zone Expander provides the FC-73 with ten (10) additional Class "B" (Style B) or five (5) Class "A" (Style D) initiating circuits. Mounts in main cabinet or in FC-2190 Accessory Cabinet. 12 D 28 PWR 29 GND 20 D 30 31 + NAC4– 18 19 B Z5 C 32 33 + NAC3– 17 A + 24 GND 16 D 34 35 + NAC2– SBUS A 14 15 B Z4 C 36 37 + NAC1– B 13 A 2 Z1 3 B– C– 5 A+ 4 D+ 6 Z3 7 B– C– 8 D+ 9 A+ 10 Z3 11 B– C– 12 D+ 13 A+ 14 Z4 15 B– C– 16 D+ 17 A+ 18 Z5 19 B– C– 20 D+ 24 25 GND + 24DC 26 A 27 B 1 A+ 21 B ® 22 23 EARTH W FIRE CONTROL INSTRUMENTS STATUS DISPLAY MODULE (FC-5280) The FC-5280 Status Display Module provides outputs and control functions for remote annunciation of alarm, trouble, and supervisory indications for each zone. The system can supervise up to eight (8) modules. The FC-5280 has ten (10) outputs for alarm and ten (10) for trouble annunciation. These outputs are “active low” (become negative when activated). Each output can provide up to 0.100 amp current, with a total of 0.700 amp available. The module has four (4), Form "C" relays that can be wired to operate with any of the outputs. The FC-5280 can be used to interface with an LED annunciator. It can be programmed to indicate alarm and trouble status for Zones 1 - 10, 11 - 20, or system status outputs. The FC-5280 mounts inside the FC73 cabinet. FIRE ALARM CONTROL MODEL FC-73 OPTIONAL ACCESSORIES LCD-FC73 The LCD-FC73 supervised remote annunciator performs all system operations. It can be used for programming and provides access to the Walk Test feature and trouble and alarm information. The control panel can support up to six (6) annunciators. Total distance is up to 3000 feet away over two pair of two-conductor wire. FIRE ALARM ANNUNCIATOR ALARM NO NO TROUBLE 1C SUPERVISORY SILENCED 3C NC NC ON NO 1 2 3 NO 4 AC . MODEL LCD-FC73 RESET SILENCE 1 2 3 4 5 6 7 8 9 * 0 # 2C 4C NC NC – C1 C2 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 C3 C4 ACK ENTER . Specifications are provided for information only, and are not intened to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. + A SBUS B © 2001 All Rights Reserved FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com 9020-0523 Rev. B / Page 2 of 4 FC-73 www.firecontrolinstruments.com NAC DISCONNECT SWITCH (TYPICAL) ZONE DISCONNECT SWITCH (TYPICAL) Integral DACT Connections RING TIP 59 P1 58 RING TIP 57 T2 56 RING TIP 55 P2 54 SUPERVISORY TROUBLE SILENCED POWER ACK SILENCE RESET DRILL TEST 42 COM 41 NO 8 D ZONE 12 Reverse Polarity Output 14 15 B Z4 C 36 37 + NAC 1– 13 A 16 D ZONE 14 17 A 18 19 B Z5 C 32 33 + NAC3 – 34 35 + NAC2 – 12 D ZONE 3 NAC 2 ZONE 4 38 39 + PR - ZONE 2 NAC 1 Municipal Circuit Output ZONE 5 ZONE 16 ZONE 7 ZONE 17 29 GND ZONE 8 ZONE 18 ZONE 9 ZONE 19 ZONE 10 ZONE 20 28 PWR ZONE 6 27 B 20 D NAC 3 4 Style Y or 2 Style Z Notification Appliance Circuits Power-limited & Supervised with 3.9KW EOL resistor(Style Y only) 3.0 amps. max. out of any one circuit 30 31 + NAC4– 10 11 B Z3 C ZONE 11 40 + 9 A ZONE 1 MASTER BOX SBUS & Auxliary Power 1.0 amp. max. @ 24 VDC 24 25 GND + 2 4DC 26 A NAC 4 21 B ® FIRE CONTROL INSTRUMENTS 22 23 EARTH W Connection to 120 VAC 3 amps. @ 60 Hz 3 Programmable Form C Relay Outputs 2.5 amps. @ 24 VDC/ 24 VAC (inductive) 5 amps. @ 24 VDC (resistive) Non power-limited 43 NC 6 7 B Z2 C 44 NO 5 A 10 Style B or 5 Style D Initiating Device Circuits Max. Voltage- 25.5 VDC Max. Circuit Resistance- 50 Ohms Total Alarm Current for all Circuits- 1.0 amp. Supervisory Current per Zone- 0.003 amp. Alarm Current per Zone- 0.095 amp. Power-Limited & Supervised with 3.9KW EOL (not required for Style D circuits) ALARM 45 C OM 4 D 46 NC 47 NO 2 3 B Z1 C 48 COM 1 A 49 NC RING TIP 61 T1 60 1 ON NAC INDICATING LEDs GREEN= CIRCUITACTIVE YELLOW= CIRCUITTROUBLE TYPICAL FIRE ALARM CONTROL MODEL FC-73 2 ZONE INDICATING LEDs RED/YELLOW= ALARM/SUPERVISORY OFF-NORMAL YELLOW= ZONE TROUBLE (TYPICAL) 3 4 B SBUS A + 24 GND Mounting Location for ZDM-FC73 or FC-5280 (ZDM-FC73 can mount remotely in FC-2190 Accessory Cabinet) Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2001 All Rights Reserved FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com 9020-0523 Rev. B / Page 3 of 4 FC-73 www.firecontrolinstruments.com GENERAL SPECIFICATIONS Primary AC Voltage Total DC Voltage output Auxiliary Power output Smoke Detector output Battery Charging Voltage Battery Charging Current Minimum Telephone input sensitivity Minimum Telephone line voltage Low Battery Threshold Low AC Brown-out Threshold Dimensions 120 Vrms @ 60 Hz, 3A 6A 27.4 VDC @ 1A 27.4 VDC @ 1A 27.4 VDC 0.75A max. (33 A/H batteries max.) 35 dB 3V 20.4 VDC 98 VAC 16” W x 26.4” H x 4” D (40.64 x 67.06 x 10.16 cm) 28 lbs. Shipping Weight ENVIRONMENTAL SPECIFICATIONS Recommended Operating Temperature Range Recommended Operating Humidity Range 60° to 80° F (15° to 27° C), 32° to 120° F max. (0° to 49° C) not to exceed 85% @ 90°F (32° C), non-condensing INITIATING DEVICE CIRCUIT SPECIFICATIONS 10 Style B (Class B) or 5 Style D (Class A) IDCs expandable to 20 Style B, 10 Style D withh addition of ZDM25.6 VDC FC73 50 ohms Maximum Voltage 1.0 amp. Maximum Circuit Resistance 0.003 amp. Maximum Alarm Current for all Zones 0.095 amp. Supervisory Current (per Zone) Alarm Current (per Zone) Supervised & Power-Limited NOTIFICATION APPLIANCE CIRCUIT SPECIFICATIONS 4 Style Y (Class B) or 2 Style Z (Class A) NACs rated 3.0 amp. each (Note: total current draw from NACS, smoke detector power, auxiliary power and main Control Panel not to exceed 6.0 amp.) Supervised & Power-Limited APPROVALS U.L. (Std 864) C.S.F.M. S1869 Pending ORDERING INFORMATION Part No. 150-00013 150-00014 150-00015 150-00016 150-00018 150-00023 Model FC73-PCB FC-73 ZDM-FC73 LCD-FC73 FC-5280 FC-2190 Description FC-73 Main Board Fire Alarm Control Panel Zone Expander Module Remote Annunciator Status Display Module Accessory Cabinet Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2001 All Rights Reserved FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com 9020-0523 Rev. B / Page 4 of 4