GAMEWELL-FCI ZDM-FC73

FC-73
www.firecontrolinstruments.com
DESCRIPTION
The FC-73 Series Fire Alarm Control
panel is a proven, versatile conventional
zoned unit which meets the requirements
of NFPA Standard 72 for Central Station,
Protected Premises, Auxiliary, Remote
and Proprietary Supervising Station Fire
Alarm Systems. It is listed to UL Standard 864; inherently power limited, and has
all necessary circuitry to meet the UL transient immunity requirements.
The system is housed in a heavy-duty
steel enclosure finished in red, with panels displaying the status of vital functions.
The surface mounted enclosure, with its
slim appearance (4-inch depth), is designed
to blend with any environment. The cabinet can house up to 7AH batteries while
the system’s power supply can maintain
batteries of up to 33 AH batteries (enclosed
in the separately available BC-1R, 11000654).
The many features of the FC-73 provide a cost effective approach to system
design, and allow a great degree of flexibility in one enclosure. The panel provides
ten (10) Class "B" (Style B) or five (5) Class
"A" (Style D) zones, expandable to twenty
(20) Class "B" or ten (10) Class "A" zones
with the addition of the ZDM-FC73 Module. The FC-73 also provides four (4) Class
"B" (Style Y) or two (2) Class "A" (Style Z)
notification appliance circuits.
Standard on all FC-73 control panels are
a City Master Box output, Polarity Reversal signaling connections, and Integrated
DACT. The combination of a conventional
fire alarm control panel with a microprocessor design allows for programming of
many unique features such as time limit
cutoff, programmed verification, pre-alarm
delay, and cross-zoning. Individual zones
can be assigned specific outputs and zone
types such as alarm, supervisory or
waterflow. In addition, up to eight (8) selectable/programmable notification appliance circuit output patterns are available
for alternate styles of warnings. Programming is achieved through the LCD-FC73
annunciator module or through the Field
Configuration Program (FCP-73).
Supervision of vital components, modules,
functional switches, and standby batteries is provided.
CONVENTIONAL
FIRE ALARM
CONTROL PANEL
The integral Digital Alarm Communicator Transmitter supports all standard reporting formats including:
• 3/1, 1400 Hz
• 3/1, 2300 Hz
• SK 4/2, 1400 Hz
• SIA 8
• SIA 20
• Contact ID
Optional modules include an LCD remote
annunciator, a zone expander module used
to expand the system and a status display module which provides outputs and
control functions for each zone as well as
program access.
FEATURES
.
•Individual Zone Disconnect Switches
•Supports up to six (6) Remote LCD
Displays
• Supports up to six (6) Remote LED
Annunciators
• Integral Digital Communicator
Transmitter
• Expandable to Twenty (20) Class B or
Ten (10) Class A Zones
• Field Programmable Configuration
• Eight (8) Selectable/Programmable
Output Patterns Including Temporal
Pattern Output per ANSI S3.41
•"Walk Test" Capability provided by the
LCD-FC73 optional Remote
Annunciator
• Programmable Alarm Verification and
Cross-Zoning
• Four (4) Class B or Two (2) Class A
Notification Appliance Circuits
• Six (6) Amp power Supply
• Three integral progammable relays
• Provides Municipal Circuit or Reverse
Polarity output
• Reverse Polarity or Municipal Circuit
output
S1869
An ISO 9001 Company
Specifications are provided for information only, and
are not intended to be used for installation purposes
and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for
their use. Specifications subject to change without
notice.
© 2001 All Rights Reserved
9020-0523 Rev. B
Page 1 of 4
FC-73
www.firecontrolinstruments.com
the BASIC FC-73 ASSEMBLY
RING
TIP
59 P1 58
RING TIP
57 T2 56
RING
TIP
55 P2 54
TROUBLE
SILENCED
POWER
ACK
SILENCE
RESET
DRILL
TEST
43
NC
6
7
B Z2 C
44
NO
SUPERVISORY
1
ON
2
3
10 11
B Z3 C
38
39
40
+ PR – MB +
4
9
A
41
NO
8
D
42
COM
5
A
ALARM
45
COM
4
D
46
NC
47
NO
2
3
B Z1 C
48
COM
1
A
49
NC
RING
TIP
61 T1 60
ZONE EXPANDER (ZDM-FC73)
The ZDM-FC73 Zone Expander provides the FC-73
with ten (10) additional Class "B" (Style B) or five (5)
Class "A" (Style D) initiating circuits. Mounts in main
cabinet or in FC-2190 Accessory Cabinet.
12
D
28
PWR
29
GND
20
D
30
31
+ NAC4–
18 19
B Z5 C
32
33
+ NAC3–
17
A
+ 24 GND
16
D
34
35
+ NAC2–
SBUS
A
14 15
B Z4 C
36
37
+ NAC1–
B
13
A
2 Z1 3
B– C–
5
A+
4
D+
6 Z3 7
B– C–
8
D+
9
A+
10 Z3 11
B– C–
12
D+
13
A+
14 Z4 15
B– C–
16
D+
17
A+
18 Z5 19
B– C–
20
D+
24
25
GND + 24DC
26
A
27
B
1
A+
21
B
®
22
23
EARTH W
FIRE CONTROL
INSTRUMENTS
STATUS DISPLAY MODULE (FC-5280)
The FC-5280 Status Display Module provides outputs and control functions for remote annunciation of
alarm, trouble, and supervisory indications for each
zone. The system can supervise up to eight (8) modules. The FC-5280 has ten (10) outputs for alarm and
ten (10) for trouble annunciation. These outputs are
“active low” (become negative when activated). Each
output can provide up to 0.100 amp current, with a
total of 0.700 amp available. The module has four (4),
Form "C" relays that can be wired to operate with any
of the outputs. The FC-5280 can be used to interface
with an LED annunciator. It can be programmed to
indicate alarm and trouble status for Zones 1 - 10, 11
- 20, or system status outputs. The FC-5280 mounts
inside the FC73 cabinet.
FIRE ALARM CONTROL
MODEL FC-73
OPTIONAL ACCESSORIES
LCD-FC73
The LCD-FC73 supervised remote annunciator performs
all system operations. It can be used for programming and
provides access to the Walk Test feature and trouble and
alarm information. The control panel can support up to six
(6) annunciators. Total distance is up to 3000 feet away
over two pair of two-conductor wire.
FIRE ALARM ANNUNCIATOR
ALARM
NO
NO
TROUBLE
1C
SUPERVISORY
SILENCED
3C
NC
NC
ON
NO
1
2
3
NO
4
AC
.
MODEL LCD-FC73
RESET
SILENCE
1
2
3
4
5
6
7
8
9
*
0
#
2C
4C
NC
NC
–
C1 C2 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 C3 C4
ACK
ENTER
.
Specifications are provided for information only, and are not intened to be used for installation purposes, and are believed to be accurate.
However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
+
A
SBUS
B
© 2001 All Rights Reserved
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com
9020-0523 Rev. B / Page 2 of 4
FC-73
www.firecontrolinstruments.com
NAC
DISCONNECT
SWITCH
(TYPICAL)
ZONE
DISCONNECT
SWITCH
(TYPICAL)
Integral DACT Connections
RING
TIP
59 P1 58
RING
TIP
57 T2 56
RING
TIP
55 P2 54
SUPERVISORY
TROUBLE
SILENCED
POWER
ACK
SILENCE
RESET
DRILL
TEST
42
COM
41
NO
8
D
ZONE 12
Reverse Polarity Output
14 15
B Z4 C
36
37
+ NAC 1–
13
A
16
D
ZONE 14
17
A
18 19
B Z5 C
32
33
+ NAC3 –
34
35
+ NAC2 –
12
D
ZONE 3
NAC 2
ZONE 4
38
39
+ PR -
ZONE 2
NAC 1
Municipal Circuit Output
ZONE 5
ZONE 16
ZONE 7
ZONE 17
29
GND
ZONE 8
ZONE 18
ZONE 9
ZONE 19
ZONE 10
ZONE 20
28
PWR
ZONE 6
27
B
20
D
NAC 3
4 Style Y or 2 Style Z
Notification Appliance Circuits
Power-limited & Supervised
with 3.9KW EOL resistor(Style Y only)
3.0 amps. max. out of any one circuit
30
31
+ NAC4–
10 11
B Z3 C
ZONE 11
40
+
9
A
ZONE 1
MASTER
BOX
SBUS & Auxliary Power
1.0 amp. max. @ 24 VDC
24
25
GND + 2 4DC
26
A
NAC 4
21
B
®
FIRE CONTROL
INSTRUMENTS
22
23
EARTH W
Connection to 120 VAC
3 amps. @ 60 Hz
3 Programmable Form C Relay Outputs
2.5 amps. @ 24 VDC/ 24 VAC (inductive)
5 amps. @ 24 VDC (resistive)
Non power-limited
43
NC
6
7
B Z2 C
44
NO
5
A
10 Style B or 5 Style D
Initiating Device Circuits
Max. Voltage- 25.5 VDC
Max. Circuit Resistance- 50 Ohms
Total Alarm Current for all Circuits- 1.0 amp.
Supervisory Current per Zone- 0.003 amp.
Alarm Current per Zone- 0.095 amp.
Power-Limited & Supervised with 3.9KW EOL
(not required for Style D circuits)
ALARM
45
C OM
4
D
46
NC
47
NO
2
3
B Z1 C
48
COM
1
A
49
NC
RING
TIP
61 T1 60
1
ON
NAC INDICATING LEDs
GREEN= CIRCUITACTIVE
YELLOW= CIRCUITTROUBLE
TYPICAL
FIRE ALARM CONTROL
MODEL FC-73
2
ZONE INDICATING LEDs
RED/YELLOW= ALARM/SUPERVISORY OFF-NORMAL
YELLOW= ZONE TROUBLE
(TYPICAL)
3
4
B
SBUS
A
+ 24 GND
Mounting Location for ZDM-FC73 or FC-5280
(ZDM-FC73 can mount remotely in FC-2190 Accessory Cabinet)
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 2001 All Rights Reserved
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com
9020-0523 Rev. B / Page 3 of 4
FC-73
www.firecontrolinstruments.com
GENERAL SPECIFICATIONS
Primary AC Voltage
Total DC Voltage output
Auxiliary Power output
Smoke Detector output
Battery Charging Voltage
Battery Charging Current
Minimum Telephone input sensitivity
Minimum Telephone line voltage
Low Battery Threshold
Low AC Brown-out Threshold
Dimensions
120 Vrms @ 60 Hz, 3A
6A
27.4 VDC @ 1A
27.4 VDC @ 1A
27.4 VDC
0.75A max. (33 A/H batteries max.)
35 dB
3V
20.4 VDC
98 VAC
16” W x 26.4” H x 4” D
(40.64 x 67.06 x 10.16 cm)
28 lbs.
Shipping Weight
ENVIRONMENTAL SPECIFICATIONS
Recommended Operating Temperature Range
Recommended Operating Humidity Range
60° to 80° F (15° to 27° C), 32° to 120° F max. (0° to 49° C)
not to exceed 85% @ 90°F (32° C), non-condensing
INITIATING DEVICE CIRCUIT SPECIFICATIONS
10 Style B (Class B) or 5 Style D (Class A) IDCs expandable to 20 Style B, 10 Style D withh addition of ZDM25.6 VDC
FC73
50 ohms
Maximum Voltage
1.0 amp.
Maximum Circuit Resistance
0.003 amp.
Maximum Alarm Current for all Zones
0.095 amp.
Supervisory Current (per Zone)
Alarm Current (per Zone)
Supervised & Power-Limited
NOTIFICATION APPLIANCE CIRCUIT SPECIFICATIONS
4 Style Y (Class B) or 2 Style Z (Class A) NACs rated 3.0 amp. each
(Note: total current draw from NACS, smoke detector power, auxiliary power and main Control Panel not to
exceed 6.0 amp.)
Supervised & Power-Limited
APPROVALS
U.L. (Std 864)
C.S.F.M.
S1869
Pending
ORDERING INFORMATION
Part No.
150-00013
150-00014
150-00015
150-00016
150-00018
150-00023
Model
FC73-PCB
FC-73
ZDM-FC73
LCD-FC73
FC-5280
FC-2190
Description
FC-73 Main Board
Fire Alarm Control Panel
Zone Expander Module
Remote Annunciator
Status Display Module
Accessory Cabinet
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 2001 All Rights Reserved
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com
9020-0523 Rev. B / Page 4 of 4