GAMEWELL-FCI FLD-1

FLD-1
www.gamewell-fci.com
FIBER OPTIC LINE
DRIVER MODULE
DESCRIPTION
Point-to-Point Mode
When configured in the Point-to-Point
Mode, a single 7100 or 7200 Series control
panel may use its RS-232 port to connect
to a single printer, video terminal or personal computer (PC) via a fiber optic link.
Each location requires an FLD-1.
The Fiber Optic Line Driver module
(FLD-1) provides fiber optic cable communications between system modules that will be
free of ground faults, transients, or noise interference. This affords greater reliability and
is a more robust application for those installations requiring communications running
outdoors between structures. It connects to
the RS-232 and RS-485 ports of the FCI 7100
and 7200 Series fire alarm control panels.
The FLD-1 converts either RS-232 or RS485 signals to a powerful optical signal that
can tolerate a signal loss of up to 10 dB. It
uses half duplex data flow, an asynchronous
protocol, and runs at speeds of up to 19.2
KBps for RS-232 and 128 KBps for RS-485
communications.
The FLD-1 is equipped with ST connectors that will support standard fiber optic
cable up to 200 microns (multimode). Optimal results can be achieved with 62.5/125
micron cable.
The FLD-1 provides two modes of operation, the Network Mode or the Point-to-Point
Mode, selectable through DIP Switch settings
on board the FLD-1.
INSTALLATION
The FLD-1 module mounts inside its own
steel cabinet, which can be located up to
15 feet (4.6 meters) away, using rigid conduit. The dimensions of the cabinet are 10
1
/4” W x 10” H x 3” D (26.04 x 25.40 x 7.62
cm).
Operating power for the FLD-1 is obtained
from the 7200 or 7100 panel, and is connected to the FLD-1 via terminal block. RS485 connections are also made via terminal block, and RS-232 connections are
made using a standard RJ-11 cable.
FEA
TURES
FEATURES
• Can be used to transmit the FCINET ®
RS-485 data between a 7200 fire alarm
control panel, and up to fifteen (15)
Distributed Intelligent Units (DIU) via
Fiber Optic Cable
• Provides a Fiber Optic connection
between the 7100 and 7200 Series fire
alarm control panel and multiple
annunciators
• Allows a Fiber Optic cable link between
a Personal Computer, Printer or Video
Terminal to 7100 and 7200 Series Fire
Alarm Control Systems over long distances
• Tolerates up to 10 dB signal loss between
each FLD-1 module
• Fiber Optic Cable offers High Immunity
from Interference, Transients and Voltage Spikes
• Automatically adjusts to different
RS-232 Baud rates
• Uses Industry Standard ST Connectors
Network Mode
Using this mode the following configurations are possible:
•The FCI 7200 RS-485 FCINET® can
be exported via Panel Bus Adapter
(PBA) or local Keyboard Display Unit
(KDU\L) from the main panel containing the System Control Unit (SCU)
to up to fifteen remotely located KDUs,
Remote Annunciator Units (RAUs), and
sub-panels containing the Distributed
Intelligent Unit (DIU). Each location requires one FLD-1.
• The RS-485 communication output
of the FCI 7100 can be converted to
an optical link and brought to as many
as five remotely located LCD-7100
alphanumeric displays or LDM-7100
remote annunciator drivers. Each
location requires an FLD-1.
.
An ISO 9001 Company
Specifications are provided for information only, and
are not intended to be used for installation purposes
and are believed to be accurate. However, no responsibility is assumed by Gamewell-FCI for their
use.
Specifications subject to change without notice.
© 2006
All Rights Reserved
9020-0517 Rev. D
Page 1 of 4
A Honeywell Company
FLD-1
www.gamewell-fci.com
FIRE CONTROL INSTRUMENTS
FLD-1 PCB
ASSEMBLY
1700-0202
1120-0820
MADE IN USA
LED3 LED4 LED2 LED1
RS232
RS485
NET- PNT
WORK MODE
SW1
1 2 3 4
ON
RS-485
TERM
W1
LED6
LED8
LED5
LED7
RXA
RXB
TXA
TXB
1 2 3 4
1 2 3 4
TB1
TB2
COM COM
A
B
J2
TXA
J3
RXA
J1
J5
RXB
J4
TXB
+24V GND
To 7100 TB5-1 or
7200 PBA TB1-3,
KDU TB1-2 or
DIU TB1-3
EGND
To 7100 TB4-3 or
7200 SPSU-V TB1-3 or 4
To 7100 TB5-2 or
7200 PBA TB1-4,
KDU TB1-1 or
DIU TB1-4
To 7100 TB4-2 or
7200 SPSU-V TB1-1 or 2
To J3connector (RXA) of previous FLD-1
From J4 connector (TXB) of next FLD-1
To J2 connector (TXA) of previous FLD-1
From J5 connector (RXB) of next FLD-1
To RS-232 RJ-11 jack of 7200 SCU (connector J1)
or 7100 BSM (connector J3)
Module layout showing connection points
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice.
© 2006 All Rights Reserved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0517 Rev. C / Page 2 of 4
FLD-1
www.gamewell-fci.com
FCINET RS-485 from KDU/L or PBA (45 ’ max. in rigid conduit)
RS-232 from SCU J1 connector (45’ max. in rigid conduit)
FLD-1
Up to
10 dB
Loss
between
each
FLD-1
FLD-1s set to Point-to-Point Mode
FLD-1
FLD-1
7200 Series Control Panel w/SCU
(Main Control Panel)
Printer
FCINET RS-485 into DIU (45’ max. in rigid conduit)
FCINET RS-485 into DIU (45’ max. in rigid conduit)
FLD-1
FLD-1
7200 Series Distributed System w/DIU
(Sub-system)
7200 Series Distributed System w/DIU
(Sub-system)
FCINET RS-485 into DIU (45’ max. in rigid conduit)
Up to
10 dB
Loss
Typical 7200
Distributed System
using FLD-1 modules
FLD-1
Up to
10 dB
Loss
FLD-1
7200 Series Distributed System w/DIU
(Sub-system)
Keyboard Display Unit
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice.
© 2006 All Rights Reserved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0517 Rev. D / Page 3 of 4
FLD-1
www.gamewell-fci.com
TxA RxA
TxB RxB
TxA RxA
TxB RxB
TxA RxA
TxB RxB
TxA RxA
TxB RxB
Network Mode
TxA
RxB
RxA
TxB
Point-to-Point Mode
SPECIFICA
TIONS
SPECIFICATIONS
DESCRIPTION
Operating voltage
Operating temperature
Relative humidity
Protocol
Speed
ST connectors
Dimensions
OPERATING VOLTAGE
24 VDC (nominal) @ 0.045 amp (all modes)
32° to 120° F (0° to 49° C)
0 to 85% (non-condensing)
Asynchronous with half-duplex data flow
RS-232 up to 64 KBps
RS-485 up to 128 KBps
Up to 200 microns (multimode), optimized for 62.5/125 microns
10 1/4” W x 10” H x 3” D (26.04 x 25.40 x 7.62 cm)
APPROVALS
U.L. 864 File S1949
FM Approved
CSFM 07300-0694:251
FCC Part 15
ORDERING INFORMA
TION
INFORMATION
PART NUMBER
1100-0429
MODEL
FLD-1
DESCRIPTION
Fiber Optic Line Driver Module with Back Box
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice.
© 2006 All Rights Reserved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-00517 Rev. D / Page 4 of 4