FLD-1 www.gamewell-fci.com FIBER OPTIC LINE DRIVER MODULE DESCRIPTION Point-to-Point Mode When configured in the Point-to-Point Mode, a single 7100 or 7200 Series control panel may use its RS-232 port to connect to a single printer, video terminal or personal computer (PC) via a fiber optic link. Each location requires an FLD-1. The Fiber Optic Line Driver module (FLD-1) provides fiber optic cable communications between system modules that will be free of ground faults, transients, or noise interference. This affords greater reliability and is a more robust application for those installations requiring communications running outdoors between structures. It connects to the RS-232 and RS-485 ports of the FCI 7100 and 7200 Series fire alarm control panels. The FLD-1 converts either RS-232 or RS485 signals to a powerful optical signal that can tolerate a signal loss of up to 10 dB. It uses half duplex data flow, an asynchronous protocol, and runs at speeds of up to 19.2 KBps for RS-232 and 128 KBps for RS-485 communications. The FLD-1 is equipped with ST connectors that will support standard fiber optic cable up to 200 microns (multimode). Optimal results can be achieved with 62.5/125 micron cable. The FLD-1 provides two modes of operation, the Network Mode or the Point-to-Point Mode, selectable through DIP Switch settings on board the FLD-1. INSTALLATION The FLD-1 module mounts inside its own steel cabinet, which can be located up to 15 feet (4.6 meters) away, using rigid conduit. The dimensions of the cabinet are 10 1 /4” W x 10” H x 3” D (26.04 x 25.40 x 7.62 cm). Operating power for the FLD-1 is obtained from the 7200 or 7100 panel, and is connected to the FLD-1 via terminal block. RS485 connections are also made via terminal block, and RS-232 connections are made using a standard RJ-11 cable. FEA TURES FEATURES • Can be used to transmit the FCINET ® RS-485 data between a 7200 fire alarm control panel, and up to fifteen (15) Distributed Intelligent Units (DIU) via Fiber Optic Cable • Provides a Fiber Optic connection between the 7100 and 7200 Series fire alarm control panel and multiple annunciators • Allows a Fiber Optic cable link between a Personal Computer, Printer or Video Terminal to 7100 and 7200 Series Fire Alarm Control Systems over long distances • Tolerates up to 10 dB signal loss between each FLD-1 module • Fiber Optic Cable offers High Immunity from Interference, Transients and Voltage Spikes • Automatically adjusts to different RS-232 Baud rates • Uses Industry Standard ST Connectors Network Mode Using this mode the following configurations are possible: •The FCI 7200 RS-485 FCINET® can be exported via Panel Bus Adapter (PBA) or local Keyboard Display Unit (KDU\L) from the main panel containing the System Control Unit (SCU) to up to fifteen remotely located KDUs, Remote Annunciator Units (RAUs), and sub-panels containing the Distributed Intelligent Unit (DIU). Each location requires one FLD-1. • The RS-485 communication output of the FCI 7100 can be converted to an optical link and brought to as many as five remotely located LCD-7100 alphanumeric displays or LDM-7100 remote annunciator drivers. Each location requires an FLD-1. . An ISO 9001 Company Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice. © 2006 All Rights Reserved 9020-0517 Rev. D Page 1 of 4 A Honeywell Company FLD-1 www.gamewell-fci.com FIRE CONTROL INSTRUMENTS FLD-1 PCB ASSEMBLY 1700-0202 1120-0820 MADE IN USA LED3 LED4 LED2 LED1 RS232 RS485 NET- PNT WORK MODE SW1 1 2 3 4 ON RS-485 TERM W1 LED6 LED8 LED5 LED7 RXA RXB TXA TXB 1 2 3 4 1 2 3 4 TB1 TB2 COM COM A B J2 TXA J3 RXA J1 J5 RXB J4 TXB +24V GND To 7100 TB5-1 or 7200 PBA TB1-3, KDU TB1-2 or DIU TB1-3 EGND To 7100 TB4-3 or 7200 SPSU-V TB1-3 or 4 To 7100 TB5-2 or 7200 PBA TB1-4, KDU TB1-1 or DIU TB1-4 To 7100 TB4-2 or 7200 SPSU-V TB1-1 or 2 To J3connector (RXA) of previous FLD-1 From J4 connector (TXB) of next FLD-1 To J2 connector (TXA) of previous FLD-1 From J5 connector (RXB) of next FLD-1 To RS-232 RJ-11 jack of 7200 SCU (connector J1) or 7100 BSM (connector J3) Module layout showing connection points Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice. © 2006 All Rights Reserved GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118 www.gamewell-fci.com 9020-0517 Rev. C / Page 2 of 4 FLD-1 www.gamewell-fci.com FCINET RS-485 from KDU/L or PBA (45 ’ max. in rigid conduit) RS-232 from SCU J1 connector (45’ max. in rigid conduit) FLD-1 Up to 10 dB Loss between each FLD-1 FLD-1s set to Point-to-Point Mode FLD-1 FLD-1 7200 Series Control Panel w/SCU (Main Control Panel) Printer FCINET RS-485 into DIU (45’ max. in rigid conduit) FCINET RS-485 into DIU (45’ max. in rigid conduit) FLD-1 FLD-1 7200 Series Distributed System w/DIU (Sub-system) 7200 Series Distributed System w/DIU (Sub-system) FCINET RS-485 into DIU (45’ max. in rigid conduit) Up to 10 dB Loss Typical 7200 Distributed System using FLD-1 modules FLD-1 Up to 10 dB Loss FLD-1 7200 Series Distributed System w/DIU (Sub-system) Keyboard Display Unit Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice. © 2006 All Rights Reserved GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118 www.gamewell-fci.com 9020-0517 Rev. D / Page 3 of 4 FLD-1 www.gamewell-fci.com TxA RxA TxB RxB TxA RxA TxB RxB TxA RxA TxB RxB TxA RxA TxB RxB Network Mode TxA RxB RxA TxB Point-to-Point Mode SPECIFICA TIONS SPECIFICATIONS DESCRIPTION Operating voltage Operating temperature Relative humidity Protocol Speed ST connectors Dimensions OPERATING VOLTAGE 24 VDC (nominal) @ 0.045 amp (all modes) 32° to 120° F (0° to 49° C) 0 to 85% (non-condensing) Asynchronous with half-duplex data flow RS-232 up to 64 KBps RS-485 up to 128 KBps Up to 200 microns (multimode), optimized for 62.5/125 microns 10 1/4” W x 10” H x 3” D (26.04 x 25.40 x 7.62 cm) APPROVALS U.L. 864 File S1949 FM Approved CSFM 07300-0694:251 FCC Part 15 ORDERING INFORMA TION INFORMATION PART NUMBER 1100-0429 MODEL FLD-1 DESCRIPTION Fiber Optic Line Driver Module with Back Box Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Gamewell-FCI for their use. Specifications subject to change without notice. © 2006 All Rights Reserved GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118 www.gamewell-fci.com 9020-00517 Rev. D / Page 4 of 4