GRAYHILL 70G

Manual Override Output Modules
FEATURES
• Integral Three Position Manual
On/Manual Off and Automatic
Control Toggle Switch
• Transient Protection: Meets the
requirements of IEEE 472, “Surge
Withstanding Capability Test”
• UL, CSA Certified
• Optical Isolation
• G5 Modules Provide Replaceable
5x20 mm Glass Fuse
• Built-in Status LED
CIRCUITRY
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 100°C. Information
is based on steady state heat transfer in a two
cubic foot sealed enclosure.
AC Outputs
+
LOAD
LOAD CURRENT (AMPS)
LOAD
1
1
VAC
SNUBBER
LOAD
4
DC Outputs
2
VOLTAGE
SPIKE
PROTECTION
VDC
–
LOAD
2
G5 PACKAGE
TRIGGER
CIRCUIT
3
DRIVER
CIRCUIT
2
Rx
+
3
–
+
OFF
DC CONTROL
1
4
Rx
3
DC CONTROL
–
AUTO
ON
OFF
4
5
AUTO
ON
5
-40˚
-20˚
0
20˚
40˚
60˚
AMBIENT TEMPERATURE (˚C)
80˚
100˚
Figure 1
PEAK SURGE CURRENT (AMPERES)
I/O Modules
Maximum Peak Surge Current
Versus Surge Duration (AC Outputs)
Information is based on a supply frequency of
60 Hz sinusoidal and a resistive or inductive
load. Application of maximum surge current
may not be repeated until the module
temperature has returned to its steady state
value.
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent.
300
200
100
80
60
40
30
20
STA
NDA
RD,
MINI,
G5
OPE
10
NLI
NE
6
4
3
1
1
1
1000
2 3 4 6 10 20 40 60 100
NUMBER OF FULL CYCLES AT 60 HERTZ
Figure 2
I/O
12
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Manual Override Output Modules
SPECIFICATIONS: All Modules*
Output Specifications
Load Current Range (rms): 0.03 to 3.5
Amps, Maximum current is derated as shown
in Figure 1.
Maximum Surge Current (peak): 80 Amps
at 60 Hz, 1 cycle as qualified by Figure 2 for
AC outputs. 5 Amp maximum for 1 second for
DC outputs.
Turn-on Time (60 Hz): 8.3 mSec maximum
for AC outputs. 20 µSec maximum for DC
outputs.
Turn-off Time (60 Hz): 8.3 mSec maximum
for AC outputs. 50 µSec maximum for DC
outputs.
ON State Voltage Drop (peak): 1.5 volts
max.
Power Dissipation: 1.0 Watt/Amp typical
General Characteristics
Mechanical Shock: 1500 G's 0.5 mS halfsine per MIL–STD–202, Method 213,
Condition F
Storage Temperature Range:
-40°C to +125°C
Operating Temperature Range:
-40°C to +100°C
Isolation Voltage Field to Logic: 4000 Vac
(rms) minimum
Vibration: 20 G's peak or .06” double amplitude
10–2000 Hz per MIL–STD–202, Method 204,
Condition D
*Specifications apply over operating temperature range unless noted otherwise.
SPECIFICATIONS: By Part Number
AC Outputs
Type/Function
Grayhill Part Number
G5, Zero Voltage Turn On, Manual Override
Specifications
70G-OAC5MA
70G-OAC5AMA
70G-OAC24MA
70G-OAC24AMA
Units
Nominal Line Voltage
Vac
Load Voltage Range
Vac
Minimum Peak Blocking Voltage
Volts
Maximum Off-state Leakage @ 60Hz
mA, rms
Nominal Logic Voltage (Vcc)
Vdc
Logic Voltage Range
Vdc
Max. Logic Supply Current @ Nominal Vcc
mA
Nominal Input Resistance (Rx)
Ω
Minimum Drop-Out Voltage
Vdc
Maximum Reverse Logic Voltage
Vdc
Maximum Zero Voltage Offset
(Vpeak)
Frequency Range
(Hz)
120
24-140
400
2
5
4-6
20
100
1
-5
8
25-70
240
24-280
600
4
5
4-6
20
100
1
-5
8
25-70
120
24-140
400
2
24
18-32
8
2700
1
-5
8
25-70
240
24-280
600
4
24
18-32
8
2700
1
-5
8
25-70
DC Outputs
Grayhill Part Number
Type/Function
G5 Manual Override
70G-ODC5MA
70G-ODC24MA
Units
Maximum Line Voltage
Load Voltage Range
Maximum Off-state Leakage @ 60 Vdc
Maximum Turn-on Time
Maximum Turn-off Time
Nominal Logic Voltage (Vcc)
Logic Voltage Range
Max. Logic Supply Current
@ Nominal Vcc
Nominal Input Resistance (Rx)
Minimum Drop-Out Voltage
Maximum Reverse Logic Voltage
Maximum Clamping Voltage
Vdc
Vdc
mA
µSec
µSec
Vdc
Vdc
60
3-60
1.5
20
50
5
4-6
60
3-60
1.5
20
50
24
18-32
mA
Ω
Vdc
Vdc
Vdc
13
150
1
-5
80
9
2700
1
-5
80
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
I/O Modules
Specifications
Available from your local Grayhill Distributor.
For prices and discounts, contact a local Sales
Office, an authorized local Distributor or Grayhill.
I/O
13