Manual Override Output Modules FEATURES • Integral Three Position Manual On/Manual Off and Automatic Control Toggle Switch • Transient Protection: Meets the requirements of IEEE 472, “Surge Withstanding Capability Test” • UL, CSA Certified • Optical Isolation • G5 Modules Provide Replaceable 5x20 mm Glass Fuse • Built-in Status LED CIRCUITRY Maximum Current Versus Ambient Temperature The chart indicates continuous current to limit the junction temperatures to 100°C. Information is based on steady state heat transfer in a two cubic foot sealed enclosure. AC Outputs + LOAD LOAD CURRENT (AMPS) LOAD 1 1 VAC SNUBBER LOAD 4 DC Outputs 2 VOLTAGE SPIKE PROTECTION VDC – LOAD 2 G5 PACKAGE TRIGGER CIRCUIT 3 DRIVER CIRCUIT 2 Rx + 3 – + OFF DC CONTROL 1 4 Rx 3 DC CONTROL – AUTO ON OFF 4 5 AUTO ON 5 -40˚ -20˚ 0 20˚ 40˚ 60˚ AMBIENT TEMPERATURE (˚C) 80˚ 100˚ Figure 1 PEAK SURGE CURRENT (AMPERES) I/O Modules Maximum Peak Surge Current Versus Surge Duration (AC Outputs) Information is based on a supply frequency of 60 Hz sinusoidal and a resistive or inductive load. Application of maximum surge current may not be repeated until the module temperature has returned to its steady state value. FUSES G5 Fuses are 5 Amp Littelfuse part number 217005 or equivalent. 300 200 100 80 60 40 30 20 STA NDA RD, MINI, G5 OPE 10 NLI NE 6 4 3 1 1 1 1000 2 3 4 6 10 20 40 60 100 NUMBER OF FULL CYCLES AT 60 HERTZ Figure 2 I/O 12 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com Manual Override Output Modules SPECIFICATIONS: All Modules* Output Specifications Load Current Range (rms): 0.03 to 3.5 Amps, Maximum current is derated as shown in Figure 1. Maximum Surge Current (peak): 80 Amps at 60 Hz, 1 cycle as qualified by Figure 2 for AC outputs. 5 Amp maximum for 1 second for DC outputs. Turn-on Time (60 Hz): 8.3 mSec maximum for AC outputs. 20 µSec maximum for DC outputs. Turn-off Time (60 Hz): 8.3 mSec maximum for AC outputs. 50 µSec maximum for DC outputs. ON State Voltage Drop (peak): 1.5 volts max. Power Dissipation: 1.0 Watt/Amp typical General Characteristics Mechanical Shock: 1500 G's 0.5 mS halfsine per MIL–STD–202, Method 213, Condition F Storage Temperature Range: -40°C to +125°C Operating Temperature Range: -40°C to +100°C Isolation Voltage Field to Logic: 4000 Vac (rms) minimum Vibration: 20 G's peak or .06” double amplitude 10–2000 Hz per MIL–STD–202, Method 204, Condition D *Specifications apply over operating temperature range unless noted otherwise. SPECIFICATIONS: By Part Number AC Outputs Type/Function Grayhill Part Number G5, Zero Voltage Turn On, Manual Override Specifications 70G-OAC5MA 70G-OAC5AMA 70G-OAC24MA 70G-OAC24AMA Units Nominal Line Voltage Vac Load Voltage Range Vac Minimum Peak Blocking Voltage Volts Maximum Off-state Leakage @ 60Hz mA, rms Nominal Logic Voltage (Vcc) Vdc Logic Voltage Range Vdc Max. Logic Supply Current @ Nominal Vcc mA Nominal Input Resistance (Rx) Ω Minimum Drop-Out Voltage Vdc Maximum Reverse Logic Voltage Vdc Maximum Zero Voltage Offset (Vpeak) Frequency Range (Hz) 120 24-140 400 2 5 4-6 20 100 1 -5 8 25-70 240 24-280 600 4 5 4-6 20 100 1 -5 8 25-70 120 24-140 400 2 24 18-32 8 2700 1 -5 8 25-70 240 24-280 600 4 24 18-32 8 2700 1 -5 8 25-70 DC Outputs Grayhill Part Number Type/Function G5 Manual Override 70G-ODC5MA 70G-ODC24MA Units Maximum Line Voltage Load Voltage Range Maximum Off-state Leakage @ 60 Vdc Maximum Turn-on Time Maximum Turn-off Time Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop-Out Voltage Maximum Reverse Logic Voltage Maximum Clamping Voltage Vdc Vdc mA µSec µSec Vdc Vdc 60 3-60 1.5 20 50 5 4-6 60 3-60 1.5 20 50 24 18-32 mA Ω Vdc Vdc Vdc 13 150 1 -5 80 9 2700 1 -5 80 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com I/O Modules Specifications Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized local Distributor or Grayhill. I/O 13