GRAYHILL 70-OAC24A-11

AC Output Modules
FEATURES
• Transient Protection: Meets the
requirements of IEEE 472, “Surge
Withstanding Capability Test”
• SPST, Normally Open
• Zero Crossing Turn-On
• UL, CSA, CE, TÜV Certified
• Optical Isolation
• OpenLine® and G5 Modules
Provide Replaceable 5x20 mm
Glass Fuses
• Built-in Status LED
• Lifetime Warranty
70L-OAC
4
LOAD CURRENT (AMPS)
DIMENSIONS
For complete dimensional drawings, see pages
L-4 or L-5.
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent. OpenLine® fuses are
3.15 Amp Littelfuse part number 2173.15.
3
2
70G-OAC
70-OAC
70M-OAC
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 100°C. Information
is based on steady state heat transfer in a 2
cubic foot sealed enclosure.
STANDARD, G5 PACKAGES
MINIATURE PACKAGE
OPENLINE PACKAGE/CH
1
-40˚
-20˚
0
20˚
40˚
60˚
80˚
AMBIENT TEMPERATURE (˚C)
100˚
Figure 1
CIRCUITRY
OpenLine®
Standard, Mini, G5
LOAD
TYPICAL WIRING FOR MODULE 0
VAC
SNUBBER
LOAD
2
GND
5
Vcc
6
CHANNEL A
A
TRIGGER
CIRCUIT
CH. A CONTROL
Rx
OPTICAL
ISOLATION
CH. B CONTROL
3
1
1
2
2
3
3
4
4
LOAD
SNUBBER
SNUBBER
LOAD
CHANNEL B
DC CONTROL
–
OPTICAL
ISOLATION
7
B
+
I/O MODULE
PIN #
1
2.15K
4
MODULE ID
RACK
OR
BASE
MODULE
Fuse and status LED in G5 and OpenLine modules only.
TERMINAL
BLOCK #
I/O Modules
SPECIFICATIONS: By Package Style
Package Style
Specifications
Load Current Range
Maximum 1 Cycle Surge 2
Maximum Turn-On-Time (60 Hz)3
Maximum Turn-Off Time (60 Hz)
Static dv/dt7
Typ. Power Dissipation
Isolation Voltage 4
Vibration5
Mechanical Shock6
Storage Temp. Range
Operating Temp. Range
Warranty
2
3
4
5
6
7
Mini (70M-)
G5 (70G-)
OL (70L-)
0.03 to 3.5
80
8.33
8.33
3000
1.0
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
0.03 to 3.0
80
8.33
8.33
3000
1.0
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
0.03 to 3.5
80
8.33
8.33
3000
1.0
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
0.03 to 2.0/CH
30
8.33
8.33
3000
1.0
2500
IEC68-2-6
IEC68-2-27
-40 to 100
-40 to 85
Lifetime
Units
1
1
Std (70-)
A rms
A rms
mSec
mSec
V/µsec
W/A
V rms
°C
°C
See Figure 1 for derating.
Maximum 10 cycle surge is 50% of 1 cycle surge. Application of maximum surge may not be repeated until module temperature has returned
to its steady state value.
Except 70-OAC5A5 which is 200 µSec and 70-OAC5A-11, 70M-OAC5A-11, and 70G-OAC5A-11 which are 100 µSec.
Field to logic and channel-to-channel if Grayhill racks are used.
MIL-STD-202, Method 204, 20 , 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz.
MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g.
Except part numbers with -L suffix which have a dv/dt rating of 200 V/µSec.
I/O
6
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
AC Output Modules
SPECIFICATIONS: By Part Number
Standard and Miniature Modules
Type/Function
Grayhill Part Number
Miniature, Normally Open, Random Turn-on
70M-OAC5A-11
Miniature, Normally Open, Zero Voltage Turn-on (ZVT)
70M-OAC5
70M-OAC5A
Miniature, Normally Open, ZVT, Inductive Load
70M-OAC5-L
70M-OAC5A-L
Standard, Normally Closed, Random Turn-on
70M-OAC15A
70M-OAC24
70M-OAC24A
70-OAC15
70-OAC15A
70-OAC24
70-OAC24A
120
24-140
400
2
24
15-30
9
2700
1
-5
240
24-280
600
4
24
15-30
9
2700
1
-5
70-OAC5A5
Standard, Normally Open, Random Turn-on
70-OAC5A-11
Standard, Normally Open, ZVT
Standard, Normally Open, ZVT, Inductive Load
Specifications
Nominal Line Voltage
Load Voltage Range
Minimum Peak Blocking Voltage
Maximum Off-state Leakage @ 60Hz
Nominal Logic Voltage (Vcc)
Logic Voltage Range
Max. Logic Supply Current @ Nominal Vcc
Nominal Input Resistance (Rx)
Minimum Drop Out Voltage
Maximum Reverse Logic Voltage
70M-OAC15
Units
Vac
Vac
Volts
mA, rms
Vdc
Vdc
mA
Ω
Vdc
Vdc
70-OAC5
70-OAC5A
70-OAC5-L
70-OAC5A-L
120
24-140
400
2
5
2.5-10
16
240
1
-5
70-OAC24A-11
240
24-280
600
4
5
2.5-10
16
240
1
-5
120
24-140
400
2
15
10-18
9
1800
1
-5
240
24-280
600
4
15
10-18
9
1800
1
-5
G5 Modules
Grayhill Part Number
Type/Function
G5 Fusible, Normally Open, ZVT
70G-OAC5
G5 Fusible, Normally Open, ZVT, Inductive Load
70G-OAC5-L 70G-OAC5A-L
G5 Fusible, Normally Open, Random Turn-on
Specifications
70G-OAC5A
70G-OAC15
70G-OAC15A
70G-OAC24
70G-OAC15-L 70G-OAC15A-L 70G-OAC24-L
70G-OAC24A
70G-OAC24A-L
70G-OAC5A-11
Units
Nominal Line Voltage
Load Voltage Range
Minimum Peak Blocking Voltage
Maximum Off-state Leakage @ 60Hz
Nominal Logic Voltage (Vcc)
Logic Voltage Range
Max. Logic Supply Current @ Nominal Vcc
Nominal Input Resistance (Rx)
Minimum Drop Out Voltage
Maximum Reverse Logic Voltage
Vac
Vac
Volts
mA, rms
Vdc
Vdc
mA
W
Vdc
Vdc
120
24-140
400
2
5
4-6
20
100
1
-5
240
24-280
600
4
5
4-6
20
100
1
-5
120
24-140
400
2
15
8-20
12
1000
1
-5
240
24-280
600
4
15
8-20
12
1000
1
-5
120
24-140
400
2
24
18-32
8
2700
1
-5
240
24-280
600
4
24
18-32
8
2700
1
-5
Type/Function
Grayhill Part Number
Dual, Fusible, Normally Open, ZVT
Dual, Fusible, Normally Open, ZVT, Inductive Load
Specifications
Units
Nominal Line Voltage
Load Voltage Range
Minimum Peak Blocking Voltage
Maximum Off-State Leakage @ 60 Hz
Nominal Logic Voltage
Logic Voltage Range
Max. Logic Supply Current @ Nominal Vcc
Module ID Resistance to Logic Ground
Minimum Drop Out Voltage
Vac
Vac
Volts
mA, rms
Vdc
Vdc
mA
Ω
Vdc
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
70L-OAC
70L-OACA
70L-OAC-L
70L-OACA-L
120
24-140
600
2
5
4.5-28
7/CH
2.15K
1
240
24-280
600
4
5
4.5-28
7/CH
2.15K
1
Available from your local Grayhill Distributor.
For prices and discounts, contact a local Sales
Office, an authorized local Distributor or Grayhill.
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
I/O