Isolated Voltage or Current Input 7B40 FEATURES FUNCTIONAL BLOCK DIAGRAM Interfaces, amplifies and filters unipolar and bipolar millivolt and voltage inputs. Module provides a precision output of either +1 V to +5 V or 0 V to +10 V. All 7B40 series modules are mix-and-match and Hot Swappable. APPLICATIONS Industrial signal conditioning Industrial signal isolation Industrial signal filtering PRODUCT OVERVIEW The 7B Series of signal conditioners feature small size, low cost and a wide output voltage range for a variety of applications including process control and factory-floor environments. The single-channel 7B modules accept inputs from a range of transducers and are fully rated over the extended -40oC to +85oC industrial temperature range. All 7B Series modules are rated for a nominal power supply input of +24 VDC; and, for maximum flexibility, they will accept supply voltages in the +14 VDC to +35 VDC range. The input modules, with the exception of the 7B21, provide a high-level output voltage that is factory configured for either the +1 V to +5 V or 0 V to +10 V range. The 7B21 is a unity gain, isolated input module with an input/output range of +10V. Output modules are available that provide either isolated process current or isolated bipolar voltage output. Model 7B39 converts either a +1 V to +5 V input to a 4 to 20 mA output or a 0 V to +10 V input to a 0-20 mA output. The input/output ranges of the 7B39 are factory configured. The 7B22 is a unity gain module that provides an isolated +10V output signal. All modules have a universal pinout and may be readily hot-swapped under full power without disrupting field wiring. Each module accepts analog transducer signals and transfers them to a process control or factory data collection system without the inherent noise, non-linearity, drift and extraneous voltages which frequently accompany the signals. Figure 1. 7B40 Functional Block Diagram The modules feature a maximum nonlinearity of +0.02% and are factory calibrated to guarantee a maximum accuracy specification of +0.1%. The 7B Series offers up to 1500 V rms continuous common mode voltage isolation and 120 V rms of field wiring input protection. The power supplies necessary to drive each of the individual module’s input circuitry are internally isolated, enabling the 7B Series modules to offer true channel-to-channel isolation of the input signals. The modules directly accept analog signals from thermocouples, RTDs, current loop powered transmitters, and other process control signals. The 7B Series modules amplify, linearize, isolate, protect and convert the transducer output signals to standardized analog inputs for high-level analog I/O subsystems. The 7B Series Subsystem consists of 19-inch rackcompatible hardware (model AC 1363), with universal mounting backplane and a family of plug-in (up to 16 per backplane) input and output signal conditioning modules. Four, eight-, and sixteen-channel backplanes are available. Each backplane incorporates screw terminals for easy power connections and field wiring, and includes a 25-pin D-type connector for interfacing the high-level single-ended voltage outputs to the user’s equipment. Gold-plated sockets are provided on each channel of the backplane to ensure the reliability of each module’s electrical connection. Rev. 0 Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective companies. One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. www.analog.com Tel: 781.329.4700 Fax: 781.326.8703 © 2004 Analog Devices, Inc. All rights reserved. 7B40 GENERAL DESCRIPTION implement transformer isolation (1500 V rms input-to-output and power). Isolated front-end circuitry power is supplied by a DC/DC converter. The output section contains a four-pole low pass filter (-3 dB @ 10KHz), a buffer amplifier and a power oscillator. The four-pole output filter and subsequent buffer ensures that a low noise, low impedance (<1Ω) signal is available at the output to drive loads of 2 kΩ minimum. The 7B40 is a single-channel signal conditioning module that interfaces, amplifies and filters unipolar and bipolar millivolt and voltage inputs and provides a protected precision output of either +1 V to +5 V or 0 V to +10 V. Model 7B40 features a nonlinearity of +0.02% maximum and an accuracy of +0.1% maximum (+0.01% typical). To accurately measure low level signals in electrically noisy environments, 1500 V rms of galvanic transformer-based isolation with a common mode rejection (CMR) of 110 dB @50/60 Hz and a normal mode rejection (NMR) of 100 dB @50/60 Hz are provided. Rated to operate with a nominal +24 VDC supply, Model 7B40 is mixand-match and hot-swappable with other 7B Series input modules, so it can be inserted or removed from any socket in the same backplane without disturbing system power. The floating differential input of Model 7B40 is fully protected up to 240 V rms line voltage. A one-pole 10 KHz filter preconditions the input signal prior to amplification by a low drift input amplifier. Amplitude modulation is used to Figure 2 Rev. 0 | Page 2 of 8 7B40 7B40 Models Available Model Input Range Output Range 7B40-01-1 0-10mV 1-5V 7B40-01-2 0-10mV 0-10V 7B40-02-1 0-100mV 1-5V 7B40-02-2 0-100mV 0-10V 7B40-03-1 0-1V 1-5V 7B40-03-2 0-1V 0-10V 7B40-06-1 +/-10mV 1-5V 7B40-06-2 +/-10mV 0-10V 7B40-07-1 +/-100mV 1-5V 7B40-07-2 +/-100mV 0-10V 7B40-08-1 +/-1V 1-5V 7B40-08-2 +/-1V 0-10V 7B40 Specifications Wideband mV/V Isolated Input module (typical @ +25C and +24 Vdc) Description Model 7B40 Range 1 Standard Range +/- 5mV to +/- 1V Custom Ranges YES Output Range Options (RL > 2 k Ω) 1-5V or 0-10V (1) Accuracy2 Initial @25C 0.01% span (0.1% max) Nonlinearity (BSL) +/-0.02% max Input Ofs vs. Temp 0.5uV/C Zero Suppression vs. Temp 0.002%Vz/C Span vs. Temp +/-35ppm/C Output Ofs vs. Temp +/-0.001% span Input Bias Current +/- 100 pA Input Resistance Power On >1G Ohm Power Off >1G Ohm Overload 200K Ohm Output Noise 5MHz Bandwidth 2mV peak 10Hz-100KHz Bandwidth 1mV rms Rev. 0 | Page 3 of 8 7B40 0.1Hz-10Hz Bandwidth 0.5uV peak Bandwidth, -3dB (7-pole Butterworth Filter) 10 KHz (2) Output Rise Time, 10-90% span 40 us (2) Common-Mode Voltage (CMV) Input-to-Output and Power Continues 1500 Vrms min Common Mode Rej. (CMR) 110 dB Normal Mode Rej. (NMR) 50/60 Hz 100 dB/dec >10 Khz (2) Input Protection 240 Vrms, +/-35Vdc continuous Input Transient Protection ANSI/IEEE C37.90.1-1989 Output Resistance <1 Ohm Output Voltage/ Current Limit +/-12V, +/-14mA Power Supply Voltage, Rated Performance 14-35Vdc Current 20mA max Sensitivity +/-0.0001%/%Vs Mechanical Dimensions 1.663"x2.11"x0.563" (42.24mm x 53.6mm x 14.3mm) Weight 60 gms Environmental Temperature Range, Operating -40°C to +85°C Temperature Range, Storage -40°C to +85°C Relative Humidity 0 to 90% @ +60°C non-condensing ESD Sensitivity IEC 801-2, Level 2 RFI Susceptibility 0.1% span max @ 158,440 MHz, 5W, 3 ft. Warm-up time required to meet specifications is approximately 10 minutes. (1) +/- 5V and +/- 10V output ranges are available as custom configurations. (2) Custom Bandwidths available, Rise and Fall times, NMR frequency will vary accordingly Specifications subject to change without notice. Rev. 0 | Page 4 of 8 7B40 PIN CONFIGURATIONS AND FUNCTIONAL DESCRIPTIONS Figure 3 7B40 Input Field Connections Table 1. Pin Function Descriptions— Pin No. 0 1 2 3 4 5 Input Module Function Output Module Function SENSOR INPUT INPUT HIGH INPUT LOW POWER SUPPLY (DC) OUTPUT VOLTAGE OUTPUT & POWER COMMON NOT USED OUTPUT HIGH OUTPUT LOW POWER SUPPLY (DC) INPUT VOLTAGE INPUT AND POWER COMMON Figure 4 . Model 7B Series Module, with pin-out assignments. ESD CAUTION ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on the human body and test equipment and can discharge without detection. Although this product features proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance degradation or loss of functionality. Rev. 0 | Page 5 of 8 7B40 OUTLINE DIMENSIONS Figure 5. Outline Dimensions Rev. 0 | Page 6 of 8 7B40 NOTES Rev. 0 | Page 7 of 8 7B40 NOTES © 2004 Analog Devices, Inc. All rights reserved. Trademarks and registered trademarks are the property of their respective companies. D05180-0-10/04(0) Rev. 0 | Page 8 of 8