MURATA-PS ACA5-20RM

ACA5-20RM Series
True-rms-AC Ammeters with 5A CT Inputs
FEATURES
N
Scales and displays the true-rms output of 5A current
transformers
N
Accurately measure complex ac current waveforms
N
Perfect for measuring current in IT applications
N
Available in three input ranges: 0-100A, 0 to 200A,
or 0 to 500A
N
Functionally complete:
On-board, low-burden toroid sensor
Scaling/interface circuitry
Precision A/D converter
N
Reliable single-board construction
N
Easy-to-read, red LED display with 0.37"/9.4mm digits
N
Two AC power options: 85-140Vac & 170-264Vac
(50/60Hz)
N
2000V isolation between ac supply and external CT
N
Digital replacement for analog meters
Murata Power Solutions’ ACA5-20RM Series accept the output of external 5A current
transformers (CTs) and accurately display the true-rms value of complex, non-sinusoidal ac
currents up to 500A. Operation and setup is straightforward: simply pass the external 5A
CT’s secondary 0-5A output leads through the ACA5-20RM’s on-board toroid sensor, apply
ac power, and the ammeter is fully operational. All models are totally self-contained—other
than the external 5A CT, no other user-supplied components are required.
Three input ranges measure 0-100.0 amps (with 0.1A resolution), 0-200 amps (0.1A
resolution), and 0-500 amps (1A resolution). Two power supply options are available:
85-140V (47-63Hz), and 170-264V (47-63Hz). Power consumption from a nominal 120V
or 220V ac supply is less than 50mA. And, precision auto-zeroing circuitry, super-stable
components, and an rms-to-dc converter circuit combine to achieve excellent performance
when measuring the complex, non-sinusoidal, ac currents found in today’s computer/telecom
equipment.
ACA5-20RM Series rms ammeters feature full-size, 0.37" (9.4mm) high, 3½ digit,
bright red LED-displays and a built-in bezel/filter assembly that features metal fasteners.
They are also panel-cutout compatible with Murata Power Solutions’ DMS-20RM Series
of rms-reading ac voltage monitors, making ACA5-20RM ammeters perfect replacements for older, less reliable, analog voltmeters and ammeters in today’s sophisticated
instrumentation.
PRECISION
rms-to-DC
CONVERTER
BUILT-IN
TOROID
SENSOR
L1
A
B
TB1
For full details go to
www.murata-ps.com/rohs
Figure 1. ACA5-20RM Series simplified schematic
www.murata-ps.com
Technical enquiries email: [email protected], tel: +1 508 339 3000
MPM_ACA5-20RM.A01 Page 1 of 5
ACA5-20RM Series
True-rms-AC Ammeters with 5A CT Inputs
Performance/Functional Specifications
~The specified full-scale current is the ac current circulating through the meter’s
built-in 5A current transformer’s primary circuit L1 (i.e., the external current
transformer’s 0-5A output current).
Typical at TA = +25°C, unless otherwise noted.
Full-Scale Primary Current ~
All Models
Min.
Typ.
Max.
Units
–
–
5.0
rms Amps
1.5 x Rated full-scale rms current
Overcurrent Rating 
Display Readings with 5A Flowing through the Ammeter’s Current Transformer
Model Number
Display Reading
ACA5-20RM-3-ACX-RL
100.0
ACA5-20RM-5-ACX-RL
199.9
ACA5-20RM-9-ACX-RL
500
 The overcurrent rating of 1.5 times the rated full-scale current is a continuous
rms rating and applies to the current passing through the built in current transformer (CT). Accuracy is only guaranteed up to the rated full-scale CT current of
5Arms.
€ Specified accuracy applies to inputs with crest factors (CF) up to 2.0, where CF
= Vpeak/Vrms. Crest factors of 2 to 5 introduce an additional error of ±3% of full
scale. Ammeters are calibrated with a 5.00Arms/60Hz current flowing through
the ammeter’s built-in 5A CT.
 All specified maximum power supply currents are steady state; larger surge
currents can occur at initial turn-on.
Performance
Sampling Rate
2.5 Samples per second
±0.4%FS ±3 Counts with 60Hz
Sine-Wave Input
Accuracy €
Input Frequency Range
47–63
Ordering Information
ACA5-20RM-3-AC3-RL-C
ACA5-20RM-3-AC4-RL-C
100.0A Range, 85-140Vac power
100.0A Range, 170-264Vac power
ACA5-20RM-5-AC3-RL-C
ACA5-20RM-5-AC4-RL-C
199.9A Range, 85-140Vac power
199.9A Range170-264Vac power
ACA5-20RM-9-AC3-RL-C
ACA5-20RM-9-AC4-RL-C
500A Range, 85-140Vac power
500A Range, 170-264Vac power
Hz
Measurement Type
rms Responding, Crest Factors of 1-5
Temperature Drift (0 to 60 °C)
–
±0.2
±0.4
Cnts/°C
Zero-Current Reading (within 30 sec.)
–001
000
001
Cnts
Breakdown Voltage
2000
–
–
Vdc
ACA5-20RM-X-AC3-RL
85
120
140
Vac/47-63Hz
ACA5-20RM-X-AC4-RL
170
220
264
Vac/47-63Hz
ACA5-20RM-X-AC3-RL
—
30
50
mA/47-63Hz
ACA5-20RM-X-AC4-RL
—
30
50
mA/47-63Hz
Power Supply Voltage
Accessory Current Transformers for above*:
Power Supply Current 
7020-01038-0
7020-01040-0
39-3681409
100A Current Transformer, RoHS compliant
200A Current Transformer, RoHS compliant
500A Current Transformer, not RoHS compliant
* See data sheet titled “Current Transformers” at www.murata-ps.com for more
information
Power Supply Terminal Block (all models)
Wire Size
16-22AWG, Solid or stranded
Insulation Strip Length
0.250 inches
Screw Tightening Torque
3.6 pounds-inches (0.4Nm)
Rated Voltage
310Vac
Display
Display Type and Size
3½ Digit Red LED, 0.37”/9.4mm High
Overrange Indication
“1___”
Model dependent; see
“Display Readings” above
Display Reading/Decimal Point
Physical/Environmental
Operating Temperature
Storage Temperature
Humidity (non-condensing)
Dimensions
0
–
+60
°C
–40
–
+75
°C
–
–
85
%
Model dependent, see page 4 & 5
Weight
All models
1.1 Ounces (31 grams) nominal
www.murata-ps.com
TECHNICAL NOTES
IMPORTANT! To ensure safe and reliable operation, ACA5-20RM
ammeters must be installed and serviced by qualified technical
personnel. Contact Murata Power Solutions if there is any doubt
regarding ammeter installation and/or operation.
1. Measurement Type: ACA5-20RM ac ammeters employ a true rms
input circuit to measure the output of external 5A current transformers. Stated accuracy specifications are measured using a sine-wave
current at, or close to, the full-scale input range, at nominal line
frequency of 60Hz.
2. Calibration: Periodic recalibration of ACA5-20RM ammeters is
not required under normal, indoor operating environments. If user
calibration is necessary, it should be performed by qualified technical
personnel. Calibration is performed with potentially lethal voltages
applied to the ACA5-20RM and its associated wiring, with 5.0 amps
flowing through the ammeter’s built-in toroid sensor. A plastic,
fully-insulated adjusting tool must be used to access the calibration
potentiometer located on the back of the meter (see Mechanical
Specifications). Contact MPS if additional information is required
regarding calibration, setup, or any other technical issue pertaining to
ACA5-20RM ammeters.
Technical enquiries email: [email protected], tel: +1 508 339 3000
MPM_ACA5-20RM.A01 Page 2 of 5
ACA5-20RM Series
True-rms-AC Ammeters with 5A CT Inputs
3. Wire Gauges and Fusing: Wires specified in the Functional Specifications section must be used for making connections to ACA5-20RM
Series ammeters. All power-supply and load wiring must be rated for
the supply voltages and currents they will conduct and must comply
with any code or application-mandated requirements pertaining to the
user’s specific installation.
6. Isolation: The built-in toroid sensor (L1) provides a minimum of
2000Vdc isolation between the external CT’s 5A secondary conductors and the ammeter supply voltage connected to TB1.
7. CT Precautions: In normal operation, a 5A CT’s secondary circuit
operates at a very low voltage due to its closed-loop operation and
low burden resistance. However, a CT can still generate potentially
lethal voltages if its output current is suddenly interrupted. For
example, loose 5A CT secondary connections can cause a condition
referred to as “inductive kick”. Inductive kick can generate extremely
high voltages across a CT’s intermittent secondary connections.
The supply wires connected to both the ammeter and the load must
be fused according to the current rating of the wire gauge being used,
in accordance with applicable regulatory codes. Also, wire insulation should be stripped to within +/–10% of the stated dimensions,
and wires should be inserted into TB1 such that their insulation is not
pinched by the screw terminal. TB1 is to be used only for powering the
meter’s internal circuitry; It must not be used to supply current to any
external loads.
Therefore, implementing connections to any 5A current transformer’s
output leads must only be performed with zero load-current flowing
the CT’s primary load-circuit.
8. CT Connections and Grounding: Some applications require connecting one of the external 5A CT’s output leads to earth/chassis ground.
In the USA, consult the latest revision of the National Electrical Code
(NEC) for more information regarding CT grounding.
All models draw minimal steady-state supply currents (50mA max.),
and in most applications they can be fused according to the supply
wire’s maximum amperage rating. However, these models can draw
significantly higher surge currents for brief periods when the ac line
voltage is initially applied.
After all mechanical assembly is completed, connect the two output
leads of the external 5A CT to each other after they are run through
L1’s center hole. Pressure-style connectors (commonly referred to as
“wire nuts”) are acceptable as long as they are rated for the number
of conductors and voltage involved.
4. AC Supply Polarity and Grounding: The two supply inputs, TB1-A and
TB1-B, on ACA5-20RM ammeters are not in themselves polarity sensitive, that is, they have no internal “AC LO” or “AC HI” designations.
ACA5-20RM ammeters do not include or require a connection to earth/
chassis ground.
9. Replacing Analog Panel Meters: ACA5-20RM ammeters can be
used as direct replacements for most analog panel meters driven by
external 5A CT’s. All wiring operations must be performed with both
the load and the supply power sources completely de-energized.
5. Connector Torque Ratings: It is important to tighten TB1’s, screw-terminals to their rated torque specification of 3.6 pound-inches (0.4Nm).
Proper tightening will minimize connector losses and ensure safe,
reliable operation.
BACK VIEW
A
FUSED AC POWER
TB1
B
L1
Figure 2. Typical wiring diagram
www.murata-ps.com
Technical enquiries email: [email protected], tel: +1 508 339 3000
MPM_ACA5-20RM.A01 Page 3 of 5
ACA5-20RM Series
True-rms-AC Ammeters with 5A CT Inputs
PANEL INSTALLATION
All connections to ACA-20RM Series ammeters must be made after
the ammeter is securely attached to the panel and with all associated
load and supply voltages de-energized (off), using extreme caution and
observing all safety measures applicable to the user’s installation.
plastic standoffs over the bezel’s threaded studs. Install the ACA5-20RM
pc-board assembly as shown and then attach and securely tighten all
four hex nuts. Use only the factory-supplied hardware as the use of substitute hardware could result in an unsafe installation and/or adversely
affect the reliability of the ammeter.
Care should be exercised when passing conductors through the ammeter’s built-in toroid sensor L1. The installed wire-positions should be such
that minimal mechanical forces are applied to L1, TB1, or to the ammeter
itself. In high-vibration environments, it is strongly recommended that
adequate strain reliefs be used for all wiring.
The recommended range of panel thickness that can be used with the
supplied hardware is 0.040 inches (1.0mm) to 0.125 inches (3.2mm).
Panel thickness outside of this range will require additional user-supplied
hardware or modifications.
Using Figure 3 as a guide, carefully insert the bezel/color filter assembly
into the panel opening. From the rear of the panel, install the four round
PANEL
0.032 (0.8) Thick
Gasket
Standoff
Gasket
Nut
Standoff
0.190 (4.83)
Board-Cutout
Bezel
ACA5-20RM
AC Ammeter
SIDE VIEW
Figure 3. Panel Installation
BEZEL AND PANEL CUTOUT
RECOMMENDED DRILL AND
PANEL CUTOUT DIMENSIONS
0.187
(4.75)
0.55
(13.97)
FRONT VIEW
1.280
(32.51)
INTERNAL CORNER RADII:
0.032 (0.81) MAX.
1.07
(27.18)
0.116 (2.95)
0.838
(21.29)
1.336 (33.93)
0.145 (3.68)
1.826 (46.38)
1.626 (41.30)
0.093 (2.362) DIAMETER (4 REQUIRED)
www.murata-ps.com
Technical enquiries email: [email protected], tel: +1 508 339 3000
MPM_ACA5-20RM.A01 Page 4 of 5
ACA5-20RM Series
True-rms-AC Ammeters with 5A CT Inputs
MECHANICAL SPECIFICATIONS
FRONT VIEW
2.100
(53.34)
100-10
M9
100-10
M9
1.400
(35.56)
BACK VIEW
A
CAL
B
TB1
Lead Length
2.0 (50.5) min.
0.35
(8.9)
Diameter
SIDE VIEW
0.250
(6.35)
0.480
(12.19)
MECHANICAL DIMENSIONS: Inches (mm)
TOLERANCES:
2 PL DEC ±0.02 (±0.51)
3 PL DEC ±0.010 (±0.254)
USA:
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
Tel: (508) 339-3000 (800) 233-2765 Fax: (508) 339-6356
www.murata-ps.com email: [email protected] ISO 9001 and 14001 REGISTERED
01/27/09
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
notice.
© 2008 Murata Power Solutions, Inc.
www.murata-ps.com
Mansfield (MA), Tel: (508) 339-3000, email: [email protected]
Canada:
Toronto, Tel: (866) 740-1232, email: [email protected]
UK:
Milton Keynes, Tel: +44 (0)1908 615232, email: [email protected]
France:
Montigny Le Bretonneux, Tel: +33 (0)1 34 60 01 01, email: [email protected]
Germany:
München, Tel: +49 (0)89-544334-0, email: [email protected]
Japan:
Tokyo, Tel: 3-3779-1031, email: [email protected]
Osaka, Tel: 6-6354-2025, email: [email protected]
China:
Shanghai, Tel: +86 215 027 3678, email: [email protected]
Guangzhou, Tel: +86 208 221 8066, email: [email protected]
Singapore:
Parkway Centre, Tel: +65 6348 9096, email: [email protected]
Technical enquiries email: [email protected], tel: +1 508 339 3000
MPM_ACA5-20RM.A01 Page 5 of 5