EPCOS B84143-B36-R

3-Line Filters
B84143-B*-R
for Converters and Power Electronics
Power line filters for three-phase systems
Rated voltage 440/250 V~, 50/60 Hz
Rated current 8 A to 80 A
Construction
■ Three-line filter
■ Metal case
Features
■ Very high insertion loss
due to two-stage construction
Low leakage current
Easy to install
Degree of protection: IP 201)
Design complies with
EN 133200, UL 1283, CSA 22.2 No.8 1986
■ Optimized for long motor cables and
operation under full load
■
■
■
■
Applications
■ Frequency converters for motor drives, e.g.
– elevators
– pumps
– traction systems
– conveyor systems
– HVAC systems (heating, ventilation and air conditioning)
■ Wind farms
■ Power supplies
Terminals
■ Safe-to-touch terminal blocks
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated current, rated voltage,
rated temperature, climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
233 03/01
3-Line Filters
B84143-B*-R
for Converters and Power Electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB0805-1
Technical data
Rated voltage VR
440/250 V~, 50/60 Hz
Rated current I R
Referred to 40 °C ambient temperature
Test voltage V P
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
Leakage current I leak
at 230 V~, 50 Hz
Climatic category
25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
IR
Terminal
cross section
mm2
I leak
Rtyp
Approx.
weight
kg
Ordering code
mA
mΩ
8
4
< 3,5
80
3,8
B84143-B8-R
12
4
< 3,5
40
3,8
B84143-B12-R
16
4
< 3,5
25
3,8
B84143-B16-R
25
10
< 3,5
10
5,7
B84143-B25-R
36
10
< 3,5
5,0
5,7
B84143-B36-R
50
10
<6
3,5
80
25
<6
2,0
A
5,7
16
For higher currents refer to B84143-B**-R110, page 246.
234 03/01
B84143-B50-R
B84143-B80-R
3-Line Filters
B84143-B*-R
for Converters and Power Electronics
Dimensional drawings
1±0,1
30±1
81 max.
36±1
20,5±0,5
B84143-B8-R … B84143-B16-R
PE M6 x 25
22,5±1
126 max.
193 max.
LOAD
140±0,3
LINE
156 max.
L2 L1
Marking
L3
L3
L2 L1
115±0,2
6,6±0,2
Anschlussklemmen
Terminal blocks
2
44 mm
mm2
171 max.
SSB1006-Z
30±1
1±0,1
91 max.
46±1
31±0,5
B84143-B25-R … B84143-B50-R
PE M6 x 25
22,5±1
126 max.
281 max.
LINE
LOAD
6,6±0,2
231 max.
156 max.
Marking
PE L3 L2 L1
140±0,3
PE L3
L2 L1
115±0,2
Anschlussklemmen
Terminal blocks
2
10
10mm
mm2
235 03/01
SSB1007-8
3-Line Filters
B84143-B*-R
for Converters and Power Electronics
45±0,5
1,0±0,1
141 max.
73±1
48,5±0,5
B84143-B80-R
PE M10 x 35
23±0,5
409 max.
141 max.
Marking
LINE
LOAD
6,6±0,2
82,5±0,2 82,5±0,2
L1
L2
L3
PE
171 max.
L1
L2
L3
PE
155±0,3
331 max.
Anschlussklemmen
Terminal
blocks
2
25
25 mm
mm2
236 03/01
SSB0993-K
3-Line Filters
B84143-B*-R
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143-B8-R
B84143-B12-R
SSB0806-9
100
αe
dB
αe
80
60
60
40
40
20
20
10 4
10 5
10 6
10 7
0
Hz 10 8
f
B84143-B16-R
dB
αe
10 6
10 7
Hz 10 8
f
60
60
40
40
20
20
10 5
10 6
10 7
Hz 10 8
f
SSB0809-Y
dB
80
10 4
10 5
100
80
0
10 4
B84143-B25-R
SSB0808-Q
100
αe
dB
80
0
SSB0807-H
100
0
10 4
237 03/01
10 5
10 6
10 7
Hz 10 8
f
3-Line Filters
B84143-B*-R
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143-B36-R
B84143-B50-R
B84143-B80-R
SSB0810-2
100
αe
dB
αe
dB
80
80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
Hz 10 8
f
SSB0994-T
100
0
10 4
238 03/01
10 5
10 6
10 7
Hz 10 8
f
Herausgegeben von EPCOS AG
Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
 EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und
Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG
nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften
zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen
für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland.
Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte
darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG
Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
 EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for
the Supply of Products and Services of the Electrical and Electronics Industry recommended by the
ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or
the international Representatives.
Due to technical requirements components may contain dangerous substances. For information on
the type in question please also contact one of our Sales Offices.
1