EPCOS B84143-G36-R11

3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
Power line filters for three-phase systems
Rated voltage 480/275 and 520/300 V~, 50/60 Hz
Rated current 8 to 220 A
Construction
■ Three-line filter
■ Metal case
■ Book size
Features
■
■
■
■
■
■
■
High insertion loss
Low leakage current
Optimized footprint saves space
Litz wires on the load side reduce mounting time
Low weight
Degree of protection: IP 20 1)
Design based on
EN 133 200, CSA 22.2 No.8 1986
■ Optimized for long motor cables and operation under full load
■ UL 1283 approval for type -R110
,
for -R112 UL and CSA approval pending
Applications
■ Frequency converters for motor drives, e.g.
– elevators
– pumps
– traction systems
– conveyor systems
– HVAC systems (heating, ventilation and air conditioning)
■ Wind farms
■ Power supplies
Terminals
■ Line: Safe-to-touch terminal blocks
■ Load: Litz wires
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current,
rated temperature, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
239 03/01
3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
Typical circuit diagrams
B84143-G8 … G20-R110/-R112
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB1286-Z
B84143-G36 … G220-R110/-R112
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB1287-8
240 03/01
3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
Technical data
Rated voltage V R
480/275 V~, 50/60 Hz (type -R110)
520/300 V~, 50/60 Hz (type -R112)
Rated current I R
Referred to 40 °C ambient temperature
Test voltage V P
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
Leakage current I leak
at 480 V~, 50 Hz
Climatic category
25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
Terminal cross section
load side:
line side:
litz wires
terminal
blocks
mm2
mm2
IR
Ileak
typ. 1)
Rtyp
Approx.
weight
kg
Ordering code
mA
mΩ
8
4
1,5
< 6
40
1,3
B84143-G8-R11*
20
4
2,5
< 6
10
1,3
B84143-G20-R11*
6,0
A
36
6
< 16
5,2
2,8
B84143-G36-R11*
50
16
10
< 16
2,4
3,3
B84143-G50-R11*
66
25
16
< 16
1,8
4,4
B84143-G66-R11*
90
25
25
< 16
1,2
4,9
B84143-G90-R11*
120
50
35
< 16
1,0
7,5
B84143-G120-R11*
150
50
35
< 16
0,7
8,0
B84143-G150-R11*
220
95
70
< 16
0,4
11,5
B84143-G220-R11*
Compilation of ordering code
Replace the asterisk * by the code number for the required version:
0 = 480 / 275 V
2 = 520 / 300 V
1) At rated operation
241 03/01
3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
Dimensional drawings
B84143-G8-R11*, B84143-G20-R11*
50
300±10
200
Litz
wire
Litze
PE
M6 x 25
1
0,5
31
15
40
80
Terminal
Anschlussblocks 44 mm
klemmen
mm 22
L3’
L2’
L1’
PE
Wire end ferrule
Aderendhülse
Litz wire markings
Litzenbezeichnung
L1
L2
L3
25±0,3
46
6,5
230
215±0,5
Marking
LINE LOAD
SSB1291-1
B84143-G36-R11*
60
250
400±10
Terminal
Anschlussblocks 66mm
klemmen
mm22
Litz
wire
Litze
L3’
150
L2’
Wire end ferrule
Aderendhülse
Litz wire markings
Litzenbezeichnung
280
265±0,5
Marking
LINE LOAD
56
L1
L2
L3
35±0,3
6,5
PE
M6 x 25
PE
1
0,5
60
30
75
L1’
SSB1292-9
242 03/01
3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
B84143-G50-R11*
60
300
500±10
Litz
wire
Litze
Terminal
Anschlussblocks 16
klemmen
16 mm
mm 22
150
L3’
1
0,5
52
L1’
30
75
L2’
PE
PE
M6 x 25
Wire end ferrule
Aderendhülse
Litz wire markings
Litzenbezeichnung
6,5
Marking
LINE
LOAD
56
L1
L2
L3
35±0,3
330
315±0,5
SSB1293-H
B84143-G66-R11*, B84143-G90-R11*
80
300
500±10
Litz
wire
Litze
Terminal
Anschlussblocks 25
klemmen
25 mm
mm 22
150
L3’
L1’
L2
Marking
LINE LOAD
L3
1
76
L1
Wire end ferrule
Aderendhülse
Litz wire markings
Litzenbezeichnung
55±0,3
330
315±0,5
PE
6,5
PE
M10 x 35
0,5
52
30
75
L2’
SSB1294-Q
243 03/01
3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
B84143-G120-R11*, B84143-G150-R11*
90
350
500±10
Terminal
Anschlussblocks
klemmen
50
mm2 2
50 mm
Litz
wire
Litze
200
L3’
PE
M10 x 35
1
0,5
40
78
100
L2’
L1’
PE
Wire end ferrule
Aderendhülse
Litzenbezeichnung
Litz wire markings
65±0,3
L1
Marking
LINE LOAD
L2
L3
86
6,5
380
365±0,5
SSB1295-Y
B84143-G220-R11*
Terminal blocks 95
Anschlussklemmen
95 mm
mm22
Litz wire
Litze
Wire end ferrule
Aderendhülse
400
110
500±10
220
L3’
PE
M10 x 35
430
L1’
PE
1
30
0,5
79
110
L2’
Litz
wire markings
Litzenbezeichnung
Marking
LINE LOAD
106
L1
L2
L3
85±0,3
6,5
415±0,5
SSB1348-T
244 03/01
3-Line Filters
B84143-G*-R110
for Converters and Power Electronics
B84143-G*-R112
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143-G8-R11*
B84143-G20-R11*
SSB1288-G
120
αe
dB
αe
100
dB
100
80
80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
Hz 10 8
f
0
10 4
B84143-G36 … G220-R11*
SSB1290-S
120
αe
dB
100
80
60
40
20
0
10 4
10 5
10 6
10 7
SSB1289-P
120
Hz 10 8
f
245 03/01
10 5
10 6
10 7
Hz 10 8
f
Herausgegeben von EPCOS AG
Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
 EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und
Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG
nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften
zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen
für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland.
Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte
darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG
Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
 EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for
the Supply of Products and Services of the Electrical and Electronics Industry recommended by the
ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or
the international Representatives.
Due to technical requirements components may contain dangerous substances. For information on
the type in question please also contact one of our Sales Offices.
1