Specifications
Operating Voltage:
18-35VDC, 18-35VAC, 115VAC, 230VAC
Operating Current (R-10T/R14T):
23mA DC @ 18-35VDC, 59mA AC @ 18-35VAC;
150mA AC @ 120VAC, 180mA AC @ 240VAC
Operating Current (R-20T/R-24T):
40mA DC @ 18-35VDC, 92mA AC @ 18-35VAC;
220 mA AC @ 120VAC, 260mA AC @ 240VAC
Operating Temperature:
–40°F to 158°F (–40°C to 70°C)
Humidity Range:
10% – 93% RH non-condensing
Dimensions:
R-10T/R-20T: 3.5˝H × 2.5˝W × 1.25˝D (89 mm H × 64 mm W × 32 mm D)
R-14T/R-24T: 3.5˝H × 10˝W × 1.25˝D (89 mm H × 254 mm W × 32 mm D)
Accessories:
R-10T/R-20T – 2 mounting screws; R-14T/R-24T – 4 mounting screws
Contact Ratings:
24VDC 7A
120VAC 10A
120VAC 1/6 HP
230VAC 7A
Notice: This manual should be left with the owner/user of this equipment.
General Description
(SPDT) relay with 4 red LEDs. The R-20T is a single 2 Form
C (DPDT) relay with a red LED and the R-24T is a 4-gang 2
Form C (DPDT) relay with 4 red LEDs. The LEDs indicate
the energization of the Relay Coil.
Models R-10T/R-20T and R-14T/R-24T are multi voltage relays with terminal strip field wiring connections, mounting
track and hardware. The R-10T is a single 1 FORM C (SPDT)
relay with a red LED and the R-14T is a 4-gang 1 FORM C
NC
C
NC
NO
C
NO
NC
C
NO
18-35 V
18-35 V
0V
115 V
115 V
230 V
230 V
Not used
0V
Not used
18-35 VDC, 18-35VAC, 115VAC, 230VAC
18-35 VDC, 18-35VAC, 115VAC, 230VAC
C0567-01
R-10T Relay
R-20T Relay
Power
Limited
Non-Power
Limited
+
–
+
–
NO
18-35 VDC, 18-35VAC, 115VAC, 230VAC
C
Not used
0V
NC
D500-81-00
C0527-01
1
C0900-00
I56-2533-003
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in
materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other
express warranty for the enclosed product. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of
the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns
D500-81-00
2
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to replace units which
are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no
case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you. This Warranty gives you specific legal
rights, and you may also have other rights which vary from state to state.
I56-2533-003
©2006 System Sensor