Presence sensor (light and motion sensor) Fitting

Description
Purpose and application
The DUO sensor detects the presence of persons and measures the intensity of ambient light.
DUO
The sensor is designed for installation on ceilings or in luminaires using a T5/T8 holding clip and is ideal for the expansion
of existing electrical installations.
The following application types are available, depending on how
the sensor is connected (see the connection diagram):
• Alternative 1: One sensor switches a load area by means of
light and/or motion detection.
• Alternative 2: One sensor switches a load area by means
of light and/or motion detection. Additional motion detection
sensors are used to expand the detection area (slave mode).
Function
The sensor operates fully automatically and the values detected
by the sensor (motion, light value) control the switching
behaviour on the basis of the parameters set by the user. The
measured light value depends on the incidence of daylight, the
artificial lighting and the properties of the surface (light/dark).
The following parameters can be set:
Presence sensor
(light and motion sensor)
Fitting instructions
• Switch-off delay time (if no motion is detected)
• Light value
• Function mode
Design
The G
sensor is made up of the following components:
A
Upper section of housing:
• Motion sensor (A)
B
D
1
B
5
B
• Light sensor (C)
DUO
• Adjusting screws:
C
6 mm
0,34 - 1,5mm2
1
• LED (B)
1 2 3 4
E
F
ON
5
–– Setpoint for brightness (D)
0V N L
–0V– NSwitch-off
delay time (E)
L
DUO
• DIP switch on the back (F)
G
A
Lower section of housing:
G
• Connections (G):
–– L, N: Supply lines
B
1
5
F
1 2 3 4
B
1
DUO
–– Switch contact
–– Parallel circuit for joint motion detection
DUO
C
6 mm
0,34 - 1,5mm2
D
5
ON
E
B
0V N
0V N L
L
G
IX 2009
DUO_ma0909en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083214963550
4008321496355
Page 1 of 4
Installation
Safety instructions
The sensor must only be installed and put into operation by
a qualified electrician. The applicable safety regulations and
accident prevention regulations must be observed.
WARNING!
Exposed, live cables.
Danger of electric shock!
•
Only work on the sensor when it is deenergised.
CAUTION!
Destruction of the sensor and other devices through
incorrect mounting!
•
Adhere to the connection diagram.
•
Protect the sensor and switch contact jointly or
individually via external circuit breakers.
•
Only operate the sensor when it is closed (the
upper and lower sections of the housing are
firmly connected).
•
Supply the sensor via an AC power supply
only.
•
When mounting in luminaires, use a UVresistant cable.
Selecting the installation location
HOptimal mounting height: 2.5 – 3 m. As the mounting height
increases, the detection area increases and sensitivity is
reduced.
JMonitoring cone: Entire workplace; not on window surfaces
2,4 m
KAvoid exposure to direct light.
LPlace devices that radiate heat outside of the monitoring
cone.
MAvoid drafts (e.g. from ventilators)
H
3,7 m
2,7 2,1 1,5 0,9
100°
0
0,9 1,5 2,1 2,7
3,7 m
100°
J
K
L
M
Page 2 of 4
Attaching the sensor to the ceiling
Installation (cont.)
D

etermine a suitable installation location (see „Selecting the
installation location“).
S
‚
crew the lower section of the housing onto the ceiling.
Note: Follow step 5 to correctly align the unit.
ƒConnect the sensor; see „Connection diagram“.
A
„
ttach the upper section of the housing to the lower section.
…Make sure that the light sensor is facing the room.
Attaching the sensor to the fluorescent
lamps
N
Precondition: T5 or T8 lamps with a min. grid of 60 mm.
O
D

etermine a suitable installation location (see „Selecting the
installation location“).
I
nsert the lamp clip into the lower section of the sensor
‚
housing
ƒAttach the sensor to the lamp end with the lamp clip to avoid
weighing down the lamp excessively. Minimum distance to
the lampholder due to heat development of the coils: 8 cm.
I
f necessary, adjust the sensor installation depth to the depth
„
of the grid luminaire by sliding the lamp clip in or out.
N With lamp clip for 26 mm fluorescent lamp
O With lamp clip for 16 mm fluorescent lamp
…Pull the upper section of the housing off of the attached
lower section.
†Connect the sensor; see „Connection diagram“.
‡Reattach the upper section of the housing to the lower
section.
Connection diagram
Alternative 1:
L
N
PE
One sensor switches a load area by means of light and/or
motion detection.
220 - 240 V~ 50/60 Hz
P Switch contact
Q Load (ECG, lamps, etc.)
F1
6A/10A
L
N
0V
P
B
DUO
L
N
PE
Q
L
N
PE
Alternative 2:
220 - 240 V~ 50/60 Hz
F1
6A/10A
One sensor switches a load area by means of light and/or motion detection. A maximum of 5 additional sensors exclusively for
motion detection are used to expand the detection area.
F1
6A/10A
Precondition: DIP switches (F) 1 and 2 are set to OFF in the
slaves.
R
L
N
0V
P
DUO
B
L
S
N
L
U
N
Q
0V
P
0V
B
S Motion signal
TSensor in slave mode (motion detection only)
USensor in master mode
S
B
RTo additional sensors (a total of 6 sensors switched in
parallel!).
DUO
PE
T
ON
1
2
3
4
OFF
F
Limiting the motion detection area
The supplied lens cover can be used to limit the detection area
and to adjust it to local conditions.
Page 3 of 4
Appendix
Technical data
Operating voltage
220-240 V/50-60 Hz
(no DC operation)
Fuse
External 6 A (10 A)
Power consumption
Switched on: Approx. 1 W
Switched off: Approx. 0.7 W
Maximum total line
length
100 m
Switch output
Floating contact (internal relay, make
contact)
Switch output load
capacity
Resistive load: 10 A/250 V AC,
6 A/30 V DC
Ohmic lamp load: 5 A
Inductive load: 5 A
30 x single-lamp ECG 18 W
20 x two-lamp ECG 18 W
30 x single-lamp ECG 36 W
20 x two-lamp ECG 36 W
20 x single-lamp ECG 58 W
10 x two-lamp ECG 58 W
Detection area
Max. Ø 12 m
Installation height
Max. 5 m (ideal: 2.5 - 3 m)
Switching hysteresis
Approx. 15%
Operating temperature
0 °C ... +50 °C
Protection class
II
Protection type
IP 20
Weight
Approx. 150 g
Dimensions (L x W x H)
58.5 x 70.5 x 47 mm
Dimensioned drawing
Conformity with the relevant EU directives is
confirmed by the CE symbol.
Page 4 of 4