440 Surge Protective Device; Technical Specification (SS-70108)

400 Series
440 Surge Protective Device
Submittal Specification
General Specifications
Maximum Continuous Operating Voltage
Short Circuit Current Rating (SCCR)
Maximum Surge Current Rating
Operating Frequency Range
EMI/RFI Noise Rejection
UL1449 Location Type
UL1449 Nominal Discharge Current (In)
Status Indication (Standard)
120VAC 150%, all others 115%
200kAIC
50/100/150kA Per Mode, 100/200/300kA Per Phase
47-63Hz
40dB Max (Type 1), 60dB Max (Type 2)
Type 1 / Type 2
20kA
Green/Red LED, Audible Alarm, Alarm
Test/Silence Feature, & Relay Alarm Contacts
N-G Indication, Surge LED, Surge Counter, ATDS
ANSI/UL 1449 Third Edition Type 1 or Type 2; cUL
CE, IEC61643-11
Class I/II
NEMA Type 4X
Optional: NEMA 12, 4 (Steel)
Standard Non-Metallic Enclosure- 3.8 lbs (1.8 kg);
Optional NEMA 12 or 4 Enclosure- 12.7 lbs (7.8 kg)
10 Year Replacement
Status Indication (Optional)
Certifications
IEC Class
Standard Enclosure
Weights
Warranty
ANSI/UL 1449 Third Edition, Type 1 VPR’s
Source Configuration
SA, YA
YC
YD
DB / DF / DG
Model Number Configurator
L-N
800V
1200V
1500V
N/A
_4 _4 _0 _ _ _ _ _A _N _ _J _1 _S
Configuration & Voltage
SA
Single Phase,
3W+G
(L1, L2, N, G)
YA
Three Phase
WYE, 4W+G
(L1, L2, L3, N, G)
Three Phase
WYE, 4W+G
(L1, L2, L3, N, G)
Three Phase
WYE, 4W+G
(L1, L2, L3, N, G)
YC
YD
DB
DF
DG
Three Phase
Delta, 3W+G
(L1, L2, L3, G)
Three Phase
Delta, 3W+G
(L1, L2, L3, G)
Three Phase
Delta, 3W+G
(L1, L2, L3, G)
120/240 VAC
120/208 VAC,
127/220 VAC
05
10
15
277/480 VAC,
254/440 VAC
A
L
C
T
220 VAC, 230
VAC, 240 VAC
480 VAC
S
Standard
X
Consult Factory for additional source
configurations, Surge Ratings, Monitoring
Options, Enclosure Ratings, Etc.
9.6”
[244]
For a unit with the RJ-45 Ethernet
port accessible on the front cover,
change the enclosure rating from
NEMA 4X (440xxxxxxxTJxx) to
NEMA 1 (440xxxxxxxTCxx)
Enclosure Type
NEMA 12 Steel
NEMA 4 Steel
* Model Number
440xxxxxxALxx
440xxxxxxAGxx
10” x 8” x 4”
[254] x [203] x [102]
Monitoring Option
Red & Green LEDs, Relay Alarm Contacts
& Audible Alarm
* Steel enclosure units require
the “A” monitoring option.
“A” option plus N-G LEDs & Surge LED
“A” option plus N-G LEDs & Surge Counter
Advanced Transient Detection System
See publication SL-70109, TS-70109
CUL Approvals
For all applications requiring CUL approvals,
change the SPD model number from a UL Type 1
(440xxxxxxxx1x) to a UL Type 2 (440xxxxxxxx2x)
NEMA 4X Enclosure (“J”)
External Ethernet
Port Option
N-G
800V
1200V
1500V
N/A
Replace the “J” in the standard model number
(11th digit) with an “L” or “G” as shown below for
an optional steel enclosure.
Dimensional Information
600 VAC
L-L
1200V
2000V
2500V
2000V / 2000V / 3000V
Optional Steel Enclosures
NEMA 4 or NEMA 12
Additional Accessories
Surge Rating
50kA Per Mode
100kA Per Phase
100kA Per Mode
200kA Per Phase
150kA Per Mode
300kA Per Phase
346/600 VAC
L-G
800V
1200V
1500V
1200V / 1800V / 2000V
½” NPT FLEXIBLE
CONDUIT
Advanced Transient
Detection System
A Web-Based Power Quality Monitor
Integrated within a Surge Protection Device
4.9”
[124]
100 Emerson Parkway
4.0”
Binghamton, NY 13905
[102]
P (607) 721 8840
P (800) 288 6169
F (607) 722 8713
E [email protected]
½” NPT FLEXIBLE CONDUIT
(24”) AND CONNECTOR
ASSEMBLY INCLUDED




Real-Time Measurements
Event Logging with Time/Date Stamp
Embedded Web Page
Ethernet, MODBUS, RS-485
Communications
 SPD Health Status - % Protection remaining
 LCD Display
2.1”
[53]
1.7”
[44]