OMRON S8VS

Switch mode Power Supply
S8VS
Visible and Slim New Din Rail Power Supply
• Ultra-compact size (40 (W) × 95 (H) mm) (60-W Model)
• Displayed on 3-digit, 7-segment LED shows many status
(voltage, current etc.) of power supply.
• Approved standards: UL508/60950, CSA C22.2 No.14/60950,
EN50178 (=VDE0160), EN60950 (=VDE0806)
Model Number Structure
■ Model Number Legend
S8VS- @@@@@@
1
2
3
1. Power Ratings
060: 60 W
090: 90 W
2. Output voltage
24: 24 V
3. Configuration
None: Standard Power Supply
A:
With maintenance forecast monitor
B:
With total run time monitor
Ordering Information
Power ratings
60 W
Type
Standard type
Output voltage
24 V
Output current
2.5 A
With maintenance forecast monitor type
S8VS-06024A
With total run time monitor type
Standard type
S8VS-06024B
3.75 A
S8VS-09024
With maintenance forecast monitor type
S8VS-09024A
With total run time monitor type
S8VS-09024B
Power
Supplies
90 W
Model number
S8VS-06024
Switch mode Power Supply
S8VS
L-55
Specifications
■ Ratings/Characteristics
Power ratings
Type
Item
Efficiency (typical)
Input
Voltage
Frequency
Current
Standard
60 W
Maintenance
Total run time
forecast monitor
monitor
78% min.
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 450 Hz)
1.7 A
1.0 A
Conforms to EN61000-3-2 A-14
0.5 mA max.
1.0 mA max.
25 A max.
50 A max.
−10% to 15% (with V.ADJ)
2.0% (p-p) max. (at rated input/output voltage)
0.5% max. (at 85 to 264 VAC input, 100% load)
1.5% max. (with rated input, 0 to 100% load)
Standard
90 W
Maintenance
forecast monitor
Total run time
monitor
80% min.
2.3 A
100 V input
1.4 A
200 V input
Power factor correction
Leakage
100 V input
current
200 V input
Inrush current 100 V input
(See note 1.)
200 V input
Output
Voltage adjustment range
Ripple
Input variation influence
Load variation influence
(rated input voltage)
Temperature variation influence 0.05%/°C max.
500 ms max.
1,000 ms max.
500 ms max.
Start up time (See note 1.) 1,000 ms max.
(at rated input/output voltage)
(at rated input/output voltage)
20 ms min. (at rated input/output voltage)
Hold time (See note 1.)
Additional Overload protection (See note 1.) 105% to 160% of rated load current, inverted L drop, intermittent, automatic reset
function
Overvoltage protection (See note 1.) Yes
Yes (selectable) (See note 3.)
No
Yes (selectable) (See note 3.)
Output voltage indication (See note 2.) No
Yes (selectable) (See note 4.)
No
Yes (selectable) (See note 4.)
Output load indication (See note 2.) No
Yes (selectable) (See note 5.)
No
Yes (selectable) (See note 5.)
Peak-hold load indication (See note 2.) No
Yes (selectNo
No
Yes
No
Maintenance forecast monitor No
indication (See note 2.)
able)
(selectable)
No
Yes (open collector
No
Maintenance forecast
monitor output
output), 30 VDC max.,
50 mA max.
No
Yes
No
Yes
Total run time monitor
indication (See note 2.)
(selectable)
(selectable)
Yes (open collector
No
Total run time monitor
output
output), 30 VDC max.,
50 mA max.
No
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm
indication (See note 2.)
Yes (open collector output),
Undervoltage alarm output No
terminals
30 VDC max., 50 mA max.
No
Parallel operation
Yes (with external diode)
Series operation
Operating: Refer to the derating curve in Engineering Data. (with no icing or condensation) Storage: −25 to 65°C
Other
Ambient temperature
Operating: 25% to 85%; Storage: 25% to 90%
Ambient humidity
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
Dielectric strength
2.0 kVAC for 1 min. (between all inputs and GR terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and GR terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
100 MΩ min. (between all outputs/ alarm outputs and all inputs/ GR terminals) at 500 VDC
Insulation resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Vibration resistance
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Yes (color: green)
Output indicator
Electromagnetic interference Conforms to FCC Class A, EN50081-2
Conforms to EN50081-2
EMI
UL: UL508 (Listing; Class 2: Per UL1310), UL60950
UL: UL508 (Listing), UL60950
Approved standards
cUL: CSA C22.2 No.14, No.60950 (Class 2)
cUL: CSA C22.2 No.14, No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806) EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806)
330 g max.
490 g max.
Weight
Note: 1.
2.
3.
4.
5.
L-56
Refer to the Engineering Data section on page 59 for details.
Displayed on 7-segment LED.
Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (±1 digit for output voltage value)
Resolution of output load indication: 0.1 A, Precision of output load indication: ±5% (±1 digit for output load value)
Resolution of Peak-hold load indication: 0.1 A, Precision of Peak-hold load indication: ±5% (±1 digit for output load value), width of Peakhold load indication: 10 ms
Switch mode Power Supply S8VS
Connections
■ Block Diagram
S8VS-06024 (60 W)
S8VS-06024A (60 W)
S8VS-06024B (60 W)
(See note.)
Display circuit
Switch
Arithmetic
operation circuit
Rectifier/smoothing circuit
Fuse 3.15 A
+V
AC (L)
INPUT
DC OUTPUT
Noise filter
−V
AC (N)
Inrush
current
protection
circuit
Rectifier/smoothing circuit
Rectifier/
smoothing
circuit
Drive control
circuit
Overcurrent
circuit
Current detection
circuit
Detection
circuit
Overvoltag
detection circuit
Photo coupler
Note: The circuits within the dotted line are for the S8VS-06024@ Model only.
S8VS-09024 (90 W)
S8VS-09024A (90 W)
S8VS-09024B (90 W)
(See note.)
Display circuit
Switch
Alarm
DC LOW
Arithmetic
operation circuit
Yrs
Rectifier/smoothing circuit
Photo coupler
Common
Fuse 4.0 A
+V
AC (L)
INPUT
DC OUTPUT
Noise filter
−V
AC (N)
Inrush
current
protection
circuit
Rectifier/
smoothing
circuit
Drive control
circuit
Rectifier/smoothing circuit
Overcurrent
circuit
Current detection
circuit
Power
Supplies
Detection
circuit
Overvoltag
detection circuit
Photo coupler
Note: The circuits within the dotted line are for the S8VS-09024@ Model only.
Switch mode Power Supply
S8VS
L-57
■ Installation
60-W Model
S8VS-06024
S8VS-06024@
1
2
1
2
6
7
8
4
5
4
5
3
3
90-W Model
S8VS-09024
S8VS-09024@
1
2
1
2
6
7
10
8
9
4
5
4
5
11 13
12 3
3
No.
Name
1
AC Input terminals
(L), (N)
2
Ground terminals
(GR)
3
DC Output terminals
(−V), (+V)
4
Output indicator
(DC ON: Green)
5
Output voltage
adjuster (V.ADJ)
6
Main display
(See note 2.)
7
Operation
V
indicator
(See note 2.)
A
Apk
Yrs
Kh
L-58
Function
Connect the input lines to these
terminals. (See note 1.)
Connect the ground line to this terminal.
Connect the load lines to these
terminals.
Lights while a direct current (DC) output
is ON.
Use to adjust the voltage.
No.
Name
8
Mode Key (See note 2.)
9
Up Key (See note 3.)
10
Down Key (See note 3.)
11
Alarm Undervoltage alarm
output output terminal (DC
terminal LOW) (See note 3.)
Maintenance forecast
monitor terminal (Yrs)
(S8VS-09024A)
Total run time monitor
output terminal (Kh)
(S8VS-09024B)
(See note 3.)
Common terminal
Terminal (emitter) shared for
for alarm output
alarm outputs (11) and (12).
(See note 3.)
Indicates the measurement or set value.
Lights up when the output voltage is
indicated. Blinks during setup of
undervoltage alarm value.
Lights up during indication of output current.
Lights up during indication of peak hold current.
Lights up during indication of maintenance
forecast monitor. Blinks during setup of
maintenance forecast monitor setting.
(S8VS-0…024A)
Lights up during indication of total run
time monitor. Blinks during setup of total
run time monitor. (S8VS-0@024B)
Switch mode Power Supply S8VS
Function
Use the Mode Key to change the
indicated parameter or reset the
peak hold current value.
Use the Up Key to change to the
setting mode or to increase the set
value.
Use the Down Key to change to
the setting mode or to decrease
the set value.
Outputs when a drop in the
output voltage is detected.
(at voltage drop: OFF)
Outputs when the maintenance
forecast has reached the set
value.
12
13
Note: 1. The fuse is located on the (L) side.
2. S8VS-@@@24@ only.
3. S8VS-09024@ Model only.
Engineering Data
Load (%)
■ Derating Curve
■ Overvoltage Protection
The Power Supply is provided with an overvoltage protection function
that protects the load and the Power Supply from possible damage
by overvoltage. When an excessive voltage is output, the output voltage is shut OFF. Reset the Power Supply by turning it OFF for at
least three minutes and then turning it back ON again.
120
100
Output voltage (V)
80
60
40
Overvoltage protection
operating
+15%
20
Rated output
voltage
0
−20
−10
0
10
20
30
40
50
60
Variable range
−10%
70 80
Ambient temperature (˚C)
Installation
Upper
0V
Upper
Note: Do not turn ON the power again until the cause of the overvoltage has been removed.
■ Inrush Current, Start Up Time,
Hold Time
Standard mounting
Face-up mounting
Note: 1. Use standard mounting only. Using any other mounting
method will prevent proper heat dissipation and may result
in deterioration or damage of internal elements. Or, the remaining service life notice function cannot work properly.
2. If there is a derating problem, use forced air-cooling. The
ambient temperature is specified for a point 50 mm below
the power supply.
■ Overload Protection
Input OFF
AC input
voltage
Inrush current on input application
AC input
current
96.5%
90%
Output
voltage
Start up time (1,000 ms max.)
Hold time (20 ms min.)
Output voltage (V)
The Power Supply is provided with an overload protection function
that protects the load and the power supply from possible damage by
overcurrent. When the output current rises above 105% min. of the
rated current, the protection function is triggered, decreasing the output voltage. When the output current falls within the rated range, the
overload protection function is automatically cleared.
Input ON
0
50
Power
Supplies
Intermittent operation
100
Output current (%)
Note: Do not allow the short-circuited or overcurrent state to continue
for more than 20 s, otherwise internal elements may deteriorate
or be destroyed.
Switch mode Power Supply
S8VS
L-59
■ Undervoltage Alarm Function (Indication and Output)
When output voltage drop is detected, an alarm (a01) and lowest
output voltage value are indicated alternately. The preset value of
detection voltage can be changed in the setting mode.
(S8VS-06024@: The value of detection voltage is fixed at 20V)
Further, the alarm is output from the transistor ((11) DC LOW) to an
external device with the S8VS-09024A/B.
(Upon output voltage alarm: OFF; with no continuity across (11) and
(13))
:
In the case that the
output voltage drops
below the set value (19V)
and an alarm is issued
AC input
Detection value
of Undervoltage
alarm
Output
voltage
Undervoltage
output
Main display
Operation
mode
Lowest value of
output voltage
Voltage indication
Note: Operation begins after about three seconds since the AC power is supplied.
Note: 1. Operation begins after about two seconds since the AC
power is supplied.
2. The alarm is not indicated in the setting mode.
((8) Mode Key) after the output voltage is re3. Press the
stored, to reset alarm indication.
4. The undervoltage alarm function monitors the output terminal voltage of the power supply unit. To check the voltage
accurately, measure the voltage at the load end.
Engineering Data (S8VS-@@@24@ Only)
■ Mode Change
Power-ON
■ Operation Mode
Various states of the power supply unit are indicated.
Model indication
Operation mode
Press and hold
Up or Down Key for
three seconds or more.
Output voltage
Key Press and hold for
three seconds or more.
Or no key operation for 30 seconds or more.
Setting mode
Output current
Note: No setting mode is provided for the S8VS-06024@.
Peak hold current
Maintenance forecast monitor
(S8VS-@@@24A)
or total run time monitor
(S8VS-@@@24B)
Note: The output voltage will be displayed when the power supply is
first turned on after it is received from the factory. Thereafter,
the output voltage will be indicated in the same display when
shutting down.
L-60
Switch mode Power Supply S8VS
■ Setting Mode
(Except for S8VS-06024@)
■ Total Run Time Monitor
Indication and Alarm Output
(S8VS-@@@24B)
Set various parameters of the power supply unit.
Undervoltage
alarm
The cumulative running hours of the power supply unit are monitored
as total run time. When the total run time reaches the predetermined
alarm set value, an alarm (a02) and the total run time monitor are
indicated alternately with an output issued from the transistor ((12)
Kh) to an external device. (The output is turned off when the total run
time reaches the alarm set value; with no continuity across (12) and
(13).)
*
18.5 t o 20.0 t o 27.5 (V)
0.1V intervals
Maintenance
forecast monitor
(S8VS-09024A)
or Total run time
monitor alarm
(S8VS-09024B)
*
0.0 t o 0.5 to 5.0 (years)
The alarm set value can be changed in the setting mode.
0.5 year intervals
In the case that the total
run time reaches the
set value (88kh) and an
alarm is issued
*
1 t o 50 to 150 (kh)
1 kh intervals
* The reverse video indicates
the shipment setting.
Note: 1. Press and hold the (9) Up Key or (10) Down Key for two seconds or more to increase or decrease the value rapidly.
2. The S8VS-06024@ is not provided with the setting mode
and its parameters are fixed at the shipment setting.
■ Peak Hold Current Reset
Note: 1. The total run time cannot be reset. To reset the alarm, increase the alarm set value beyond the value indicated as total run time.
Ex.) If a customer decided to change the load at 5,000
hours, when they turn the unit again the timing will start at
5,000 hours and on.
2. The alarm function (setting, indication, and output) is not
provided for S8VS-06024B.
Operation mode
Key 3 seconds or more
Reset
2 seconds
Peak hold current
value measurement
starts
Note: The peak hold current value is not reset in the setting mode.
■ Self-Diagnostics Function
Description
Output state
Restoration method
Setting after restoration
--h%t
e01
Noise detected in voltage or current
No change
Automatic restoration
No change
Overheated
(12) OFF
Automatic restoration
No change
e02
Memory error of alarm set value of
(12) OFF
maintenance forecast monitor or total
run time monitor
e03
Other memory error
Undervoltage alarm set value memory (11) OFF
error
(11) (12) OFF
Shipment setting or
Press and hold the (9) Up Key or (10)
Down Key for three seconds and check value set in the setting
the set value of the corresponding point. mode again
The set value must return to the
shipment setting
Turn the AC input off then on again.
If the product is not reset, contact the
dealer.
No change
Note: 1. External noise is probable as a cause of “---”, “e01 ”, “e02 ” and “e03 ” errors.
2. Operation out of the derating curve area, ventilation error, and incorrect mounting direction are probable as a cause of “h%t” error.
3. If the “h%t” error state continues for about three hours, the maintenance forecast monitor function (S8VS-@@@24A only) becomes invalid.
The indication for maintenance forecast monitor remains as “h%t” even after the overheat condition is removed, and the Yrs output (12)
remains OFF (with no continuity across (12) and (13)).
Replace the power supply if this condition occurs even if the output is correct, as internal parts may be deteriorated.
4. The “h%t” error detection function is only for the S8VS-@@@24A.
Switch mode Power Supply
S8VS
L-61
Power
Supplies
(6) Main display
■ Undervoltage Alarm Indication
■ Maintenance Forecast
This indicator lights when the output voltage is insufficient.
Displays when the maintenance forecast has reached the set value.
Operation
Mode
Operation
Mode
The maintenance forecast
has reached the set value.
Undervoltage occurs.
Undervoltage
alarm
Maintenance
forecast
monitor
*
* This indicator alternately
displays alarm (
)
and the output voltage
lower limit.
Output
current
*
Remaining time
until replacement
Output voltage lower limit
Output
voltage
* This indicator alternately
displays alarm (
)
and the maintenance
time until replacement.
Peak-hold
current
Output
current
Maintenance
forecast
monitor
Peak-hold
current
Note: The display changes to the output voltage display when the
voltage is restored to the set value or higher.
■ Indication and Output
■ Multiple Alarms
When the product is purchased, “ful” will be indicated. As electrolytic capacitors deteriorate, indication changes to “hlf ”. After the
remaining time to maintenance is reduced to two years, indication
automatically changes to a value, which decreases from “1.5” to “1.0 ”
to “0.5” to “0 ” (year) as the running hours increase.
When two or more different alarms occur at the same time
Operation Mode
If the maintenance forecast monitor setting is set to a value larger
than two years, value indication automatically begins after the
remaining time to maintenance is reduced to the set years.
Undervoltage
alarm
*
The indication shifts
alternately in the direction
of the arrow every 2 s.
Maintenance
forecast monitor
*
* When undervoltage alarm is indicated: Press
output load indication
When the maintenance forecast monitor or overheat alarm is indicated:
Press
undervoltage alarm indication
L-62
Switch mode Power Supply S8VS
If the remaining time becomes smaller than setting L (which can be
set arbitrarily between 0 and 5.0 years), an alarm (a02) and the
remaining time are indicated alternately.
With the S8VS-09024A, an output is given to an external device from
a transistor ((12) Yrs) to notify of the replacement timing, together
with indication. (The output is turned off after the replacement timing
is reached; with no continuity across (12) and (13).)
In the case that the
remaining time is reduced
to smaller than 0.5 year
and an alarm is issued.
Note: 1. The remaining time to maintenance is based on continuous
operation, not including the time when the power supply is
turned off, and so may take longer to reach than the actual
time indicated.
2. Until the power supply has been turned for about one month
in total, indication is fixed at “ful” to estimate the extent of
deterioration, while the output remains turned on (with continuity across (12) and (13)).
■ Maintenance Forecast Monitor Function
The power supply unit is equipped with electrolytic capacitors.
The electrolyte inside the electrolytic capacitor penetrates the sealing rubber and evaporates as time passes since it is manufactured,
which causes deterioration of characteristics such as decreasing the
capacitance, etc.
Due to this deterioration of the characteristics of the electrolytic
capacitor, the power supply unit decreases its performance as time
passes.
The maintenance forecast monitor function shows an approximate
period left for maintenance of the power supply unit due to deterioration of electrolytic capacitors. When the period left for maintenance
that the power supply forecasts reaches the set value, an alarm is
indicated and an output signal is triggered.
Use this function to know the approximate replacement timing of the
power supply unit.
Note: The maintenance forecast monitor function indicates an approximate period left for maintenance, based on deterioration
of the electrolytic capacitor. It does not predict failures caused
by other reasons.
Relationship Between Indicated Values and Output of Set Values
L: Maintenance forecast set value
(See note.) 0.0 to 5.0, 0.5 steps
In case of setting L between 2.5 and 5 years.
Initial capacity
(L−0.5)
"1.0" is displayed on the main display for the
duration that the maintenance forecast up to
replacement satisfies the condition 1.0 ≤ T < 1.5.
Capacity level
at replacement
Capacity of Capacitor
5.0
Main display
2.5
2.0
1.5
1.0
0.5
0
T: Maintenance time
until replacement
L=2.5
Maintenance forecast monitor output
L=0.5
■ Principle of Operation
The deterioration speed of the electrolytic capacitor varies considerably according to the ambient temperature. (Generally the speed follows “Rule of Two for every 10°C”; for every 10°C increase in
temperature the rate of degradation doubles according to Arrhenius’s
equation.) The S8VS-0@024A monitors the temperature inside the
power supply, and calculates the amount of deterioration according
to the running hours and inside temperature. Judging by this amount
of deterioration, the power supply will give the alarm indication and
output when the period left for maintenance reaches the set value.
Note: 1. Due to degradation of internal electronic parts, replace the
power supply at least once every 15 years even if indication
and output of maintenance forecast monitor are not issued.
2. The maintenance forecast is accelerated or decelerated according to operating conditions. Periodically check indication.
The numerical value
decreases with time.
■ Reference Value
Item
Value
Reliability
(MTBF)
Definition
135,000 hrs MTBF stands for Mean Time Between
min.
Failures, which is calculated according to
the probability of accidental device failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
Life
10 yrs. min. The life expectancy indicates average opexpectancy
erating hours under the ambient temperature of 40°C and a load rate of 50%.
Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
Note: The “maintenance forecast” is the service life (the power supply’s internal temperature is monitored at all times) of the internal electrolytic capacitor in actual operating conditions, and
varies according to the customer’s operating conditions. 15
years is taken as the maximum period of the maintenance forecast.
Power
Supplies
Note: This function can be set only on the S8VS-09024A Model.
Switch mode Power Supply
S8VS
L-63
Dimensions
Note: All units are in millimeters unless otherwise indicated.
S8VS-06024 (60 W)
S8VS-06024A (60 W)
S8VS-06024B (60 W)
11.3
Five, M4
with square washer
10
97
35.4
95
74
1
40
108.3
Track stopper
4.5
(Sliding: 15 max.)
Note: The photo is the S8VS-06024A Model.
S8VS-09024 (90 W)
S8VS-09024A (90 W)
S8VS-09024B (90 W)
10.8
Five, M4
with square washer
110.5
10
34.9
115
94
50
4.5
(Sliding: 15 max.)
Track stopper
Screwless block (2.5 mm pitches)
1
121.3
Note: The photo is the S8VS-09024A Model.
■ DIN Track (Order Separately)
Note: All units are in millimeters unless otherwise indicated.
Mounting Track (Material: Aluminum)
PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3
15
25
10
25
25
1,000 (500) *
10
25
27±0.15
15(5) *
1
*Values in parentheses
are for the PFP-50N.
Mounting Track (Material: Aluminum)
16
PFP-100N2
4.5
35±0.3 27
15
L-64
25
10
Switch mode Power Supply S8VS
25
25
1,000
10
25
15
29.2
24
1
1.5
Precautions
Operating and Storage Environments
!Caution
Do not disassemble the product or touch internal parts.
Electric shock may be caused.
Do not touch the product during power-on, and immediately after
poweroff. Hot surface may cause heat injury.
Tighten the terminal screw with torque 1.08 N·m.
A loose screw may cause fire.
Install the terminal cover.
Electric shock may be caused if not installed.
Mounting
Be sure to allow convection in the atmosphere around devices when
mounting. Do not use in locations where the ambient temperature
exceeds the range of the derating curve.
When cutting out holes for mounting, make sure that cuttings do not
enter the interior of the products.
Before turning the Power Supply ON, be sure to remove sheets that
were used as covers during mounting, and make sure that heat
release is not obstructed.
Do not use or store the Power Supply in the following locations.
Doing so may result in failure, malfunction, or deterioration of performance characteristics.
• Do not use in locations subject to direct sunlight.
• Do not use in locations where the ambient temperature exceeds
the range of the derating curve.
• Do not use in locations where the humidity is outside the range
25% to 85%, or locations subject to condensation due to sudden
temperature changes.
• Do not store in locations where the ambient temperature is outside
the range −25 to 65°C or where the humidity is outside the range
25% to 90%.
• Do not use locations where liquids, foreign matter, corrosive gases,
or flammable gases may enter the interior of products.
S8VS-@@@24A Model Only
Satisfy the following conditions when storing the Power Supply for
long periods of time to maintain its remaining service life function.
• When storing for more than three months, store within an ambient
temperature range of −25 to +30°C and the humidity range of 25 to
70%.
*1
Periodic Inspection (S8VS-09024A
Model Only)
*2
*1
*1. Convection of air
*2. 20 mm min.
Wiring
Ground the product (GR) completely. Failure to do so could cause
electric shock or malfunction.
Ensure that input and output terminals are wired correctly.
Do not apply more than 100N force to the terminal block when tightening it.
Be sure to remove the sheet covering the product for machining
before power-on.
Recommended Wire Type
Model
Under general operating conditions, the remaining service life function starts to work from several to ten and several years after start of
use. When the Power Supply is used for long periods of time, periodically follow the procedure below to check that the remaining service life function ((12)Yrs) is working properly.
1. Set to the Power Supply to the Run Mode.
2. Make sure that output ((12)Yrs) is ON (electrical continuity across
terminals (12) and (13)).
3. In the Run Mode, hold down the Down Key (10) and the Mode
Key (8) for at least three seconds at the same time.
The main display ((6)) changes to a02.
This function is working properly if output ((12)Yrs) is OFF (no
electrical continuity across terminals (12) and (13)).
4. Release the key to return to the regular mode.
Note: DC output is also maintained during periodic inspection.
1
2
6
7
10
8
9
Recommended wire size
S8VS-06024@
AWG14 to 20
(Cross section 0.517 to 2.081mm2)
S8VS-09024@
AWG14 to 18
(Cross section 0.823 to 2.081mm2)
Alarm output terminal: AWG22 to 28
(Cross section 0.081 to 0.326mm2)
Installation Environment
Do not use the Power Supply in locations subject to shocks or vibrations. In particular, install the Power Supply as far away as possible
from contactors or other devices that are a vibration source.
Power
Supplies
Install the Power Supply well away from any sources of strong, highfrequency noise.
4
5
11 13
12 3
Switch mode Power Supply
S8VS
L-65
Charging the Battery
If a battery is to be connected as the load, mount an overcurrent limiting circuit and an overvoltage protection circuit.
Output Voltage Adjuster
Note: 1. Connect the diode as shown in the figure. If the load is
short-circuited, a reverse voltage may be applied inside the
power supply unit, causing deterioration or breakage of the
power supply unit.
Select a diode having the following ratings.
Type
Do not add unnecessary power. The output voltage adjuster (V.ADJ)
may be damaged.
DIN Track Mounting
To mount the Block on a DI track, hook portion (A) of the Block onto
the track and press the Block in direction (B).
A
Schottky Barrier diode
Dielectric strength
(VRRM)
Twice the rated output voltage or
above
Forward current
(IF)
Twice the rated output current or
above
2. Though products having different specifications can be connected in series, the current flowing through the load must
not exceed the smaller rated output current.
Parallel Operation
The product is not designed for parallel operation.
AC (L)
B
To dismount the Block, pull down portion (C) with a flat-blade screwdriver and pull out the Block.
AC (N)
AC (L)
AC (N)
+V
−V
+V
−V
In Case There is No Output Voltage
30 mm min.
The possible cause for no output voltage may be the presence of an
overload or overvoltage condition, or may be due to the functioning of
an latching protective device. The latching protection may operate if
a large amount of surge voltage such as a lightening surge occurs
while turning on the power supply.
C
Track stopper
Series Operation
Two power supplies can be connected in series.
The (±) voltage output can be accomplished with two power supplies.
In case there is no output voltage, please check the following points
before contacting us:
Check the Overload Protected Status:
AC (L)
+V
AC (N)
−V
AC (L)
+V
AC (N)
−V
• Check whether the load is in overload status or is short-circuited.
Remove wires to load when checking.
• Attempt to clear the overvoltage or latching protection function:
Turn the power supply off once, and leave it off for at least 3 minutes. Then turn it on again to see if this clears the condition.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. T026-E1-01
L-66
In the interest of product improvement, specifications are subject to change without notice.
Switch mode Power Supply S8VS
Switch mode Power Supply
S8PS
The Most Compact DIN-track-mounting
Switch mode Power Supplies Ever with
Capacities Up to 600 W
• Power range from 50 W up to 600 W.
• Open-frame and covered types available.
• Easily mounted to DIN track with provided Mounting Brackets.
• Models with Front-mounting Bracket available.
• Conforms to EMC standards: EN50081-1, EN50082-2, and
EN61000-3-2.
• Maintenance-free up to 300 W due to natural ventilation.
• Protection-ON alarm indicator shows valuable protection functions in action (300-/600-W models).
• AC universal input: 100 to 240 VAC
• Approved by UL/CSA standards, EN60950 (IEC950), and
VDE0160.
• Six-language instruction manual provided.
• Life expectancy of 10 years min.
• Finger protection terminal block meets VDE0106/P100. (Covered type)
Model Number Structure
■ Model Number Legend
2. Output Voltage
05: 5 V
12: 12 V
24: 24 V
3. Configuration
C:
Covered type with Front-mounting Bracket
D:
Open-frame type with DIN Track Mounting Bracket
CD: Covered type with DIN Track Mounting Bracket
None: Open-frame type with Front-mounting Bracket
S8PS-@@@@@@@
1
2
3
1. Power Ratings
050: 50 W
100: 100 W
150: 150 W
300: 300 W
600: 600 W
Ordering Information
■ List of Models
Covered type
Open-frame type
Input voltage
100 to 240 VAC
100 to 240 VAC
Power ratings
50 W
Output voltage
Output current
Front-mounting
Bracket
DIN Track Mounting
Bracket
5V
10 A
S8PS-05005C
S8PS-05005CD
12 V
4.2 A
S8PS-05012C
S8PS-05012CD
24 V
2.1 A
S8PS-05024C
S8PS-05024CD
100 W
24 V
4.5 A
S8PS-10024C
S8PS-10024CD
150 W
24 V
6.5 A
S8PS-15024C
S8PS-15024CD
300 W
24 V
14 A
S8PS-30024C
S8PS-30024CD
600 W
24 V
27 A
S8PS-60024C
---
50 W
5V
10 A
S8PS-05005
S8PS-05005D
12 V
4.2 A
S8PS-05012
S8PS-05012D
24 V
2.1 A
S8PS-05024
S8PS-05024D
100 W
24 V
4.5 A
S8PS-10024
S8PS-10024D
150 W
24 V
6.5 A
S8PS-15024
S8PS-15024D
Switch mode Power Supply
S8PS
L-67
Power
Supplies
Configuration
Specifications
■ Ratings/Characteristics
Item
50 W
100 W
150 W
300 W
2.7 or 1.4 A
max.
5.4 or 2.7 A
max.
Efficiency (typical)
75 to 87% (depends on the model)
Input
Voltage
100 to 240 VAC (85 to 264 VAC)
Frequency
47 to 450 Hz
Current (see note 1)
0.9 or 0.45 A
max.
Power factor (see note 1)
0.95 TYP.
Output
Additional
function
Other
1.8 or 0.9 A
max.
600 W
10 or 5 A max.
Leakage current (see note 1)
0.5 or 1.0 mA max.
Inrush current (25°C, cold start) (see note 1)
25 or 50 A max.
Voltage adjustment range
−5% to 10%
Ripple (see note 1)
2% (p-p) max.
Input variation influence
0.4% max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100% load)
Load variation influence
0.8% max. (with rated input, 0 to 100% load)
Temperature variation influence (see note 1)
0.05%/°C max.
Rise time
1,000 ms max. (up to 90% of output voltage at rated output voltage/current)
Hold time (see note 1)
20 ms min.
Overload protection
105% min., voltage trailing intermittent operation
(With the 600-W model, output is turned OFF at 5 s min.)
Overvoltage protection
Yes
Overheat protection
No
Protection-ON alarm indicator
No
Yes (Red)
Yes, 2 units max.
Yes
Parallel operation
No
Heat radiation
Natural air-cooling
Ambient temperature
Operating:
Storage:
Fan
See the derating curve in the Engineering Data section. (with no condensation
nor icing)
−25°C to 65°C (with no condensation nor icing)
Ambient humidity
25% to 85%
Dielectric strength
3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)
Insulation resistance
100 MΩ min. (between all output and input/GR terminals at 500 VDC)
Vibration resistance
10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions
Shock resistance
300 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (green)
Terminal screw tightening torque
1.08 N·m (see note 2)
Electromagnetic interference
Conforms to FCC Class B, EN50081-1
EMC
(EMI):
Emission Enclosure:
Emission AC Mains:
Harmonic Current:
(EMS):
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Immunity Surge:
EN50081-1
EN55022 class B
EN55022 class B
EN61000-3-2
EN50082-2
EN61000-4-2: 4-kV contact discharge (level 2)
8-kV air discharge (level 3)
ENV50140:
10 V/m (80 MHz to 1 GHz) (level 3)
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2-kV power-line (level 3)
2-kV output line (level 4)
EN61000-4-5: between 3-kV lines
between 4.5-kV line and FG
Approved standards
UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.
Conforms to UL1950 and CSA E.B. 1402C
Reliability (MTBF) (see note 3)
135,000 hrs min.
Life expectancy (see note 4)
10 yrs. min. (Used at 40°C at the rated input with a 50% load, standard installation)
Weight (see note 5)
420 g max.
Mounting method
Front-mounting Bracket or DIN Track Mounting Bracket
60,000 hrs min.
600 g max.
900 g max.
2,200 g max.
3,500 g max.
Front-mounting Bracket
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates
reliability of devices. Therefore, it does not necessarily represent a life of the product.
4. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40°C and a load rate
of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be noted that the life
expectancy of the fan built into the 600-W model is not included.
5. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)
L-68
Switch mode Power Supply S8PS
Connections
■ Block Diagrams
S8PS-050@@@@ (50 W)
AC(L)
INPUT
Rectifier
Fuse
(4 A)
+V
Noise filter
AC(N)
DC OUT
Inrush current
protection circuit
Harmonic
current
control
Smoothing
Rectifier/
smoothing
circuit
−V
Drive control
circuit
Overload
detection circuit
Detector
Overload
detection circuit
S8PS-10024@@ (100 W)
S8PS-15024@@ (150 W)
S8PS-30024@@ (300 W)
Rectifier
AC(L)
Fuse*
INPUT
+V
Noise filter
AC(N)
DC OUT
Inrush current
protection circuit
*Fuse capacity
100-W: 6.3 A
150-W: 6.3 A
300-W: 8 A
Harmonic
current
control
Smoothing
Rectifier/
smoothing
circuit
−V
Control circuit
Overload
detection circuit
Detector
Overload
detection circuit
S8PS-60024C (600 W)
INPUT
AC(N)
Rectifier
Fuse
(15 A)
+V
Noise filter
DC OUT
Inrush current
protection circuit
Harmonic cur- Smoothrent control
ing
Rectifier/
smoothing
circuit
−V
Control circuit
Fan
Power
Supplies
AC(L)
Detector
Overcurrent
detection
Overheat
detection
Overload
detection circuit
Switch mode Power Supply
S8PS
L-69
■ Installation
50-W Models
100-/150-W Models
4
5
4
5
1
1
3
3
2
2
300-W Models
4
5
600-W Models
1
5 4
6
2
1
3
1. DC Output Terminals: Connect the load lines to these terminals.
2. Input Terminals: Connect the input lines to these terminals.
6 2
3
Note: A fuse is inserted into the AC (L) side.
3. Ground Terminal (GR): Connect a ground line to this terminal.
4. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON.
5. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%.
6. Protection-ON Alarm Indicator: The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for a
600-W model) circuit is triggered. This indicator will also be lit when overcurrent (for a 600-W model) is detected.
L-70
Switch mode Power Supply S8PS
Engineering Data
■ Derating Curve
Covered Type
Load (%)
50- to 150-W Model
Forced air-cooling
50- to 150-W Model
Natural air-cooling
50- to 300-W Model
Forced air-cooling,
600-W Model
Load (%)
Open-frame Type
50- to 300-W Model
Natural air-cooling
Ambient temperature (°C)
Ambient temperature (°C)
Note: 1. Forced air-cooling must be provided with an air volume of 1 m3/mm min.
2. The derating curve shown is for standard installation. The derating curve depends on the mounting direction of the Power Supply.
Standard Installation
50-W Model
20 mm min. 20 mm min.
20 mm min.
20 mm min.
20 mm min.
20 mm min.
20 mm min.
20 mm min.
Standard Installation
100/150-W Model
30 mm min.
30 mm min.
20 mm min.
20 mm min.
30 mm min.
30 mm min.
20 mm min.
20 mm min.
Standard Installation
300-W Model
30 mm min.
30 mm min.
20 mm min.
20 mm min.
Standard Installation
600-W Model
20 mm min.
20 mm min.
20 mm min.
Power
Supplies
20 mm min.
Switch mode Power Supply
S8PS
L-71
■ Overload Protection
■ Overvoltage Protection
The Power Supply is provided with an overvoltage protection function
that protects the load and the Power Supply from possible damage
by overvoltage. When the output voltage rises above a set value
(115% of the rated output voltage), the protection function is triggered, shutting OFF the output voltage. If this occurs, reset the
Power Supply by turning it OFF for 1 minute min. and then turning it
ON again.
50- to 300-W Models
Output voltage (V)
Output voltage (V)
The Power Supply is provided with an overload protection function
that protects the load and the power supply from possible damage by
overcurrent. The protection function operates when the load current
rises above an overcurrent set value (105% of the rated load current). For a short-circuit or overcurrent lasting less than 20 seconds,
output voltage is decreased to protect equipment. When the output
current falls within the rated range, the overload protection function is
automatically cleared.
Overvoltage
protection
operating
Rated output
voltage
Variable range
Intermittent
operation
0V
300- and 600-W Models Only
Rating
Output current (%)
The overvoltage protection-ON alarm indicator lights when the function is operating.
Note: Do not continue using the S8PS under short-circuited or overcurrent conditions for longer than 20 seconds, otherwise the internal elements of the S8PS may be damaged or broken.
■ Overheat Protection Function
600-W Models
600-W Model Only
If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously protection-ON alarm indicator will be lit. To
reset the S8PS, turn OFF the input voltage, leave the S8PS for at
least three minutes, and then apply the input voltage again.
If the internal temperature of the S8PS rises excessively as a result
of fan failure or any other reason, the overheat protection circuit will
be triggered to protect the internal elements of the S8PS and simultaneously a protection-ON alarm indicator will be lit. To reset the
S8PS turn OFF the input voltage, leave the S8PS for at least one
minute and then apply the input voltage again.
Note: Do not continue using the S8PS with the output terminals
short-circuited or the overcurrent condition continued, otherwise the internal elements of the S8PS may be damaged or
broken.
■ Inrush Current, Rise Time, Hold Time
Input ON
Input OFF
AC input
voltage
Inrush current on input application
AC input
current
96.5%
90%
Output
voltage
L-72
Rise time
(1,000 ms max.)
Switch mode Power Supply S8PS
Hold time
(20 ms min.)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Front-mounting Bracket Type
The Front-mounting Bracket is provided as an accessory. Screws for fixing the Bracket to the panel are not provided.
S8PS-050@@ (50 W)
S8PS-050@@@C (50 W)
11.5 max.
Five, M4 terminal screws
3.5 dia.
3.5 dia.
Three, M3 (depth: 6 max.)
Front-mounting Bracket for 50-W Models
Attach the Mounting Bracket to the panel and loosely
tighten the two screws. Insert the projected parts of the
Bracket (b) to the square holes of the power supply (a).
Then securely tighten the screws.
Mounting Holes
11
1.5
Using the Mounting Bracket
4.6
15±0.2
9
60
Two,
3.5 dia.
74
Two, M3
60
4.6
11
5
20
20
31.5
4.7
15
20.5
Mounting Bracket
11.5 max.
S8PS-10024 (100 W)
S8PS-10024C (100 W)
4.5 dia.
Mounting holes (also on opposite side)
Power
Supplies
Five, M4 terminal screws
4.5 dia.
Three, M4 (depth: 4 max.)
Switch mode Power Supply
S8PS
L-73
S8PS-15024 (150 W)
S8PS-15024C (150 W)
11.5 max.
Five, M4 terminal screws
4.5 dia.
Mounting holes (also on opposite side)
4.5 dia.
Three, M4 (depth: 6 max.)
Front-mounting Bracket for 100/150-W Models
Appearance and Mounting Dimensions
Dimensions with Mounting Bracket
Using the Mounting Bracket
Mounting Bracket
5 dia.
115 max.
Two, 5 dia.
Eight, M4 (depth: 8 max., also for the opposite side)
Seven, M4 terminal screws
S8PS-30024C (300 W)
(14)
Four, M4 (depth: 8 max.)
L-74
Switch mode Power Supply S8PS
S8PS-60024C (600 W)
Seven, M4 (depth: 8 max.)
Eight, M4 (depth: 8 max., also for the opposite side)
Four, M4 (depth: 8 max., opposite side only)
Four, M4
(depth: 8 max.)
Using the Mounting Bracket
Note: Four screws for attaching the Bracket to
Dimensions with Mounting Bracket
the Power Supply Unit are provided.
300-W models
300-W models
Front-mounting Bracket for 300/600-W Models
Appearance and Mounting
Dimensions
10 dia.
Two, 5 dia.
Four, M4
Note: Mount the Unit 21.6 mm away from the
mounting surface in order to provide air
ventilation on the rear side.
Four, M4
Note: Mount the Unit 28 mm away from the mounting surface in order to provide air ventilation
on the rear side.
Switch mode Power Supply
S8PS
L-75
Power
Supplies
600-W models
600-W models
■ DIN Track Mounting Bracket Type
DIN Track Mounting Bracket
DIN Track Mounting Bracket is
attached to the Power Supply
Unit when the Unit is shipped.
S8PS-050@@D (50 W)
S8PS-050@@@CD (50 W)
11.5 max.
Five, M4 terminal screws
3.5 dia.
S8PS-10024D (100 W)
S8PS-10024CD (100 W)
11.5 max.
Five, M4 terminal screws
S8PS-15024D (150 W)
S8PS-15024CD (150 W)
4.5 dia.
5.6
(With slide: 9 max.)
11.5 max.
Five, M4 terminal screws
4.5 dia.
L-76
5.6
(With slide: 9 max.)
Switch mode Power Supply S8PS
5.6
(With slide: 9 max.)
S8PS-30024CD (300 W)
(14)
Seven, M4 terminal screws
5.6
(With slide: 9 max.)
■ Accessories
Mounting Track (Order Separately)
PFP-100N/PFP-50N
PFP-100N2
16
7.3±0.15
4.5
4.5
35±0.3
15
25
25
10
25
1,000 (500)
(see note)
15
25
10
35±0.3 27
27±0.15
15 (5)
(see note)
1
25
25
10
25
1,000
25 15
10
24
29.2
1
1.5
Power
Supplies
Note: The values shown in parentheses are for the
PFP-50N.
Switch mode Power Supply
S8PS
L-77
Precautions
Parallel Operation
!WARNING
Do not attempt to disassemble the Power Supply or touch its internal parts while power is being supplied. Doing so may result in
electric shock.
Do not touch the terminals of the Power Supply within one minute
after power has been turned OFF. Doing so may result in electric
shock due to a residual voltage.
Do not touch the S8PS or heat radiation fin while the power is being supplied or immediately after the power is turned OFF. Otherwise, a skin burn may result from the hot Switching Power Supply
or radiator.
Only 300- and 600-W models can be in parallel operation provided
that they are operated under 90% of the ratings. Do not operate any
other models in parallel.
Make sure that the thickness and the length of all wires connected to
the load are the same to ensure that the wires will have no voltage
drop differences.
+V
INPUT
Load
!Caution
Be sure to connect the grounding line. Not doing so may result in
electric shock.
−V
+V
INPUT
Mounting
−V
To improve and maintain the reliability of the Power Supply over a
long period of time, adequate consideration must be given to heat
radiation.
The Power Supply is designed to radiate heat by means of natural
air-flow. Therefore, mount the Power Supply so that air flow takes
place around the Power Supply.
When mounting the Power Supply, mounting it to a metal plate is recommended.
Forced air-cooling is highly recommended.
Fan Replacement
The service life of the fan is approximately 50,000 hours (at 25°C).
The service life varies, however, depending on the ambient temperature or other surrounding environmental conditions such as dust. As
a preventive maintenance measure, replace the fan within two years
if it is used at an ambient temperature of 40°C.
Fans are available as replacements.
It is recommended that the clearance around the Power Supply be
larger than those shown on page page 71 under Standard Installation.
Generating Output Voltage (±)
An output of ± can be generated by using two Power Supplies as
shown below, because the Power Supply produces a floating output.
+V
−V
Load
+V
Load
INPUT
Input
INPUT
Model: S82Y-JFAN
Fan Set:
Fan (above), four M4 x 35 sems screws, instruction sheet, and packing case
Replace the fan as shown in the following illustration.
−V
Series Operation
Only models with power ratings of 100/150 W allow series operation.
As shown in the following diagram, the output voltage from each
Switching Power Supply can be added.
+V
−V
Load
INPUT
+V
INPUT
−V
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. T021-E1-03
L-78
In the interest of product improvement, specifications are subject to change without notice.
Switch mode Power Supply S8PS