TELEDYNE XV46D30K

Series XV
Single Output to 30A 420 Vac
No Heat Sink, Hybrid Relay
Part Number
Description
XV46D30K
30A, 420 Vac
Part Number Explanation
XV
46
D
30
K
NOTES
1) Line Voltage (nominal): 46 = 420 Vac
2) Switch Type: D = Zero-cross turn-on
3) Control Range: K = 20–30 Vdc, *C = 12 Vdc also available
MECHANICAL SPECIFICATION
1.10 (28)
1.87 (47.6)
2.41 (61.3)
.27
(6.8)
1.77 (45)
1.70 (43.2)
WEIGHT: 5.64 oz (160g)
Ø.19 (Ø4.7)
.35 (9)
M4
FEATURES/BENEFITS
• Industry standard package
• Combines the best of solid-state and
electromechanical relays
• Tight zero-cross window for low EMI
• Control LED
• Internal output protection
• High immunity to surges
DESCRIPTION
The Series XV relay combines the best of solid-state
and electromechanical technology. The relay is
designed in a touch-proof hockey-puck package. The
XV relay switches current up to 30A without a heat
sink. Visual control status is provided as a standard.
Elimination of the heat sink conserves space and
makes the XV ideal for numerous applications.
M3.5
1.75 (44.5)
1.00 (25.4)
Figure 1 – XV relay; dimensions in inches (mm)
INPUT (CONTROL) SPECIFICATION
Min
Max
Units
Control Range*
20
30
Vdc
Input Current Range
31
41
mAdc
Must Turn-Off Voltage
10
Vdc
Input Resistance (Typical)
640
Ohms
Reverse Voltage Protection
30
Vdc
Control Frequency
1
Hz
APPLICATIONS
• Interface applications
• Heating Control
• Light/Lamp control
• Contactor driver
• Fan speed control
• HVAC controls
APPROVALS
Model XV46D30K is UL recognized.
UL File Number: E128555.
CONTROL CHARACTERISTIC
TYPICAL APPLICATION
45
A1+
t3
Vc
SSR
Supply
t1
A1-
T1
t2
EMR
VL
L1
LED
Input Current (mA)
40
35
30
25
20
15
10
Load
Figure 2 – XV relay
5
0
0
5
10
15
20
25
30
35
Control Voltage (V)
Figure 3 – XV relay
© 2003 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
XV 1
XV\032003\Q1
Series XV
OUTPUT (LOAD) SPECIFICATION
Max
12
420
Vrms
800
Vpeak
Peak Voltage
Load Current Range
0.1
Motor Load Current
Unit
30
Arms
7.5
Arms
250
200
Apeak
Operating Range
SURGE CURRENT
Min
Maximum Surge Current Rating (Non-Repetitive)
(See Figure 4)
240
Apeak
0.3
V
Zero-Cross Window (Typical)
±12
V
Off-State Leakage Current (60Hz)
2
mA
Turn-On Time (60Hz)
12
ms
Turn-Off Time (60Hz)
20
ms
Off-State dv/dt
500
V/µs
Maximum di/dt (Non-repetitive)
50
A/µs
Operating Frequency
440
Hz
288
2
40
I t for fuse matching (<8.3ms)
100
50
On-State Voltage Drop
2
150
0
1
10
100
1000
Number of Cycles
Figure 4 – XV relay
LIFETIME EXPECTANCY
5
At maximum rated current
(Resistive load)
AS
ENVIRONMENTAL SPECIFICATION
Min
Max
Unit
Operating Temperature
–40
90
°C
Storage Temperature
–40
100
°C
4000
Vrms
4000
V
Input-Output Isolation
Output-Case Isolation
Life Expectancy
See Figure 5
10 6 Operations
4
3
2
1
0
100
200
300
400
500
Load Voltage (V)
Figure 5 – XV relay
NOTES:
1. Electrical Specifications at 25°C unless otherwise specified.
2. For 800Hz applications, contact factory.
3. For additional/custom options, contact factory.
XV 2
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2003 TELEDYNE RELAYS
XV\032003\Q1