PROTEC 420LB35

05048
420LE28
thru
Only One Name Means ProTek’Tion™
420LB60
TWO LINE PAIR 4-20mA CONTROL LOOP PROTECTOR
APPLICATIONS
420LB
✔ Multi-Process Control Loops
✔ Fire & Security Systems
✔ Petro-Chemical Plants
✔ Refineries & Tank Farms
IEC COMPATIBILITY (EN61000-4)
✔ 61000-4-2 (ESD): Air - 15kV, Contact - 8kV
✔ 61000-4-4 (EFT): 40A - 5/50ns
✔ 61000-4-5 (Surge): 8/20µs - 95A, Level 4 (Line-Gnd) & 48A, Level 4 (Line-Line)
FEATURES
420LE
✔ Designed for 4-20mA Current Loops
✔ Automatic Reset - Does Not Interrupt Service
✔ Permanent Two-Stage Line Pair Protection
✔ Common Mode & Differential Mode Protection
✔ Subnanosecond Response Time
✔ Effective Against Lightning, Inductive Switching and ESD
MECHANICAL CHARACTERISTICS
✔ Weight: 420LB - 28 grams & 420LE - 142 grams (Approximate)
✔ Flammability Rating UL 94V-0
✔ Device Marking:
Case - Logo, Terminal Designations & Part Number
Board - Logo, Date Code & Part Number
DESCRIPTION
The 420LE/B series is a two stage transient voltage protector providing primary and
secondary protection against lightning, inductive switching and electrostatic discharge
(ESD) transient threats. The first stage diverts the transient current through the ground
terminal return path and the second stage clamps the voltage to a safe level without
interruption of service.
The 420LE/B series is designed to protect data lines from differential (line to line) and
common mode (line to ground) transients. Terminals 1 and 2, 3 and 4 for the 420LE
and pins 2 and 3, 4, and 5 for the 420LB are designated as line pairs. Each line pair is
referenced to ground. A transient voltage suppressor is connected across each line
pair for differential mode protection. Each line pair is referenced to ground.
This product can also be used on telephone, signal/data lines, security, timing and
control interface circuits. For most applications, the product should be located as close
as possible to the equipment being protected. A low impedance grounding system is
important to maintain a low voltage clamp between the line-to-ground connection.
05048.R3 11/03
1
www.protekdevices.com
420LE28
thru
420LB60
DEVICE CHARACTERISTICS
MAXIMUM RATINGS @ 250C
Operating Line Current
100mA
Operating Temperature
-55 to 1000C
Storage Temperature
-55 to 1000C
Transient Source Voltage
6kV
Transient Current (8/20µs)
10kA
ELECTRICAL CHARACTERISTICS @ 250C Ambient Temperature
PROTEK
PART
NUMBER
420LE28
420LE35
420LE60
420LB28
420LB35
420LB60
MAXIMUM
OPERATING
LINE VOLTAGE
MAXIMUM
LEAKAGE
CURRENT
VOP
± VOLTS
@ VOP
ID
µA
MAXIMUM
CLAMPING
VOLTAGE
(8/20µs)
@2,000A
VC
VOLTS
28.0
35.0
60.0
28.0
35.0
60.0
5.0
5.0
5.0
5.0
5.0
5.0
40
60
85
40
60
85
MAXIMUM
MAXIMUM
CAPACITANCE LINE THRUPUT
RESISTANCE
@ 0V, 1 MHz
C
pF
R
OHMS
2800
1500
1000
2800
1500
1000
12
12
12
12
12
12
INSTALLATION INSTRUCTIONS
There are five (5) terminals on the LINE SIDE and five (5) terminals on
the EQUIPMENT SIDE of the 420LE, 4 data lines and one ground. Both
grounds are connected together internally. A single low impedance is
ground sufficient. Incoming data lines are cut or disconnected from the
equipment to insert the 420LE/B products. The incoming lines are to be
connected to the line side terminals as the equipment side lines are
connected to the equipment side terminals. The location of the product
should be as close to the equipment as possible. The 420LE/B series is
designed with a short circuit failure mode to give maximum protection. A
fuse, fussable link, or circuit breaker is recommended for each data/
signal line on the input side for those that require an open circuit failure
mode.
05048.R3 11/03
Caution: A low DC resistance ground may not be indicative of a good
lightning ground. Lightning contains a broad spectrum of frequencies up
to 1 MHz. A low impedance path to ground at the transient frequencies is
necessary. A ground strap is recommended or a #6 AWG stranded wire.
For wire lengths over 1.5 meters, there may be some excessive line to
earth potential under severe thunderstorm conditions.
2
www.protekdevices.com
420LE28
thru
420LB60
PACKAGE OUTLINE & DIMENSIONS
420LE CASE OUTLINE
420LB BOARD OUTLINE
0.325” MAX
(8.25mm)
3.8” MAX
(96.5mm)
3.25”±0.015”
(82.6mm±0.38mm)
3.0” MAX
(76.2mm)
4
WARNING:
4
2
2
EQUIPMENT
2.25” MAX
(57.2mm)
1
1
Terminal Screw
LINE
LINE
GND
EQUIPMENT
Adhesive Mylar Label
GND
3
3
1.125”
(28.575mm)
3.8” MAX
(95.5mm)
CONTINUITY
Mounting Hole for #8 Screw
Orientation Notch
Terminal Strip
0.61” MAX
(15.5mm)
0.30” MAX
(7.6mm)
#6 Screw
1.19” MAX
(30.2mm)
1.9” MAX
(48.2mm)
2
5
12
15
GND
OUTPUT Connected to
Transmit/Receiver Circuits
0.07
(17.8mm)
INPUT
12
13
14
15
OUTPUT
5
4
3
2
INPUT Connected to Lines
From Out Side World
NOTE: I/O contacts spaced at 0.156” (3.96 mm) centers
COPYRIGHT © ProTek Devices 2003
SPECIFICATIONS: ProTek reserves the right to change the electrical and or mechanical characteristics described herein
without notice (except JEDEC).
DESIGN CHANGES: ProTek reserves the right to discontinue product lines without notice, and that the final judgement
concerning selection and specifications is the buyer’s and that in furnishing engineering and technical assistance,
ProTek assumes no responsibility with respect to the selection or specifications of such products.
05048.R3 11/03