ETC 420LE60

05048
420LE28
thru
420LB60
. . . engineered solutions for the transient environment™
TWO LINE PAIR 4-20mA CONTROL LOOP PROTECTOR
APPLICATIONS
✔ Multi Process Control Loops
✔ Fire & Security Systems
✔ Petro-Chemical Plants
✔ Refineries & Tank Farms
IEC COMPATIBILITY (EN61000-4)
✔ 61000-4-2 (ESD): Air - 15kV, Contact - 8kV
✔ 61000-4-4 (EFT): 40A - 5/50ns
✔ 61000-4-5 (Surge): 8/20µs - 95A, Level 4(Line-Gnd) & 48A, Level 4(Line-Line)
420LE PACKAGE
FEATURES
✔ Designed for 4-20mA Current Loops
✔ Automatic Reset - Will Not Interrupt Service
✔ Permanent Two-Stage Line Pair Protection
✔ Line-to-Ground (Common) & Line-to-Line (Differential) Protection
✔ Subnanosecond Response Time
✔ Effective Against Lightning, Inductive Switching & ESD
MECHANICAL CHARACTERISTICS
✔
✔
✔
✔
420LB BOARD
Module Weight 160 grams (Approximate)
Board Weight 32 grams (Approximate)
Flammability Rating UL 94V-0
Device Marking: Part Number, Logo, Date Code, and Terminal Designations for the LE Device
DESCRIPTION
The 420LE/B series is a two stage transient voltage protector providing primary and secondary protection against lightning, inductive
switching and electrostatic discharge (ESD) transient threats. The first stage diverts the transient current through the ground terminal
return path and the second stage clamps the voltage to a safe level without interruption of service.
The 420LE/B series is designed to protect data lines from differential (line to line) and common mode (line to ground) transients.
Terminals 1 and 2, 3 and 4 for the 420LE and pins 2 and 3, 4, and 5 for the 420LB are designated as line pairs. Each line pair is
referenced to ground. A transient voltage suppressor is connected across each line pair for differential mode protection. Each line
pair is referenced to ground.
This product can also be used on telephone, signal/data lines, security, timing and control interface circuits. For most applications,
the product should be located as close as possible to the equipment being protected. A low impedance grounding system is important to maintain a low voltage clamp between the line-to-ground connection.
05048.R2 7/02
1
www.protekdevices.com
420LE28
thru
420LB60
DEVICE CHARACTERISTICS
MAXIMUM RATINGS @ 250C
Operating Line Current
Operating Temperature
100mA
-55 to 1000C
Storage Temperature
-55 to 1000C
Transient Source Voltage
6kV
Transient Current (8/20µs)
10kA
ELECTRICAL CHARACTERISTICS @ 250C Ambient Temperature
PROTEK
PART
NUMBER
MAXIMUM
OPERATING
LINE VOLTAGE
MAXIMUM
LEAKAGE
CURRENT
VOP
± VOLTS
@ VOP
ID
µA
MAXIMUM
CLAMPING
VOLTAGE
(8/20µs)
@2,000A
VC
VOLTS
28.0
35.0
60.0
28.0
35.0
60.0
5.0
5.0
5.0
5.0
5.0
5.0
40
60
85
40
60
85
420LE28
420LE35
420LE60
420LB28
420LB35
420LB60
MAXIMUM
MAXIMUM
CAPACITANCE LINE THRUPUT
RESISTANCE
@ 0 V, 1 MHz
R
C
pF
OHMS
2800
1500
1000
2800
1500
1000
12
12
12
12
12
12
INSTALLATION INSTRUCTIONS
There are five (5) terminals on the LINE SIDE and five (5) terminals on the EQUIPMENT SIDE of the 420LE, 4 data lines and one ground. Both
grounds are connected together internally. A single low impedance is ground sufficient. Incoming data lines are cut or disconnected from the
equipment to insert the 420LE/B products. The incoming lines are to be connected to the line side terminals as the equipment side lines are
connected to the equipment side terminals. The location of the product should be as close to the equipment as possible. The 420LE/B series is
designed with a short circuit failure mode to give maximum protection. A fuse, fussable link, or circuit breaker is recommended for each data/signal
line on the input side for those that require an open circuit failure mode.
Caution: A low DC resistance ground may not be a good ground. Lightning contains a broad spectrum of frequencies up to 1 MHz. A low
impedance path to ground at the transient frequencies is necessary. A ground strap is recommended or a #6 AWG stranded wire. For wire
lengths over 1.5 meters, there may be some excessive line to earth potential under severe thunderstorm conditions.
420LE CASE OUTLINE
420LB BOARD OUTLINE
0.325” MAX
(8.25mm)
3.8” MAX
(96.5mm)
3.25”±0.015”
(82.6mm±0.38mm)
3.0” MAX
(76.2mm)
4
WARNING:
4
2
2
EQUIPMENT
2.25” MAX
(57.2mm)
1
1
Terminal Screw
LINE
LINE
GND
EQUIPMENT
Adhesive Mylar Label
GND
3
3
1.125”
(28.575mm)
3.8” MAX
(95.5mm)
CONTINUITY
Mounting Hole for #8 Screw
Orientation Notch
Terminal Strip
0.61” MAX
(15.5mm)
0.30” MAX
(7.6mm)
#6 Screw
1.19” MAX
(30.2mm)
1.9” MAX
(48.2mm)
2
5
12
15
GND
OUTPUT Connected to
Transmit/Receiver Circuits
0.07
(17.8mm)
INPUT
12
13
14
15
OUTPUT
5
4
3
2
INPUT Connected to Lines
From Out Side World
NOTE: I/O contacts spaced at 0.156” (3.96 mm) centers
COPYRIGHT © ProTek Devices 2001
SPECIFICATIONS: ProTek reserves the right to change the electrical and or mechanical characteristics described herein without notice (except
JEDEC).
DESIGN CHANGES: ProTek reserves the right to discontinue product lines without notice, and that the final judgement concerning selection and
specifications is the buyer’s and that in furnishing engineering and technical assistance, ProTek assumes no responsibility with respect to the
selection or specifications of such products.
05048.R2 7/02