SCHRACK General Purpose Relays Safety Relay on DIN-rail SR6 Z n 6 pole 8 A n SR6 on printed circuit board n AC / DC input n Screwless clamp connectors n Module width 46 mm Applications Elevator control, machine control F0238-C Contact data Terminal assignment Contact set single contact, forcibly guided type A according to EN50205 Rated voltage / max. switching voltage AC 250 VAC / 250 VAC Rated current / limiting continuous current 8A Maximum breaking capacity AC 2000 VA Contact material AgSnO2 Minimum contact load 10 mA / 5 V Contact resistance w100 mOhm / 1 A / 24 VDC w20 Ohm / 10 mA / 5 VDC Rated frequency of operation with / without load 6 min-1 / 150 min-1 DC module, 4 NO+2 NC version S0422-BA Coil data DC energizing voltage Urtd 6, 12, 18, 21, 24, 36, 40, 48, 60, 115 VDC AC/DC energizing voltage Urtd 12, 21, 24, 40, 48, 60,115 VAC/VDC AC energizing voltage Urtd 230 VAC Input circuit bridge rectifier, series resistor Minimum operate voltage, % of rated coil voltage 90% Minimum release voltage (+23°C), % of rated coil voltage 10% Limiting voltage, % of rated coil voltage 110% DC module, 3 NO+3 NC version Insulation Surge voltage resistance coil-contacts open contact circuit adjacent contacts Clearance / creepage coil-contact adjacent contacts Insulation to IEC 60664 Voltage rating Pollution degree Overvoltage category 3000 Vrms 1000 Vrms 2000 Vrms W 5.5 / 5.5 mm W 3 / 3 mm S0422-BB DC module, 5 NO+1 NC version 250 V 2 III S0422-BC AC/DC module, 4 NO+2 NC version AC/DC module, 3 NO+3 NC version AC/DC module, 5 NO+1 NC version S0422-BD S0422-BE S0422-BF 1 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the ‘Schrack’ section. Specifications subject to change. SCHRACK General Purpose Relays Safety Relay on DIN-rail SR6 Z (Continued) Other data 10x106 cycles Mechanical endurance Material RoHS - Directive 2002/95/EC Environment Ambient temperature Processing Connections (according IEC) solid wire stranded wire AWG Installation position Mounting Type of connection Relay weight Packaging unit compliant -25...+50 °C 0.2...2.5 mm2 0.2...2.5 mm2 28...14 any in rows with zero spacing screwless clamp connectors 90 g 2 pcs Dimensions Module width 46 mm Module length 87 mm Fit onto mounting rails according to DIN EN 50022 or DIN EN 50035 S0423-A Product key Typical product key SR6Z A 524 Type SR6Z Safety Relay on DIN-rail SR6 Z Contact configuration A 3 NO + 3 NC contacts (3 form A + 3 form B) B 4 NO + 2 NC contacts (4 form A + 2 form B) C 5 NO + 1 NC contacts (5 form A + 1 form B) Coil DC Coil code = rated coil voltage (e.g. 024=24 VDC) AC/DC coil code: 524=24 VAC/VDC, 615=115 VAC/VDC AC coil code: 730=230 VAC Other types on request Product key SR6ZA024 SR6ZA524 SR6ZA615 SR6ZA730 SR6ZB024 SR6ZB524 SR6ZB615 SR6ZB730 SR6ZC024 SR6ZC524 SR6ZC615 SR6ZC730 Type 6-pole safety relay module Contact configuration 3 NO + 3 NC contacts Contact material AgSnO2 4 NO + 2 NC contacts 5 NO + 1 NC contacts Coil 24 VDC 24 VAC/VDC 115 VAC/VDC 230 VAC 24 VDC 24 VAC/VDC 115 VAC/VDC 230 VAC 24 VDC 24 VAC/VDC 115 VAC/VDC 230 VAC Part number 7-1415033-1 9-1415059-1 1415060-1 1-1415060-1 5-1415033-1 2-1415060-1 6-1415046-1 3-1415060-1 3-1415042-1 4-1415060-1 5-1415060-1 6-1415060-1 2 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the ‘Schrack’ section. Specifications subject to change.