MA-COM 1810X

Paralleling Relays
WILMAR™ Protective Relays – 1800 Series
Function: 25
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
#6 - 32 STUDS
6 PLACES
3
Application:
These relays are designed for automatic paralleling
(synchronizing) of generators. The relays sense the
phase angle displacement and the amplitude difference between two voltages and permit paralleling
only when both voltages are equal and in phase. A
short time delay is provided to assure that the
frequencies are essentially the same at the moment
of paralleling. The basic series is designed to parallel
two or more energized AC generators. The “Dead
Bus” type provides paralleling of AC generators to
the main bus. They permit electrical connection of an
energized generator to an un-energized line (Dead
Bus). If the bus is energized, connection of the
generator to the bus is permitted only when both are
synchronized.
4
1 /2
4
7 /8
4
7 /8
3 5 /8
4
11/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
Part Number
1800 Series
Sensing Voltage .............................
120 V, 230 V, 277 V, 380 V, 460 V, 575 V, & 415 V
Line Frequency ...............................
Pick-Up Adjustment .......................
50-500 Hz
External adjustment for field sensing of 10-30% of
nominal input voltage. (Vertical voltage differential of 6
to 18 electrical degrees).
Time Delay .....................................
Fixed @ 60 milliseconds is provided to assure that the
frequencies of both input lines are sufficiently close to
permit paralleling within the preset window.
Output Contacts .............................
36
A. 3 Phase, 4 Wire System
Connect phase "A" of LINE 1 to terminal 1
Connect phase "A" of LINE 2 to terminal 3
Connect the neutrals to terminals 2 & 4
B. 3 Phase, 3 Wire or 1 Phase, 2 Wire System
Connect phase "A" of LINE 1 to terminal 1
Connect phase "B" of LINE 1 to terminal 2
Connect phase "A" of LINE 2 to terminal 3
Connect phase "B" of LINE 2 to terminal 4
Consult factory for additional models and options.
One set N.O., one set N.C.
5 amp resistive at 120 VAC or 28 VDC
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
Paralleling Relays
Function:
Selection Guide
(Typical Applications)
Sensing Voltage
Series 1800
Generator to Generator
Series 1800DB
Generator to Bus
Series 1800DDB
Bus to Bus
Permits paralleling of two generators
only when they are "on-line" and
their voltages are equal and in phase
(synchronized)
Normally used to permit
paralleling of a generator to a
bus when: (a) both line
voltages are equal and in phase,
or: (b) when the generator is
"on-line" and the bus is "dead"
Permits paralleling of two power
lines (buses) when: (a) both line
voltages are equal and in phase, or:
(b) when either bus is "hot" and the
other bus is "dead"
120 Volts
1810X
1810DBX
1810DDBX
230 Volts
1820X
1820DBX
1820DDBX
380 Volts
1830X
1830DBX
1830DDBX
460 Volts
1840X
1840DBX
1840DDBX
575 Volts
1850X
1850DBX
1850DDBX
415 Volts
1860X
1860DBX
1860DDBX
277 Volts
1870X
1870DBX
1870DDBX
Condition
Series 1800
Contacts
Energized
Not
Energized
Synch.
Line 1
X
Line 2
X
Yes
Line 1
X
No
Line 2
X
No
Line 1
X
1
2
3
Line 2
X
Line 1
X
Line 2
X
Line 1
X
4
5
Line 2
Series 1800DB
Contacts
Series 1800DDB
Contacts
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Open
Close
Open
Close
Open
Close
Close
Open
Close
Open
Close
Open
Close
Open
Open
Close
Open
Close
Close
Open
Close
Open
Close
Open
Close
Open
Close
Open
Open
Close
X
Output Contact Options: 1. Two Form A. (Add -A to Model Number)
2. Two Form B. (Add -B to Model Number)
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)