SUPREX® II CYPRESS Connection Diagram INDUSTRY LEADERS DEPEND ON US ...FOR SOLUTIONS Cypress Computer Systems, Inc. • 1778 Imlay City Rd. • Lapeer, MI 48446-3206 TX(810)245-2300 • FX(810)245-2332 • www.cypresscom.com }A 8 7 6 5 4 3 2 1 SUPREX Remote Unit Off Line + On LED RS-232 Connector Line +8 to +24 Vdc @ 150 ma Ground Dip Switch Off Line + Line - SUPREX Central Unit On LED RS-232 Connector +8 to +24 Vdc @ 150 ma Ground OUTPUT RELAYS 8 7 6 5 4 3 2 1 }C Aux Relay Control +5 Vdc @ 100 ma Data 0 / Clock Data 1 / Data LED Program Resistor #2 Program Resistor #1 Ground READER Input 1 +8 to +24 Vdc @ 150 ma Dip Switch D{ C{ ACCESS CONTROL PANEL }B OUTPUT RELAYS Input 2 B{ A{ Normally Closed Common Normally Open Normally Closed Common Normally Open } } Door Strike Relay 125 Vac @ 1 Amp Aux Output Relay 125 Vac @ 1 Amp +8 to +24 Vdc @ 150 ma To control door strike relay, short LED to Ground Ground +5 Vdc @ 100 ma Data 0 / Clock }D Data 1 / Data LED Normally Closed Common Normally Open Normally Closed Common Normally Open } } Trouble / Output Relay 2 125 Vac @ 1 Amp Output Relay 1 125 Vac @ 1 Amp Actual size of each circuit board is 4-1/2” x 2-5/8” 1 2 3 4 5 6 7 8 9 RS-232 DB-9 Male 2 - Receive 3- Transmit 5 - Ground SUPREX® II Remote Unit Dip Switch Setting Switch #2 - On = Door Strike Relay does NOT follow LED status. Off = Door Strike Relay follows status of LED. Switch #6* - On = Bit mode (Noise filter off) for keypad applications. Off = Noise filter mode, standard reader applications (Default setting) SUPREX® II Central Unit Dip Switch Setting Switch #3 - On = Inverts idle on MagStripe version Off = Normal operation of MagStripe version Switch #4 - On = Inverts Aux 2 Relay Status Off = Normal operation *Not active on versions earlier than 2-1-2003 When wired and powered up corectly, LEDs on Remote and Centrol will blink 5 to 10 times per second. When there is a problem with communication between the Remote and Central, the LED on the Central will blink 2 times per second and the Remote LED will not light at all. Part Numbers: • SPX-2000 : Wiegand format (RS-485) • SPX-2100 : MagStripe format (RS-485) • SPX-2500 : Wiegand format (RS-232) • SPX-2600 : MagStripe format (RS-232) Typical 2-Wire Communications Installation Power Supply Line+ Line Pwr Gnd Remote 10,000 Ft Power Supply Pwr Gnd Central Cypress Computer Systems, Inc. 1778 Imlay City Road Lapeer, MI 48446 TX(810)245-2300 FX(810)245-2332 www.cypresscom.com Typical 4-Wire Communications Installation with Wiegand Reader Gnd +5vDC Data 0 Data 1 LED End of Line Device Wiegand Reader Line+ LinePwr Gnd Remote Power Supply 10,000 Ft. Door Strike Programming Resistor 12vDC Gnd Data 0 Data 1 LED Supervised Trouble Input Supervised Alarm Input Central Weigand Controller • The Controller's LED signal changes the state of the Door Strike relay. • The Controller's Supervised Alarm Input monitors the state of the End-of-Line Device. • If loss of power or communication occurs, the Supervised Trouble Input will activate. • The Programming Resistor 1 is used to calibrate the Remote Unit's Alarm Input 1 Sensor. (Any End-of-Line value from 100 Ω to 20KΩ can be monitored by using the same value for the Programming Resistor.) Cypress Computer Systems, Inc. 1778 Imlay City Road Lapeer, MI 48446 TX(810)245-2300 FX(810)245-2332 www.cypresscom.com Typical 4-Wire Communications Installation with MagStripe Reader SPX-2100 Series Gnd +5vDC Clock Data LED End of Line Device MagStripe Reader Line+ LinePwr Gnd Remote Power Supply 10,000 Ft. Door Strike Programming Resistor 12vDC Gnd Clock Data LED Supervised Trouble Input Supervised Alarm Input Central MagStripe Controller • The Controller's LED signal changes the state of the Door Strike relay. • The Controller's Supervised Alarm Input monitors the state of the End-of-Line Device. • If loss of power or communication occurs, the Supervised Trouble Input will activate. • The Programming Resistor 1 is used to calibrate the Remote Unit's Alarm Input 1 Sensor. (Any End-of-Line value from 100 Ω to 20KΩ can be monitored by using the same value for the Programming Resistor.) Cypress Computer Systems, Inc. 1778 Imlay City Road Lapeer, MI 48446 TX(810)245-2300 FX(810)245-2332 www.cypresscom.com SUPERVISED Status Monitoring Remote End of Line Device Programming Resistor Central Supervised Alarm Input Programming Resistor Remote Supervised Alarm Input Central End of Line Device Cypress Computer Systems, Inc. 1778 Imlay City Road Lapeer, MI 48446 TX(810)245-2300 FX(810)245-2332 www.cypresscom.com UN-SUPERVISED Status Monitoring SW2 SW1 Remote Switches (ie: Request-To-Exit, Door Sending Unsupervised Status from Remote to C Central SW2 SW1 Normally Op Contacts wil status of sw Remote SW2 SW1 Normally Open Contacts will follow status of switch Sending Unsupervised Status from Central to Rem Central SW1 GND SW2 LED Switches or Relay Contacts 211128 Cypress Computer Systems, Inc. 1778 Imlay City Road Lapeer, MI 48446 TX(810)245-2300 FX(810)245-2332 www.cypresscom.com