MA-COM SCF

Catalog 1308242
Issued 3-03
AGASTAT
SCF series
Programmable
Time Delay Relay
•
•
•
•
•
•
4 user-programmable timing modes
0.1 sec. to 10 hr. programmable timing range
Parameters set with recessed dials
Narrow width saves panel space
10A DPDT output relay
Socket can be DIN-rail or back panel mounted
File E15631(relay) and E140494 (socket)
File LR29186 (relay) and LR29513M7 (socket)
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Timing Modes
Input Data @ 25°C
Modes are user selectable via screwdriver adjustment of recessed 4position selector dial.
Modes offered are: On-Delay, Off-Delay, Interval and Latching Interval.
Voltage: See Ordering Information section for details.
Power Requirement: 2W, max.
Timing Specifications
Timing Ranges: 0.1 to 3 / 0.33 to 10 / 1 to 30 / 4 to 120 sec.; 0.33 to 10 /
1 to 30 / 2 to 60 min.; 0.33 to 10 hr.
Timing Range Selection: Screwdriver select via recessed 8-position
selector dial.
Timing Adjustment: External knob potentiometer adjustment with
reference calibrations.
Accuracy: Repeat Accuracy: ± 1% ± 0.01 sec.
Overall Accuracy: ± 3% ± 0.01 sec.
Reset Time: 30 ms.
Relay Operate Time: On-Delay and Interval mode: 55 ms.
Relay Release Time: Off-Delay, Interval and Latching Interval: 40 ms.
Transient Protection: Non-repetitive transients of the following magnitudes will not cause spurious operation of affect function and accuracy.
Operating Voltage
<0.1 ms
<1 ms
12VDC
1,000V
240V*
24VAC/VDC
1,000V
240V*
48 VAC/VDC
1,000V
480V*
120 VAC, 125VDC
3,000V
2,500V*
240VAC/VDC
3,000V
2,500V*
* Minimum source impedance of 100 ohm.
Environmental Data
Temperature Range: Storage: -40°C to +85°C.
Operating: -30°C to +65°C.
Contact Data @ 25°C
Mechanical Data
Arrangements: 2 Form C (DPDT).
Rating: 10A @ 28VDC or 120VAC, resistive; 1/3 HP @ 120/240VAC; 345VA.
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 500,000 operations, min., at rated resistive load.
Mounting/Termination: 11-pin octal-type plug for use with mating socket.
Mount relay in horizontal position (pins horizontal, knob down, LEDs up).
Status Indication: Power On LED and Output Contacts LED.
Weight: Relay: 3.5 oz. (156g) approx.; Socket: 1.7 oz. (48.3g) approx.
Initial Dielectric Strength
Between Terminals and Case: 1,000VAC plus twice the nominal voltage
for one minute.
Outline Dimensions
M3 X 0.5 CAPTIVE
CLAMP SCREWS
.84
(21)
CLEARANCE
HOLE FOR
M4 OR #8
MACHINE
SCREW
3.29
(84)
1.38
(35)
1.645
(42)
0.372 (10)
1.42
(36)
0.71
(18)
SCF TIMER
.21
(5)
.109 (3) DIA.
ANTI-ROTATION
PIN BETWEEN
TERMS 10 & 2
Ordering Information
RX
90
|
|
Series SCF |
Operating Mode
|
Plug-In
= Multiple Modes
| 90
Programmable
On-Delay
| Off-Delay
Timer
| Interval
| Latching Interval
|
SCF
|
Mounting
RX = Without Socket
RF = With Socket
BCSF11SC SOCKET
Wiring Diagram (Bottom View)
2
|
|
|
|
|
|
|
|
A
|
Output Rating
A = 10 Amp
B = 5 Amp
Output
A
|
|
|
|
|
|
|
|
Operating Voltage
(+10%, –15%)
2 = DPDT Relay
A = 120VAC, 50/60 Hz. / 125VDC
B = 240VAC, 50/60 Hz. §
E = 24VAC, 50/60 Hz. / 24VDC
F = 48VAC, 50/60 Hz. / 24VDC
Q = 12VDC
§ Voltage Option B is only
available with 5 Amp
output option.
Authorized distributors are likely to stock the following:
None at present.
Dimensions are shown for
1218 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.